Delta AHCPU530-EN

Delta AHCPU530-EN AH500 PLC CPU with Ethernet

The Delta AHCPU530-EN is a main-backplane PLC CPU for the Delta AH500 series with a 256K-step program capacity. It has built-in 10/100 Mbit/s Ethernet, mini USB, an SD card slot and one serial COM port. Local I/O is added through backplane-mounted digital and analog modules.

Program memory and expansion capacity

With a suitable backplane and module layout, Delta specifies up to 4,352 local I/O points, 68 modules and one main plus seven extension backplanes. The data register range is D0–D65535. Plan AH expansion modules and AH power supplies together. Check total module load when selecting the AHPS05-5A or AHPS15-5A.

Related CPU models. The AHCPU530-RS2 also has a 256K-step capacity and uses two serial COM ports. The Ethernet-equipped AHCPU520-EN and AHCPU531-EN have capacities of 128K and 384K steps respectively. Check the exact CPU code, project type and ports in use before replacing a CPU.

ISPSoft, programming cables and communications

Use Delta ISPSoft for programming and online monitoring, and COMMGR to configure the communication driver. Delta lists the UC-PRG015-01A and UC-PRG030-01A for mini USB. Once the USB driver is installed, select USB (Virtual COM) in COMMGR and use that driver in ISPSoft. For Ethernet, check the CPU’s current IP address and the computer’s network settings.

Built-in Ethernet supports Modbus TCP. The single serial COM port provides RS-232, RS-422 or RS-485. Match the cable pinout and serial settings to the connected device. See the Modbus FAQ and AH communication modules for related options.

Hardware and ISPSoft manual

AH500 Hardware and Operation Manual · AHCPU530-EN · English PDF. Pages 40–41 cover capacity and ports, page 46 shows the front panel, and pages 333–335 show a mini USB and COMMGR connection example. See the Delta AH PLC PDF archive for related documents.

Editor’s Note

When buying a used CPU, check the full AHCPU530-EN code and inspect the Ethernet and mini USB connectors.
On the bench, start it with a compatible backplane and power supply and check the RUN, ERROR and BUS FAULT indicators.
Read the model and firmware in ISPSoft’s System Information window.
If you can access the existing project, back up the program, hardware configuration and TCP/IP settings before replacement.
Test the Ethernet and serial connections used by the project separately before fitting the CPU to the machine.