Delta AHPS15-5A
Delta AHPS15-5A – 24 V DC input AH PLC power supply
Delta AHPS15-5A is a power supply installed on compatible AH series PLC backplanes to provide internal power for the CPU and modules. It operates from a 24 V DC input; its backplane output is rated 24 V DC, 1.5 A, with a maximum output power of 36 W. The “5A” suffix in the model code does not specify a 5 A output. This unit belongs to the Delta AH power supplies group.
Input, output and power budget
Input voltage tolerance: −35% / +30% relative to 24 V DC. Momentary power interruption rating: 10 ms in the manufacturer's specification table. Protection functions: short-circuit, overcurrent and overvoltage protection. The interruption rating does not provide extended battery backup. Check the external 24 V supply for voltage stability under load and adequate startup current capacity.
The 36 W rating is used for the rack's internal power budget. Add the specified consumption of the CPU, digital I/O, analog and communication modules using the applicable hardware manual. For example, a rack containing an AHCPU501-EN or AHCPU531-EN must account for the individual consumption of its AH digital modules, AH analog modules and AH communication modules. External power for sensors, valves and other field loads must be assessed separately. The input terminal block is not a general-purpose 24 V distribution output.
+24V / 24G versus VS+ / VS−
+24V and 24G are the main DC power input terminals. VS+ and VS− are sensing inputs used to monitor an external 24 V supply; they do not replace the main power input. In the manufacturer's wiring diagram, FG connects to the control cabinet's functional ground, while FE connects to the DC supply's ground. NC is unused. Follow the specified grounding arrangement and do not arbitrarily bridge 24G, FG and FE.
Delta's AH series guidance identifies SR731 for examining the supply monitored through the VS inputs and the I34 interrupt task for low-voltage detection. Check the system register and interrupt definitions for the actual CPU before implementing this function. Delta ISPSoft is used for CPU programming and diagnostics; the AHPS15-5A does not require a separate user program.
Backplane, installation and model comparison
In a supported AH configuration, the AHPS15-5A occupies the dedicated power supply slot at the left side of the backplane. Check main and extension rack arrangements under Delta AH PLC series, and motion configurations under AH motion controllers and AH Motion backplanes. For backplanes such as AHBP03M2-5A, AHBP05M2-5A and AHBP07M2-5A, verify the CPU, module arrangement and total power consumption together. A higher slot count does not increase the power supply's wattage rating.
Dimensions: height 110 mm, width 50 mm, depth 103 mm. The front green POWER indicator provides an initial supply status check; it does not establish that the entire rack is healthy. The related AHPS05-5A is rated for 100–240 V AC, 50/60 Hz input and 60 W output power. Keep these ratings separate from the AHPS15-5A's 24 V DC input and 36 W output power. Recheck the input wiring and rack power budget when considering a replacement.
Editor's Note
Start with the complete label. The AHPS15-5A requires a DC input. A similar-looking AHPS05-5A does not justify using the same supply wiring. Photograph the terminals and wire numbers before removal to make the replacement straightforward.
Measure the voltage at the module's own power input under load. A loose terminal or long cable can cause voltage loss even when the upstream supply measures correctly. Voltage at VS+ / VS− alone does not confirm a sound +24V / 24G power connection.
Disconnect power before inspecting the backplane contacts. Look for discoloration, oxidation, loose mounting and damaged plastic. Replacing only the power supply leaves a poor contact unresolved and may cause the replacement to overheat as well.
If the rack shuts down as its load increases, isolate the cause in stages. Assess the external 24 V source, the AHPS15-5A and the module load separately. A controlled test starting with the minimum configuration permitted by the manufacturer can help identify overload or a faulty module. Remove or install modules with power disconnected.
For used equipment, ask for more than a lit POWER indicator. Request load testing from cold and after warm-up. Following repair, check voltage stability and ripple with suitable measurement equipment. Bridging a fuse or increasing its rating does not correct the fault that caused it to open.
Check the machine's behavior when power returns. Review CPU restart conditions, retained data and output permissions in the PLC program. Complete the replacement with a controlled stop and restart test to catch recovery problems before returning the machine to service.
PDF and software documents
Use Delta PLC accessories PDF and software files for wiring diagrams, specification tables and related software documents. Select CPU and rack documentation from Delta PLC and HMI manuals. Match the AHPS15-5A designation and the installed hardware revision when choosing a document.
Related topics
Browse power units and connection hardware under Delta PLC accessories. Calculate field power separately when using Delta AH external terminals; loads connected through terminal assemblies must not be confused with the rack's internal power consumption. Main model information page: Delta AHPS15-5A.
External references
Delta AH series manufacturer catalogue · Delta AH Motion Controller Hardware Manual · Delta AH500 hardware manual and power supply specifications · Delta AH series VS input guidance