Delta AHPS05-5A

Delta AHPS05-5A

Delta AHPS05-5A is an AH-series rack power supply with a 100–240 V AC, 50/60 Hz input. Its 24 V DC output, maximum 2.5 A / 60 W, powers the system through the backplane. The manufacturer specifies this output for the backplane only; do not treat the front terminals as an external 24 V sensor-supply output.

AC input and VS monitoring terminals

L/N are the AC mains input. VS+ and VS− monitor a separate external 24 V DC supply. These terminals are not the DC output generated by the module. Connecting 110/220 V AC to them damages the PLC. LG is line ground, FG is functional ground, and NC is a no-connection terminal. Match the wiring to the markings on the actual unit.

Delta's AH-series application explanation identifies SR731 and the I34 low-voltage detection interrupt task for external 24 V monitoring. Verify support for the CPU, firmware and rack configuration used in the Delta ISPSoft project. Program the alarm and stopping response for the machine; wiring VS alone does not establish an automatic safety-stop function.

Rack consumption and system selection

For Delta AH500 applications within the Delta AH PLC series, total the backplane consumption of the CPU and installed modules. Check an AHCPU530-EN or AHCPU530-RS2 against the appropriate standard AH500 rack. A 60 W rating does not establish suitability for every slot arrangement or module combination.

When adding Delta AH expansion modules, include the documented consumption of AH digital modules, AH analog modules, AH temperature / motion modules and AH communication modules. Assess the separate supply requirements of field devices independently of the rack's internal power budget.

The AHBP03M2-5A, AHBP05M2-5A and AHBP07M2-5A in the Delta AH Motion backplanes group require the appropriate AH Motion controller. Do not treat these M2 backplanes as standard AHCPU/RTU backplanes. Sharing a power-supply model does not make controllers and backplanes interchangeable.

Difference from AHPS15-5A

Delta AHPS15-5A is a 24 V DC-input, 36 W power supply. AHPS05-5A is the AC-input, 60 W model. Check input type, terminal functions and rack consumption together during replacement. Compare alternatives under Delta AH power supplies.

Installation, protection and testing

The manufacturer housing drawing shows 50 mm width, 110 mm height and 103 mm depth. Allow separately for the indicated connection projection and cable space. Check the backplane connector, mounting and ventilation clearance. Disconnect power and verify absence of voltage before removal or wiring changes.

The output has short-circuit and overcurrent protection. The specification table lists a 4 A / 250 V AC fuse; verify its other characteristics against the relevant hardware documentation before replacement. This rating does not directly specify the control panel's incoming protective device. Test PLC restart and retained-data behaviour after power interruption as part of the application.

PDF and technical documentation

Start document selection at Delta PLC accessories files. In the archived 2016 AH Motion Hardware Manual, PDF pages 53–54 / printed 3-21–3-22 cover ratings and the housing; PDF page 56 / printed 3-24 explains terminal functions; and PDF page 156 / printed 4-20 covers wiring. PDF page 38 / printed page 37 of the 2024 AH catalogue compares AC- and DC-input supplies. Use these page references with the matching document edition.

Editor's Note

Identify L/N and VS before touching the wiring. Photograph the original connections before removal. Measuring 24 V at VS does not prove that the module supplies voltage there; it may be coming from the separate field supply.

A lit POWER indicator does not prove the supply is healthy. Complete testing with the actual CPU and module load. For intermittent restarts, investigate AC-input dips, rack consumption and connector contact together.

If the problem began after adding a module, update the power calculation. Inspect modules and connections with power disconnected, keeping a record of the arrangement. Random CPU replacement can prolong a fault caused by excessive consumption or a damaged connection.

Do not increase the rating of a blown fuse. With power disconnected, inspect burn marks, loose terminals and input-stage shorts. Replacing the fuse alone does not establish a completed repair without identifying the cause.

Record both cold and warmed-up operation when testing a used supply. If external 24 V monitoring is used, verify the alarm and machine response to voltage loss. Include the CPU code, backplane and installed modules in the test record.

Related topics

Browse supporting hardware under Delta PLC accessories and system documentation under Delta PLC and HMI manuals.

External references: Delta AH Motion Hardware Manual — 2024, English · Delta AH manufacturer catalogue — 2024, English · Delta VS+/VS− monitoring explanation.