Delta AHCPU560-EN2

Delta AHCPU560-EN2 – AH500 Redundant PLC CPU

The Delta AHCPU560-EN2 is the redundant PLC CPU in the Delta AH500 family. Two AHCPU560-EN2 units mount on separate main racks and synchronize over fiber. The Master CPU runs the process. The Standby CPU takes over when the switchover conditions are met. Typical applications include pumping stations, water treatment and continuous processes where downtime matters.

Program Capacity and Switchover Time

Program capacity is 1 million steps. Delta specifies up to 4,352 I/O points in single mode and 3,584 I/O points in redundant mode for I/O modules. Use the 3,584-point limit when sizing a redundant project.

Delta’s manual specifies CPU switchover within 20 ms following a Master CPU fault. Field outputs have a separate refresh time. The number of extension racks affects backplane output refresh, while network reconnection affects remote I/O recovery.

Redundant Racks and Communications

A minimum installation uses two CPUs, two main backplanes, two power modules, two optical transceivers and one synchronization fiber. Redundant main backplane options include the AHBP04MR1-5A, AHBP06MR1-5A and AHBP08MR1-5A. Select the AHPS05-5A or AHPS15-5A to suit the supply. Plan the rack and power arrangement separately if redundant power is required.

The CPU has two RJ45 Ethernet ports, one RS-232/RS-485 serial port, Mini USB and a microSD slot. Ethernet supports EtherNet/IP, DLR ring topology and Modbus TCP. A dedicated fiber port handles CPU-to-CPU data synchronization.

ISPSoft and Model Selection

Build the project in ISPSoft. In HWCONFIG, check the module layout of both main racks and verify firmware compatibility. Section 6.3 of Delta’s manual shows how to connect a PC over Mini USB. The AHCPU530-EN and AHCPU531-EN are standard Ethernet CPU options. Use the full AHCPU560-EN2 model code when selecting the redundant CPU pair.

Editor’s Note

When buying used, check for EN2 on the CPU label. Confirm which rack, optical transceivers and fiber are included.

Set up both racks side by side on the bench. Compare the module order and firmware compatibility with the project.

Once the fiber link is up, use ISPSoft diagnostics to verify the Master, Standby and synchronization status.

Run a controlled switchover test before production. Time the CPU switchover and remote I/O recovery separately.

Record when the HMI starts displaying fresh data again. That baseline helps distinguish CPU switchover delays from network reconnection delays during maintenance.

User Manual and PDF Files

AHCPU560-EN2 redundancy manual – English PDF. See section 3.1 for specifications, 3.2 for minimum hardware and 3.5 for switchover timing. For other documents, see the Delta AH PLC PDF files.

Related Topics

AH digital modules · AH analog modules · AH10EN-5A Ethernet module · EtherNet/IP diagnostics · Delta PLC software

Delta Automation · Delta PLC · Delta AH PLC series · Delta AH expansion modules