Delta UN-03PF-03A

Delta UN-03PF-03A

Delta UN-03PF-03A is a male DB9 connector for connecting a PROFIBUS cable to a device port. It includes switch-selectable line termination. The manufacturer table specifies no additional programming socket for this model.

This is a physical connection accessory. It does not perform the function of a PROFIBUS communication module or protocol converter. Start selection under Delta network connectors and verify that the receiving device has a DB9 port specifically designated for PROFIBUS.

Differences from UN-03PF-01A and UN-03PF-02A

Delta UN-03PF-01A, Delta UN-03PF-02A and UN-03PF-03A are listed as male DB9 PROFIBUS connectors. UN-03PF-02A has an additional female DB9 programming socket; UN-03PF-01A and UN-03PF-03A do not. Compare the housing shape, cable exit and clearance to the cabinet door separately.

Using the termination switch

The manufacturer specifies ON for the termination switches at the two ends of the PROFIBUS line and OFF for intermediate connections. Record the original switch position before replacement and check the device's actual position on the line. Setting every connector to ON is not a correct commissioning procedure.

When investigating a fault at an intermediate station, check the line sequence, incoming and outgoing cables and termination settings together with the device address. Reassess the physical endpoints after removing a cable or station.

Cable and mechanical connection

The manufacturer's PROFIBUS accessory table also lists the Delta UC-PF01Z-01A cable. Select cables by protocol under Delta industrial network cables. Do not assign a cable from Delta DVP communication cables to a PROFIBUS line solely because its connector looks similar.

Check the A/B markings, shield contact and cable restraint. Verify pin functions against the receiving device's PROFIBUS wiring diagram. Avoid excessive jacket stripping, shield strands touching signal terminals and cable tension being transferred to the terminal connections.

PLC and interface selection

For the Delta DVP PLC series, the communication module determines the device side of the PROFIBUS connection. Evaluate DVPPF01-S and DVPPF02-SL under DVP Slim communication modules, and DVPPF02-H2, against their individual CPU, installation and configuration requirements. A connector fitting the port does not make these modules interchangeable.

Assess interface requirements using the documentation for Delta DVP interfaces and relevant devices such as Delta IFD9503. UN-03PF-03A requires no software installation; select Delta ISPSoft or the tool supported by the particular controller separately for the PLC project. Replacing the connector does not automatically resolve address, communication-parameter or project-mapping errors.

PDF and technical documentation

Start document selection at Delta PLC accessories files. In the 2019 Delta PLC/HMI Cable Selection Guide, PDF page 163 / printed 4-10 covers connector type, the additional programming socket and termination-switch settings. PDF page 172 / printed A-5 classifies the model as a PROFIBUS connector. These references apply to the 175-page edition.

Editor's Note

A DB9 connector does not automatically mean a serial port. Read the receiving device's port designation and wiring diagram. The same connector shape does not establish the same signals or protocol.

Photograph the switch before removing the connector. Include incorrect termination in the checks for intermittent communication loss. Verify the line endpoint before transferring the old setting to the replacement.

If moving the cable interrupts communication, investigate mechanical contact. Stop the machine appropriately and disconnect power before inspection. Distinguish loose clamping, poor shield contact and crushed cable from a PLC fault.

Do not conceal a contact problem with improvised soldering or an extra resistor. For bent pins, a cracked housing or a faulty termination switch, compare operation with a sound connector. Identify the removed part and record the result.

Complete testing on the actual network. One station connecting successfully is insufficient; monitor communication-error records with all stations operating. Record the line position, switch setting and cable used in the maintenance log.

Related topics

Delta UN-03EN-04A is an RJ45 network accessory; distinguish it from the PROFIBUS DB9 connector. Browse other supporting hardware under Delta PLC accessories, system topics under Delta PLC, and documentation under Delta PLC and HMI manuals.

External reference: Delta PLC/HMI Cable Selection Guide — 2019, English.