Delta UC-PF01Z-01A

Delta UC-PF01Z-01A PROFIBUS-DP Communication Cable

Delta UC-PF01Z-01A is a cable for the copper communication link of a PROFIBUS-DP network. It belongs to the Delta industrial network cable range. It provides no protocol conversion, station addressing or additional PLC communication capability by itself; suitable PROFIBUS hardware is required at the connected devices.

The manufacturer lists the construction as 1PR #22 AWG FRFPE FRPE; 1PR denotes one data pair. Prepare the required field length and fit suitable network connectors. Specify the complete model, required length and whether connectors are included when ordering.

Ordering length and segment length

The Delta MS300 catalogue lists 305 m. An older PLC/HMI cable guide shows 200 m in its table but describes metre-based ordering from 1 to 305 m in its note. Because these entries differ, confirm the supplied length on the quotation.

Reel length is not the permitted PROFIBUS segment length. PI’s Type-A RS-485 cabling table gives 200 m at 1.5 Mbit/s and 100 m at 3–12 Mbit/s. Check cable class, speed, device limits and any repeaters together. A cable cut from a 305 m reel cannot automatically be used as a 305 m segment at every speed.

Connector selection and DB9 signals

Delta’s selection guide lists the male DB9 PROFIBUS connectors UN-03PF-01A, UN-03PF-02A and UN-03PF-03A. UN-03PF-02A also has a female DB9 programming connection. Check cable entry direction and available mounting space for the selected connector.

The following signals apply to the standard PROFIBUS RS-485 DB9 interface. Bond the shield using the connector’s shield clamp and preserve the data-pair twist during assembly. Confirm whether the pin drawing shows the mating face or the wiring side.

DB9 pin Signal Function
3 B / RxD-TxD-P Data + / red
8 A / RxD-TxD-N Data − / green
5 DGND Data reference
6 VP / +5V Termination supply

Termination and network devices

Enable termination only at the two physical ends of each segment. Leave it disabled at intermediate stations. On some connectors, the termination switch also disconnects the outgoing cable; check IN/OUT markings against the manufacturer’s diagram. Use a suitable PROFIBUS termination circuit rather than fitting an arbitrary single resistor.

For DVP PLCs, DVPPF01-S is an example of a PROFIBUS-DP slave module. In AH PLC systems, AH10PFBM-5A is a master, AH10PFBS-5A is a slave and AHRTU-PFBS-5A is a PROFIBUS remote I/O communication module. Verify the port, connector, station address and device GSD file as well as the cable.

Differences from other Delta network cables

UC-DN01Z-01A and UC-DN01Z-02A are DeviceNet cables. UC-EMC003-02A belongs to the Ethernet/EtherCAT range, while UC-CMC003-01A is a CANopen cable. These are not direct UC-PF01Z-01A substitutes; EtherCAT cables and CANopen cables serve different network connections.

Editor’s Note

If communication drops intermittently, do more than move the cable until it works again. With power isolated, inspect crushed sections, loose data conductors and shield strands trapped in the connector.

A continuity test can find a broken conductor, but it cannot establish complete network health. Reflections, poor shielding or signal distortion at higher speeds may require measurement with a PROFIBUS analyser.

If trouble began after adding a station, check whether termination remains enabled at the former segment end. Draw the actual start and finish of the segment before changing switches.

Use the proper shield clamp instead of leaving a long shield pigtail. Bundling the cable tightly with motor and drive power wiring can turn an apparently healthy network into an intermittent one under load.

For used cable or a reel remainder, inspect the jacket, cut ends and actual length. Similar colour is insufficient identification; confirm the jacket marking and conductor construction.

Disconnect devices and termination electronics before insulation testing the cable. After reconnection, check shield contact and station addresses, then verify that every station returns online.

PDF, software and related topics

Use the Delta PLC accessories PDF and software files page for cable selection documents and related software links. UC-PF01Z-01A needs no separate driver; configure the network using the tools for the master and communication module.

Delta AH communication modules · Delta PLC and HMI manuals · Delta PLC accessories

Navigation: UC-PF01Z-01A main page · Industrial network cables · Delta PLC models · Used Delta products