Delta AH500 redundant PLC

Delta AH500 Redundant PLC Systems

A Delta AH500 redundant PLC system transfers control to a ready standby CPU when the active CPU fails. The Delta AH500 architecture places the Master and Standby CPUs in separate main racks. A fiber link synchronizes system state and configured data between the CPUs. The CPU model in this category is the Delta AHCPU560-EN2.

CPU pair, backplanes and power supplies

Delta’s minimum CPU redundancy configuration uses two AHCPU560-EN2 CPUs, two main backplanes, two power modules, two optical transceivers and one fiber synchronization cable. For designs that require dual power modules in each rack, Delta lists the AHBP04MR1-5A, AHBP06MR1-5A and AHBP08MR1-5A redundant main backplanes. Power options include the 100–240 V AC AHPS05-5A and the 24 V DC AHPS15-5A. See Delta AH power supplies and Delta PLC accessories for rack and power selection.

Redundant expansion and remote I/O

The AHBP06ER1-5A and AHBP08ER1-5A are six- and eight-slot redundant extension backplanes. Use the manual’s Appendix B compatibility table to check which digital I/O, analog I/O and temperature measurement modules can be installed in redundant mode. Browse the module groups under AH expansion modules.

Choose the RTU, industrial communication protocol and network topology together. Delta shows DLR ring and star topologies with compatible EtherNet/IP devices. See AH communication modules for network cards and remote station options.

CPU switchover and ISPSoft configuration

Delta specifies CPU switchover within 20 ms following a Master CPU fault. For remote I/O controlled by the Master CPU, the manual specifies under two seconds. Remote output refresh depends on network reconnection. During acceptance testing, measure CPU switchover, field I/O and HMI communication separately.

Configure redundancy in HWCONFIG in ISPSoft. Use COMMGR to manage the PC connection. During commissioning, verify the hardware and firmware pairing, Master/Standby roles, synchronization status and remote station connections. See Delta PLC software for other engineering tools.

Manual and PDF archive

AH500 Redundancy System Operation Manual (EN) · PDF page 35 covers minimum hardware, page 42 covers switchover timing, and Appendix B starts on page 199 with rack and module compatibility. See the redundant CPU table in the Delta AH catalogue or browse Delta AH PLC PDF files for other series documents.

Editor's Note

When reviewing a used set, check that both CPU nameplates read AHCPU560-EN2.

Check for both main racks, the power modules, optical transceivers and fiber cable. Match the transceivers to the fiber type.

Record the backplane codes. Pay particular attention to the MR1 main rack and ER1 extension rack designations.

On the bench, use ISPSoft diagnostics to confirm that the Standby CPU is ready and synchronized.

During a planned switchover test, watch the CPU role, the furthest field station and the HMI alarms together. Record the actual recovery time as part of machine acceptance.