Delta UC-DN01Z-02A

Delta UC-DN01Z-02A

Delta UC-DN01Z-02A is a thin, shielded industrial communication cable with a PVC jacket, used in DeviceNet networks. Delta's cable selection guide specifies 2 × AWG22 + 2 × AWG24, SHLD PVC (Thin). In a DeviceNet installation, the cable carries network power alongside the data pair. It belongs to the Delta industrial network cables group and differs from the thick UC-DN01Z-01A in conductor sizes and permitted network distances.

Delta catalogues list a 305 m roll and ordering by the metre. 305 m is not the permissible length of one DeviceNet network. The cable can serve as a trunk or drop line under the applicable conditions. Selection must consider communication distance, individual and cumulative drop lengths, network load and voltage drop. Delta also lists it for suitable CANopen applications; connection and commissioning requirements remain specific to each protocol.

Conductors and DeviceNet terminal assignment

The power pair is AWG22 and the data pair is AWG24. DeviceNet colours are red for V+ (24 VDC), black for V− (0 V), white for CAN_H, blue for CAN_L, plus the shield connection. The shield must not replace the negative power conductor.

The five-pole DeviceNet terminal shown in Delta's guide is assigned 1: V−, 2: CAN_L, 3: SHIELD, 4: CAN_H, 5: V+. Do not transfer these numbers directly to a different M12 or RJ45 connector; check the actual port diagram. The DeviceNet V+ assignment must not automatically be carried over to a CANopen application either. See Delta network connectors for related connection hardware.

DeviceNet network and drop length limits

The stated end-to-end distance limit for thin UC-DN01Z-02A is 100 m at 125, 250 and 500 kbit/s. The 500 m or 250 m figures specified for thick UC-DN01Z-01A do not apply to thin 02A cable. Mixed thick/thin installations require their cable sections to be calculated according to the relevant network design rules.

The maximum distance from the trunk to a device on an individual drop is 6 m. Cumulative drop budgets are 156 m at 125 kbit/s, 78 m at 250 kbit/s and 39 m at 500 kbit/s. These are separate constraints: the cumulative budget does not permit a longer individual drop, and drop distances cannot be disregarded when checking end-to-end network distance.

Termination, distribution and network power

DeviceNet requires 121 Ω termination between CAN_H and CAN_L at the two physical ends of the trunk. Delta specifies a resistor rating of 1/4 W. Do not add termination at every device or drop end. With distribution hardware such as TAP-CN01, TAP-CN02 and TAP-CN03, account for the wiring arrangement and any built-in termination. Check physical connector compatibility when selecting TAP-TR01 as well.

A suitable communication distance does not establish an adequate power supply. Calculate total device current, cable length, power feed location and voltage drop in the AWG22 power conductors. Measure voltage at the remote node while devices are operating. Do not assume the current capacity of thick cable applies to thin cable; follow the manufacturer's network shielding and earthing rules.

Use with Delta DeviceNet devices

Devices with DeviceNet interfaces, including DVPDNET-SL, AS01DNET-A, AH10DNET-5A, RTU-DNET and AHRTU-DNET-5A, require suitable terminals and a correctly designed network. The cable does not perform protocol conversion. It is also a different product from UC-PF01Z-01A PROFIBUS cable. Consult the device documentation and Delta DeviceNet Builder information for network configuration; no software is installed in the passive cable itself.

Editor's Note

A 305 m roll does not mean the network can run for 305 m. Packaging length and communication limits are different. Draw the trunk and every drop first, then check the design against the selected data rate.

For intermittent network faults, check more than CAN_H and CAN_L. Seeing 24 V at the supply is insufficient; measure the furthest device's voltage under load. Voltage drop can make healthy cable and communication hardware appear faulty.

Check resistance with network power removed. If two 121 Ω terminators are correctly connected in parallel, approximately 60 Ω is expected between CAN_H and CAN_L. This alone does not prove the network is healthy; it is a useful clue when investigating open wiring or missing or excessive termination.

If a fault begins after adding a drop, check its length and conductor order at the connector. Also verify matching data rates and unique node addresses among devices on the same DeviceNet segment.

For used or cut-length cable, inspect the jacket marking, crushed sections and joints. Continuity can be checked with the cable suitably disconnected; do not apply an insulation tester with device electronics connected. Moving cable carrier use requires separately documented suitability.

Do not leave temporary splices as a permanent repair. Correct sections with excessive exposed shielding, unnecessarily untwisted data pairs or poor routing alongside power wiring. Sound connections and the correct topology are more useful than repeated cable replacement.

PDF documents, cable selection and software

Use our Delta PLC accessories PDF and software files page for supporting documents. Read the DeviceNet wiring and cable section of the Delta PLC/HMI Cable Selection Guide together with the connected module's manual and ODVA distance rules. General documents are available under Delta PLC and HMI manuals.

Related subjects

UC-DN01Z-01A thick cable · Industrial network cables · CANopen cables · UC-PF01Z-01A PROFIBUS cable · Network connectors · TAP-CN01 · TAP-CN02 · TAP-CN03 · TAP-TR01

DVPDNET-SL · AS01DNET-A · AH10DNET-5A · RTU-DNET · AHRTU-DNET-5A · DeviceNet Builder

Navigation: Delta PLC accessories · Delta DVP PLC series · Delta AS PLC series · Delta AH PLC series · Delta PLC models · Used Delta products · PDF and software files

External references

Delta PLC/HMI Cable Selection Guide – cable construction, colours and termination · Delta AS catalogue – UC-DN01Z-02A Thin / Drop cable · ODVA DeviceNet Technology Overview – topology and distance limits