Delta AH Motion backplanes

Delta AH Motion backplanes

Delta AH Motion backplanes provide the mounting positions and backplane bus connections for an AH Motion CPU, power supply and supported AH500 modules. Motion programs run in the CPU; the backplane provides the physical and electrical interconnection. See Delta AH PLC series and Delta AH motion controllers for the associated product families.

AHBP03M2, AHBP05M2 and AHBP07M2

Delta AHBP03M2-5A is an AH Motion backplane with 3 additional module slots.

Delta AHBP05M2-5A provides 5 additional module slots.

Delta AHBP07M2-5A provides 7 additional module slots.

These counts refer to additional module positions excluding the dedicated power supply and Motion CPU positions. They do not indicate the number of motion axes. Plan the required modules, any spare service positions and cabinet mounting dimensions together.

Motion CPU and AH500 module compatibility

The CPU position on an M2 Motion backplane is specified for AHxxEMC-5A controllers, including Delta AH08EMC-5A, Delta AH10EMC-5A and Delta AH20EMC-5A. Do not assume that a standard Delta AH500 CPU or RTU module can occupy this position. M1, MR1 and M2 backplane codes identify different system arrangements.

Select Delta AH expansion modules against the Motion CPU's supported module list. Check Delta AH digital modules, Delta AH analog modules, Delta AH temperature and motion modules and Delta AH communication modules for their individual functions and addressing requirements. Membership of the same product family alone does not establish support.

The manufacturer states that the compact motion control system using this type of Motion backplane does not support an expansion backplane. Standard AH500 rack expansion capabilities should not be carried over to this arrangement. Field devices connected through EtherCAT form a separate network layer.

Power supply and serial connection

See Delta AH power supplies, including AHPS05-5A and AHPS15-5A, when selecting the supply arrangement. Account for the combined consumption of the CPU, backplane and installed modules, and assess external field power separately. An available slot does not establish that sufficient power capacity remains.

The AH Motion hardware manual identifies a terminal-block COM2 / RS-485 connection on AHBP03M2-5A and AHBP05M2-5A. Treat this separately from the CPU's Ethernet and EtherCAT interfaces, and check pin assignments and serial settings against the applicable hardware diagram.

Editor's Note

When ordering a replacement, record the complete backplane label, particularly M2 and the final suffix. Photograph the existing backplane, CPU and power supply together. A visually similar AH500 backplane may belong to a different system arrangement.

If a module is missing from the configuration, first back up the program, hardware configuration and slot order. Moving a module can affect addressing. Preserve the existing arrangement while checking connectors, module latches and supply voltage.

Disconnect system and external field supplies before removing the backplane. Inspect connectors for bent contacts, corrosion, heat damage and loose mounting. Do not force contacts into position with metal tools or insert material into connectors to restore contact pressure.

If several modules disappear together, investigate common power and backplane bus connections as well. Avoid assuming that a single module is responsible. Measure and change one item at a time; where possible, compare with a known-good part of the same code and record the result.

For a used backplane, inspect both sides of the board, mounting points and every slot. Record missing screws, broken housings and repair marks. Where testing is available, use an appropriate CPU and modules to check startup, slot detection and stable operation.

PDF manuals and hardware configuration

Use Delta PLC accessories files for model documentation and Delta PLC and HMI manuals for system manuals. In an AH Motion CPU project, the HWCONFIG arrangement in Delta ISPSoft must match the actual backplane and module order. Configure the computer connection through Delta COMMGR according to the CPU and connection method.

Related topics

Delta AH I/O cables · Delta AH external terminals · Delta EtherCAT cables · Delta PLC accessories

Browse controllers in the Delta PLC category and available equipment under second-hand Delta products.

External references: Search the Delta Download Center using the complete model code for manufacturer documentation.


Refine Search