Delta DVP24XN11R
Delta DVP24XN11R – 24-point relay output expansion unit
Delta DVP24XN11R is a 0-input / 24-relay-output expansion unit for DVP-ES and DVP-EX control systems. Its nominal unit supply is 24 V DC. The host CPU executes the program and sends output commands to the unit; it does not operate as a standalone PLC.
It belongs to the 11-code H-type devices in the DVP ES / EX modules group. XN identifies digital output expansion and R identifies relay switching. DVP24XP11R instead provides 16 inputs / 8 outputs. See DVP expansion modules for the wider selection.
Relay outputs and load limits
The 2013 ES/EX DIDO sheet lists 2 A per point and 5 A per common for relay outputs, with a voltage specification of below 250 V AC / 30 V DC. Response time is approximately 10 ms; switching frequency is specified as no more than 1 Hz, also affected by CPU scanning. Approximate dimensions are 155 × 100 × 82 mm, width/height/depth.
Assess the 24 V DC unit supply separately from the switched load supply. A relay opens or closes its C–Y circuit; powering the unit does not automatically supply voltage to every output. Follow the actual terminal drawing to identify common connections. Do not combine unrelated voltage sources in a shared circuit.
The 2 A rating alone is insufficient for selecting every load. Check the manual’s load-power limits, coil starting current and contact life. Suitable suppression can include a diode or diode/Zener for a DC coil and an RC network for an AC inductive load. Use appropriate contactors or interposing devices for motors and higher-current loads.
Mechanical relay outputs are unsuitable for fast PWM or servo pulse commands. DVP24XN11T is the transistor version, with different voltage, current and wiring requirements. Changing from R to T requires a circuit assessment rather than simply transferring the wires.
Addressing and commissioning
DVP output addresses use octal numbering. The assigned Y start depends on the host CPU and preceding expansions. If this unit starts at Y20, its 24 outputs occupy Y20–Y47. Treat this as an example and verify the actual project and expansion order.
Fit the expansion connection with power isolated, then check DC polarity, terminals and load-circuit fuses. Prevent machine movement during testing and begin with a low-current test load. Operate each Y address in turn, checking the LED, contact closure and load behaviour together. Remove all software forces afterwards.
Programming software and cables
No separate program is downloaded to DVP24XN11R. Its relays are controlled by Y coils in the host CPU project. The legacy ES/EX documentation identifies WPLSoft. Use ISPSoft only where the actual host CPU and version are supported; the expansion model name alone does not establish software compatibility.
Connect the computer to the host CPU RS-232 programming port. The ES/EX sheet lists DVPACAB215, 1.5 m, and DVPACAB230, 3 m, for PC–PLC connections. A computer without a serial port needs a suitable USB–RS-232 adapter, driver and COM settings. Back up the existing program before downloading changes.
The CPU-to-expansion cable performs a different task: DVPACAB403 is listed as a 30 cm expansion connection cable. Do not confuse it with the programming cable. Verify expansion order, connection direction and the available total I/O capacity against the host CPU documentation.
Related models and topics
For fewer relay outputs, compare DVP08XN11R and DVP16XN11R. Transistor options include DVP08XN11T and DVP16XN11T. To add sensor inputs, examine DVP08XM11N or DVP16XM11N instead; an output unit cannot replace a sensor input module.
Mixed I/O choices include DVP08XP11R, DVP08XP11T, DVP24XP11T, DVP32XP11R and DVP32XP11T. AC-powered models such as DVP24XP00R, DVP32XP00R and DVP32XP00T also require a separate supply assessment. Similar housings or point counts do not establish direct interchangeability.
Editor’s Note
Read the complete label when buying a used unit: DVP24XN11R. An XP mixed module or a T transistor model involves significant wiring differences.
Hearing a relay click is insufficient. Test all 24 outputs with a suitable load, checking contact voltage drop under load and whether any output remains closed after being switched off.
If several outputs fail, first measure the common supply, fuse and terminal connections. An active LED with an inactive load can result from worn contacts or a broken load circuit.
Before replacing a relay, match its coil voltage, contact arrangement and PCB pinout. Matching external dimensions alone is insufficient; inspect damaged tracks and solder joints as well.
Repeated relay failures call for checks of starting current and load suppression. Replacing relays without correcting the cause only postpones the fault. Keep the machine in a safe state during tests, then remove forces and verify normal program operation.
PDF documents and navigation
Collected documentation: Delta DVP PLC PDF files. Our DVP-ES/EX installation, software and cable sheet is the English 2006 edition. DVP24XN11R model page · Delta main page.
External reference: Delta DVP-ES/EX DIDO specification and wiring sheet — 5011671702-ED02, 15 August 2013; English and Chinese, manufacturer documentation hosted in a distributor archive. Check against the installed hardware revision.