Delta AHRTU-PFBS-5A

Delta AHRTU-PFBS-5A PROFIBUS DP remote I/O module

The Delta AHRTU-PFBS-5A connects Delta AH500 I/O modules to a PROFIBUS DP network as a remote I/O slave. The DP master reads inputs and sends output data through this station. The rack accepts supported digital I/O, analog I/O and temperature measurement modules.

Communication, rack and capacity

The module uses high-speed RS-485 over DB9 with shielded twisted-pair PROFIBUS cable. It automatically detects rates up to 12 Mbit/s. DP-V0 cyclic exchange supports up to 244 bytes in each direction. DP-V1 supports acyclic parameter reads and writes when available on the master.

Use an AHPS05-5A power supply and a suitable AH main rack. A station supports one main rack and up to seven extension racks. Delta specifies a maximum of 48 I/O modules. The usable count depends on the data length and parameter area of the selected expansion modules.

PROFIBUS node address, DB9 and GSD setup

Set node address 1–125 in hexadecimal using the two front rotary switches. For example, decimal 26 equals 1A. Set the high digit to 1 and the low digit to A. An address changed while the station is powered takes effect after a power cycle.

On the DB9 connector, pin 3 is B / P, pin 8 is A / N, pin 5 is DGND and pin 6 is VP (+5 V). VP supplies the connector termination circuit. Check the termination at both physical ends of the bus and check the shield connection.

Import the DETA09B9.GSD device description into the DP master’s configuration tool. See Delta GSD device description files for the file type. Match the station address, module types and physical slot order to the project. With a Delta AH10PFBM-5A master, use ISPSoft for the CPU hardware configuration. Chapter 14 of the module manual shows an example setup.

Manual and PDF

AH500 Hardware and Operation Manual — English PDF. See section 4.12.2 for the AHRTU-PFBS-5A DB9 wiring and rotary address switches. Browse the Delta AH PLC PDF archive for related documents.

Editor’s Note

Before buying used, read the entire part number. The AHRTU-PFBS-5A manages a remote I/O station. The AH10PFBS-5A is a PROFIBUS slave card for a station with an AH CPU.

Inspect the DB9 pins, screw threads and both address switches. A bent pin or loose connector can produce an intermittent bus fault.

Start on the bench with an AH main rack, a suitable power supply and one I/O module. Read an input from the DP master and verify an output with a test load isolated from the machine.

Record the RUN and NET LEDs and the seven-segment display together. If cyclic exchange does not start, check for a duplicate address, confirm termination and compare the slot order in the master project.

If the bus is online but signals appear on the wrong channels, compare the slot order and byte offsets with the original project. Moving one module can shift later addresses.

Related topics

In the AH communications range, the AHRTU-DNET-5A is for DeviceNet and the AHRTU-ETHN-5A is for EtherNet/IP and Modbus TCP. See the Delta device description files for the different network file types.

AHBP03M2-5A main rack · AH external terminals · Delta PLC accessories

Delta AH PLC series · Delta PLC · Second-hand Delta equipment