Delta DVP08XN11R
Delta DVP08XN11R - 8 Relay Output ES/EX Extension Module
Delta DVP08XN11R is a 24 V DC digital extension module with 8 relay outputs for the DVP-ES and DVP-EX family. It has no digital inputs. Commands from a compatible host PLC program control the additional output points.
Select it from the ES/EX extension range after checking the exact CPU, hardware revision, extension module order and power budget. The compact housing measures approximately 42 mm wide, 100 mm high and 82 mm deep.
Supply and relay specifications
Operating supply: 24 V DC at the +24V and 0V terminals. The digital extension sheet specifies 5 W maximum consumption for the 08XN11 family. Include field-load demand separately when sizing the 24 V power supply. C0 serves a different function from the module’s 0V operating-supply terminal.
Outputs: Y0-Y7, eight relay contacts. The manufacturer specifies 2 A per output, 5 A per common, voltage limits of 250 V AC / 30 V DC and approximately 10 ms response. Apply current, power and contact-life limits for the actual load type. These relay outputs are unsuitable for fast pulse or PWM generation.
Single C0 common and load wiring
All Y0-Y7 outputs share one C0 common. The total current of simultaneously operating loads must remain within 5 A. Eight loads drawing 1 A each would total 8 A: individual channels could remain below their limit while C0 is overloaded.
Example for a 24 V DC load: load supply +24V → C0; Y0 → load; the other load terminal → 0V. Apply the same principle to other Y terminals. A relay contact switches the external load supply rather than generating voltage. Do not copy C0 wiring from a transistor-output installation without checking its function.
Use appropriate suppression and circuit protection for contactor or valve coils. For DC coils, select a suitable diode or manufacturer-approved suppressor; use an appropriate AC suppressor for AC coils. Inrush and switching frequency affect contact life.
Addressing and extension cable
Y0-Y7 are local terminal labels; program addresses depend on the installed extension chain. Examples for a first output extension are Y20-Y27 in a suitable 14ES/32ES installation and Y30-Y37 in the 60ES example. Confirm the starting address against preceding output modules and the CPU manual.
I/O numbering is octal: Y10 follows Y7. This unit adds output points and provides no physical X inputs. Legacy ES/EX peripherals include the DVPACAB403, 30 cm extension cable. The extension connection and computer programming connection perform different functions.
Programming software and computer cable
The host CPU program issues output commands. Legacy ES/EX documents specify WPLSoft. Before using ISPSoft, check support for the exact CPU in that version and configure COMMGR as appropriate. DVP08XN11R has no separate user-program download or independent Modbus station setting.
Connect the computer to the compatible host CPU’s COM1 RS-232 port. Examples are the UC-PRG020-12A USB programming cable, UC-MS020-01A serial cable and legacy DVPACAB2A30. Select the Delta PLC cable for the CPU port and pinout; check the USB-serial driver, COM number and communication settings.
Related models and selection differences
DVP08XN11T provides 8 transistor outputs with different wiring and current limits. DVP16XN11R provides 16 relay outputs, while DVP24XN11R provides 24. DVP08XP11R is a mixed module with 4 inputs/4 relay outputs. Review terminals, supply, commons and addressing together when changing models.
Editor’s Note
Read DVP08XN11R on the actual label. XN identifies an output module; XP identifies mixed I/O. R and T distinguish relay and transistor outputs.
If all eight outputs fail together, first measure the C0 supply and check its protection. Assuming simultaneous failure of every relay can hide a simple wiring fault.
A click and an LED are insufficient evidence. Test every channel with a controlled load and verify that the contact opens when its command is removed. A welded contact may keep its load energized.
Measure the C0 total when several loads switch on together. Loads that work individually but fail together may be exceeding the common-current limit or supply capacity.
For overheated terminals or darkened boards, inspect coil suppression, fuses and grounding. Replacing a relay alone leaves the cause unresolved if the faulty load remains.
Back up the CPU program and photograph wiring and extension order before removal. Disconnect power before handling connectors and prevent machine movement during the first output test.