Delta AH10PFBM-5A

Delta AH10PFBM-5A PROFIBUS DP Master Module

The Delta AH10PFBM-5A adds PROFIBUS DP Class 1 master functionality to a Delta AH500 PLC system. It collects input data from field stations and sends PLC output data back to those stations. A production line can use the network to control remote I/O and drives with compatible PROFIBUS DP interfaces. Delta AH communication modules.

Master and field stations. The AH10PFBM-5A manages cyclic data exchange on the network. The AH10PFBS-5A connects an AH PLC as a slave. The AHRTU-PFBS-5A connects a remote I/O rack, while the DVPPF02-SL connects a supported DVP Slim PLC to PROFIBUS DP.

User manual

AH10PFBM-5A user manual (PDF) · English, Chapter 12. Start at PDF page 562 for main-rack installation, DB9 wiring, SYCON.net setup, I/O mapping and diagnostics. All Delta AH PLC PDF files.

Specifications and wiring

Protocol and data capacity. The module supports 9.6 kbps to 12 Mbps. DP-V0 handles cyclic I/O exchange. DP-V1 supports acyclic parameter reads and writes on compatible field devices. Configurable capacity is 2,880 input words and 2,880 output words. Delta’s product catalogue lists 124 slave stations, while the module manual lists 125. For projects near that limit, verify the capacity against the module revision and applicable manual.

Rack mounting. The module fits an I/O slot on the AH500 main rack and draws 5 V DC from the backplane. Power consumption is 2 W. The manual shows the AHPS05-5A in the POWER slot. See AH expansion modules and AH power supplies for rack components.

PROFIBUS DP port. Use shielded twisted-pair cable and a DB9 RS-485 connection. Pin 3 is B (P), pin 8 is A (N), pin 5 is DGND and pin 6 is VP. Enable termination at both physical ends of the segment. The permitted cable length depends on the selected bit rate. See the PROFIBUS DP section of the Delta PLC/HMI Cable Selection Guide.

SYCON.net, ISPSoft and I/O mapping

Use SYCON.net to set the master station address, bus rate and slave I/O layout. Delta’s example downloads the network configuration through the module’s CONF port. Select the GSD file or corresponding DTM for the exact field device model and revision. Delta device description files.

On the PLC side, check the module slot and data exchange area in the ISPSoft hardware configuration. The manual’s USB example uses COMMGR for the PC-to-CPU connection. The master input area holds data received from field devices. The master output area holds data sent to them. Delta PLC software.

Editor’s Note

Check for PFBM on the nameplate when buying a used card. The PFBS model serves a different role on the same network.

Before swapping a working module, back up the SYCON.net project, PLC hardware configuration and slave address list.

On the bench, inspect the DB9 screws, CONF port and backplane connector. Test communication with a known-good slave.

If one station drops out, compare its address and selected GSD I/O length with the project. If several stations drop out together, inspect the segment terminations and connectors.

Record the RUN, SYS and DP LEDs together with the seven-segment display. The display can alternate between an error code and the affected station number.

Related topics

AH10DNET-5A DeviceNet · AH10COPM-5A CANopen · AH10EN-5A Ethernet · Delta PLC accessories.

Delta AH PLC series · Delta PLC models · Second-hand Delta.

External references

Delta AH500 Module Manual, Chapter 12 (distributor copy).