Delta DVPPF01-S

Delta DVPPF01-S PROFIBUS DP Slave Module

The Delta DVPPF01-S is a communication module that connects a compatible DVP Slim PLC to a PROFIBUS DP network as a slave station. It exchanges a fixed four input bytes and four output bytes with the DP master. For example, it can receive a recipe selection from a central PLC and report machine status from the Delta PLC.

See Delta DVP PLC files for wiring, station addressing and X/Y mapping diagrams.

Port, supply and CPU compatibility

The front panel has a DB9 PROFIBUS port, two hexadecimal address switches and POWER/NET LEDs. The port uses DPV0 over the RS-485 physical layer with shielded twisted-pair cable. It detects the supported baud rate automatically, from 9.6 kbit/s to 12 Mbit/s. Delta specifies a nominal 24 V DC supply.

Fit the module to the right-side expansion bus of a compatible CPU. The original instruction sheet names the DVP-SS, DVP-SA, DVP-SX and DVP-SC families. Delta illustrates the installation on a DVP-12SA. For a different CPU generation, check the exact order code and expansion support.

GSD, station address and data direction

Add the module’s GSD definition to the DP master’s hardware project. Delta’s application manual names DELT09B9.GSD and its 2006 instruction sheet names EATN09B9.GSD. Both list device ID 0x09B9. Verify the device definition in the existing project and the fixed four-byte configuration in each direction. Set a unique DP address from 1 to 125 on the front switches and use that same address in the master project.

Master → Delta. When the adapter is the first expansion unit, the master’s four output bytes appear at X20–X57 in the Delta PLC.

Delta → Master. In the same example, Delta PLC bits Y20–Y57 go to the master’s four input bytes. If the module order has changed, confirm the actual X/Y start addresses in the PLC project.

Programming and field wiring

Use WPLSoft through the Delta CPU to edit the ladder program and monitor X/Y bits. For the DVP12SA11R, Delta documents COM1 RS-232 and the DVPACAB2A30 programming cable. See DVP programming cables for other CPU connections. GSD and DP station settings belong in the master’s hardware configuration software.

Choose cable for the baud rate of the industrial communication network. Delta specifies a segment limit of 100 m at 12 Mbit/s and 1,200 m at 9.6–93.75 kbit/s. Use a suitable PROFIBUS connector and terminate the two physical ends of each segment. See the PROFIBUS FAQ for related maintenance topics.

The same cabinet may also contain Modbus RS-485 devices or PROFINET stations. Recording each network’s protocol, port and station address on the terminal schedule makes the correct connection easier to find during cable replacement.

Editor’s Note

Start with the label on a used module. Confirm DVPPF01-S and inspect the DB9 pins, address switches and expansion latch.

Record settings before removal. Note the two address switch positions, the master’s GSD definition, and the input and output start addresses.

Watch the NET LED. Steady green indicates cyclic data exchange. Rapid red flashing indicates an invalid station address.

Check the bus connection. With power off, verify pin 3 as B and pin 8 as A against the Delta drawing. Check the connector’s termination switch for its position on the segment.

Verify the data direction on the bench. With machine loads disabled, monitor a test value in each direction and compare byte order with the project’s mapping table.

Related topics

DVPPF02-SL · DVPDT01-S DeviceNet · DVPEN01-SL Ethernet · DVPCOPM-SL CANopen

Delta pages

DVP expansion modules · Delta DVP PLC series · Delta PLC · Delta and used models

External references

Delta DVPPF01-S Instruction Sheet · Delta DVP Special Modules Application Manual · Delta DVP-SA CPU Instruction Sheet · PI PROFIBUS Commissioning Guide