Delta TAP-CN01
Delta TAP-CN01 — CANopen / DeviceNet Trunk and Drop Distribution Box
Delta TAP-CN01 is a passive distribution box connecting a trunk and one drop cable in a CANopen or DeviceNet network. It has two trunk connections and one drop connection. Delta’s 1 for 2 catalogue description corresponds to trunk continuation through TB1/TB2 and a single drop at TB3.
This unit in the Delta DVP other accessories range includes a switchable 121 Ω terminating resistor. It does not regenerate signals, convert protocols or extend network distance limits. It is not an active repeater or Ethernet switch.
TB1, TB2 and TB3 connections
| Terminal | Connection role |
|---|---|
| TB1 | Trunk connection |
| TB2 | Trunk continuation |
| TB3 | Single drop connection |
Delta’s circuit diagram assigns TB1/TB2 to the trunk and TB3 to the drop. Connections use removable terminal blocks with 5.08 mm pitch. The trunk/drop arrangement does not permit unrestricted star wiring; preserve the required network topology.
V+, H, S, L and V− terminals
| Marking | Function | DeviceNet colour reference |
|---|---|---|
| V+ | Network supply + | Red |
| H | CAN_H data line | White |
| S | SHIELD | Shield / drain conductor |
| L | CAN_L data line | Blue |
| V− | Network supply 0 V | Black |
The colours refer to the manufacturer’s DeviceNet wiring example. Do not assume identical colours in another CANopen cable. The table explains signal markings; confirm physical terminal order from the board. Copying the TB1/TB2 orientation onto TB3 can cause incorrect wiring.
The instruction sheet specifies 11–25 V DC for DeviceNet, supplied through the network power conductors. TAP-CN01 is not a power supply or voltage converter. Keep V+ and V− distinct from the data lines and do not use the S shield terminal as an arbitrary supply return.
Termination switch: ON and OFF
Select ON at a physical trunk end and OFF at an intermediate position. Terminate the two trunk ends, not every distribution point or drop end. Adding another resistor where internal termination is already enabled creates excessive loading. TAP-TR01 is a separate terminator; account for all enabled terminations together.
Delta’s TAP-CN01/02/03 instructions limit a drop cable to 6 m. This does not establish that a 6 m drop is suitable at every speed or in every network. Also check any stricter protocol limits for baud rate, cumulative drop length and cable type.
Differences from TAP-CN02 and TAP-CN03
TAP-CN02 provides two trunk connections and three terminal-block drop connections. TAP-CN03 is a different model with three RJ45 drop connections. TAP-CN01 has one drop, so do not confuse it with these multiple-drop arrangements. Define the required drop count and connector type when selecting Delta network connectors.
Cables and controller-side devices
Review UC-DN01Z-01A and UC-DN01Z-02A under Delta industrial network cables. The CANopen cable range includes RJ45 options such as UC-CMC003-01A, UC-CMC010-01A and UC-CMC030-01A. An RJ45 plug cannot connect directly to TAP-CN01’s terminal blocks.
Related controller pages include DVPCOPM-SL for DVP PLCs, AS-FCOPM for AS PLCs and AH10COPM-5A for AH PLCs. Distinguish the physical distribution box from the master/slave communication module.
Editor’s Note
Passive hardware still needs careful wiring. When replacing a removable terminal block, compare V+, H, S, L and V− individually. A connector that fits is not proof of correct conductor order.
If connecting one drop disrupts the whole network, isolate that drop first. A crushed cable, an H/L short or supply voltage on a data terminal can affect an otherwise healthy trunk.
With power disconnected, resistance between H and L can provide an initial check. Two 121 Ω terminations in parallel give an ideal 60.5 Ω. A reading near 60 Ω is useful, but it does not prove complete network health.
If trouble began after adding a box, check its termination switch. An intermediate box left ON can introduce a third termination. Disabling every resistor without identifying the trunk ends is not a solution either.
On used units, inspect terminal sockets, screw tightness, copper tracks and switch contacts. A single loose shield strand touching an adjacent power or data terminal can create an intermittent fault.
The manufacturer shows mounting on a 35 mm DIN rail. Secure the box inside the cabinet, support cable weight and keep data wiring away from motor power bundles. Record cable and terminal markings before disconnecting plugs.
PDF, software and related topics
Use the Delta PLC accessories PDF and software files page for wiring diagrams. TAP-CN01 has no programming software of its own. Tools such as CANopen Builder configure the relevant network devices. Further documents are available under Delta PLC and HMI manuals.
Navigation: TAP-CN01 main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta TAP-CN01/02/03 Instruction Sheet — 5011667500-TN00 · Delta PLC/HMI Cable Selection Guide — 4-12 / 4-13 / 4-14 · Delta AH Catalogue — Distribution Boxes · ODVA — DeviceNet Cable System Planning and Installation Manual