Delta AHRTU-ETHN-5A
Delta AHRTU-ETHN-5A Ethernet Remote I/O Adapter
The Delta AHRTU-ETHN-5A is an Ethernet remote I/O adapter for the Delta AH PLC series. It connects compatible digital I/O and analog I/O modules in a remote rack to the host controller. It supports EtherNet/IP and Modbus TCP. The two RJ45 ports, X1 and X2, support 10/100 Mbps auto-detection and Auto MDI/MDIX.
A typical installation uses this module to bring sensor and valve signals from a remote section of a machine into the main PLC. The host controller runs the PLC program. On EtherNet/IP, the Scanner initiates the connection. The AHRTU-ETHN-5A acts as the Adapter for the attached AH expansion modules.
Ethernet Connection and Commissioning
Ports and IP addressing. Connect a CAT 5e network cable to X1 or X2. The unit supports BOOTP, DHCP and NTP. The two front selectors can set the last octet of an address in the documented 192.168.1.x range in hexadecimal. For example, 1A selects 192.168.1.26. Use the documented 00 setting when assigning the project address through EIP Builder.
EtherNet/IP setup. In Delta’s examples, EIP Builder in ISPSoft defines the network connection and data mapping, while HWCONFIG defines the remote rack’s module layout. The manual shows connections with supported firmware on the AHCPU5x1-EN family, including the AHCPU521-EN, and with the AHCPU560-EN2. For a third-party Scanner, verify the applicable EDS file and the input and output data sizes. For Modbus TCP, check the client addresses and data types against the station’s mapping.
Rack and field connections. Check the station backplane, module order and AH power supply together. Field signals terminate at the corresponding I/O module. Select Delta AH I/O cables and AH external terminals by the complete module code.
Manuals and PDF Downloads
Delta AH500 Hardware & Operation Manual (PDF, English) · April 12, 2023. Section 2.11 covers remote I/O specifications and indicators. Section 4.12.3 covers Ethernet wiring and IP addressing.
Delta EtherNet/IP Operation Manual (PDF, English) · May 13, 2019. Section 3.2.3 gives EtherNet/IP specifications for the adapter. Section 4.6 provides AH remote I/O connection and mapping examples.
Editor’s Note
When buying used, read the entire AHRTU-ETHN-5A code on the label. Similar housings are used for different field networks.
Test X1 and X2 individually. Inspect the RJ45 latch slots, backplane connector and address selectors as well.
Photograph the selector positions and module order before removing the unit. That record comes in handy when preparing the replacement.
Once the link indicator comes on, check the MS, NS and I/O indicators and the Scanner’s connection status. The physical link can be healthy while the slot layout or data sizes are wrong.
On the bench, confirm that one input reaches the expected PLC address. With field loads disconnected, check that a test output maps to the intended channel.