Delta DVPDT01-S

Delta DVPDT01-S — DeviceNet slave communication module

The Delta DVPDT01-S connects a compatible DVP-S Slim PLC to a DeviceNet network as a slave adapter. The master scanner exchanges a fixed 4 bytes in each direction with the module. The adapter operates as a Group 2 Only Server and supports Polled I/O and Explicit Messaging. Delta’s connection examples show DVP-SC and DVP-SA CPUs. Check the full CPU model and its expansion support before installation.

In a packing machine, the scanner can send a run request and product selection to the DVP while the PLC returns ready, fault and cycle-complete status. In this master–slave arrangement, the scanner maps the bytes it sends and receives. DeviceNet uses a CAN physical layer. CANopen is a different protocol. When selecting an industrial communication module, check both the protocol and the role required on the network.

DeviceNet wiring and switch settings

The 5.08 mm removable connector uses 1 V− black, 2 CAN_L blue, 3 Drain shield, 4 CAN_H white and 5 V+ red. The network supply is nominally 24 V DC, with an 11–25 V DC range specified by Delta. Network current is below 50 mA at 24 V DC. The PLC side takes power through the expansion connection. Use suitable shielded industrial network cable and network connectors. Delta’s DeviceNet examples include the UC-DN01Z-01A cable.

Use the two rotary switches to set a unique MAC ID (0–63). The DR1/DR0 settings are OFF/OFF for 125 kbit/s, OFF/ON for 250 kbit/s, ON/OFF for 500 kbit/s and ON/ON for auto baud. Delta recommends setting a fixed rate to match the network. IN0 ON retains the I/O buffer data when communication is lost. IN0 OFF clears the buffers. IN1 is reserved.

4-byte I/O mapping, software and programming cable

In Delta’s first expansion module example, scanner output → PLC X20–X57 and PLC Y20–Y57 → scanner input. The PLC can read K4X20 and K4X40 as two 16-bit groups and place its two return words in K4Y20 and K4Y40. Check the actual X/Y starting addresses for your CPU and expansion order.

Configure the network in Delta DeviceNet Builder or the installed scanner’s engineering tool. Register the adapter’s EDS and set Polled I/O to 4 input bytes and 4 output bytes in the scan list. The Delta manual lists Vendor ID 799, device type 12 and product code 80 for checking the EDS identity. PLC programming takes place on the host CPU using WPLSoft or ISPSoft, subject to CPU support. For compatible 8-pin RS-232 CPU ports, see the UC-PRG020-12A and other DVP programming cables.

Editor’s Note

On a used module, check the nameplate and the five-position removable plug. Inspect the side expansion connector for bent pins, corrosion or looseness before fitting it.

Photograph the original MAC ID, DR1/DR0 and IN0 settings before replacement. Disconnect the old module before putting the replacement on the network with the same address.

The POWER LED can be on during a network fault. Measure V+ to V− at the module plug with a multimeter. Then check CAN_H/CAN_L polarity and the 121 Ω terminators at both ends of the trunk.

If NS is red, check for a duplicate address, a speed mismatch or wiring faults. If NS flashes green, check the scanner’s scan list and I/O connection. Test one command bit at the PLC’s X area and one status bit at the scanner input.

With IN0 ON, the last command can remain in the buffer after a network outage. Verify the machine’s response to communication loss in its PLC logic and safety circuit. Keep motion outputs disabled during the initial bit test.

Related topics and communication modules

DVPDNET-SL DeviceNet master · DVPDT02-H2 DeviceNet slave for EH2/SV · DVPPF01-S PROFIBUS DP slave · DVPCOPM-SL CANopen master · DVPEN01-SL Ethernet

DVP Slim communication modules · DVP expansion modules · Delta DVP PLC series · Used Delta PLCs · Delta main page

PDF files and manuals

Delta DVP PLC PDF files

External references · Delta DVP Special Modules Manual, section 10.1 (EN) · Delta DVPDT01-S product specifications · ODVA DeviceNet cable guide (EN)