Delta DVP16XN11R

Delta DVP16XN11R — 16-Point Relay Output Expansion Module

Delta DVP16XN11R is a 16-point relay output expansion module for DVP-ES and DVP-EX PLC systems. It has no digital inputs. It switches field loads according to commands from the host CPU’s program. The module uses a 24 V DC supply and does not execute a standalone PLC program. The R suffix identifies relay outputs.

Supply power versus switched-load voltage

The electronics require 24 V DC; the instruction sheet specifies 5 W maximum consumption. Connect power to the marked 24VDC and 0V terminals according to the equipment label and wiring diagram. Check DC supply polarity. Module consumption is separate from the power switched through the contacts; calculate the field-load supply and current independently.

The outputs are relay contacts; a Y terminal does not generate 24 V. An external source supplies the AC or DC load within the contact ratings. Distinguish the module’s electronic supply from the switched-load circuit. Use a suitable contactor or intermediate switching device for larger loads.

Terminal arrangement for all 16 outputs

Each output has its own C terminal. The pairs are C0–Y0, C1–Y1, C2–Y2, C3–Y3, C4–Y4, C5–Y5, C6–Y6, C7–Y7; followed by C10–Y10, C11–Y11, C12–Y12, C13–Y13, C14–Y14, C15–Y15, C16–Y16 and C17–Y17. Numbering is octal: Y7 is followed by Y10.

Do not use another module’s shared-common diagram for this model. For example, C0 belongs to the Y0 contact circuit; the other C terminals must be wired to their respective circuits. Leave unused or no-function terminals unconnected. Compare the complete layout with the equipment’s terminal label.

Contact ratings and switching speed

The manufacturer sheet specifies 2 A per output with voltage limits of 250 V AC / 30 V DC. Account for load type, inrush current and contact life. The family sheet’s general 5 A/COM figure does not permit 5 A through one output; individual C terminals do not increase the per-point rating.

Relay response is approximately 10 ms, with a specified switching frequency of up to 1 Hz; CPU scanning also affects actual operation. Mechanical contacts are unsuitable for fast PWM or servo pulse trains. For frequent switching, assess an appropriate SSR or another output technology against the actual load and control circuit.

Use suitable flyback suppression for DC coils and an appropriate RC network or varistor for AC coils. Match suppression to the load voltage and design. In inverter or motor applications, distinguish control-signal switching from power switching; do not supply the motor directly through these contacts.

Host compatibility and Y addressing

DVP16XN11R belongs to the ES/EX-generation digital expansion family. Check the exact CPU, side expansion connection and total I/O capacity. A newer code such as DVP16XN211R must not be assumed to have the same terminals. This unit adds outputs only; it provides no X inputs for sensors or pushbuttons.

Local outputs are labelled Y0–Y7 and Y10–Y17. These labels do not necessarily match the starting addresses in the CPU project. For example, as the first digital expansion after an ES CPU with 16 outputs, the module normally occupies Y20–Y37. Earlier modules and the CPU’s allocation rules determine the actual addresses.

Programming software and connection cable

No separate program is downloaded to DVP16XN11R. Its outputs are used in the host CPU’s PLC programming project. WPLSoft can be used for ES/EX systems. When choosing ISPSoft, confirm support for the exact CPU and software version. Drive the assigned Y addresses in the ladder program. Analog-module CR configuration does not apply to this standard digital unit.

For a host CPU with an 8-pin mini-DIN RS-232 programming port, UC-PRG020-12A is a suitable USB programming cable. Alternatively, UC-MS020-01A connects to a PC RS-232 port or an appropriate USB-to-RS-232 converter. Configure the driver, COM port and COMMGR connection where required. The computer cable connects to the CPU; the expansion connection joins the CPU and module.

The module is not a standalone RS-485 or Modbus RTU station. Communication and remote monitoring use the host CPU and the project’s data mapping.

Panel installation and load protection

Approximate dimensions are 155 × 100 × 82 mm (width × height × depth), with an operating temperature of 0…55°C. Provide ventilation and wiring clearance inside a suitable enclosure. Complete grounding and protect load circuits with appropriate fuses. Separate relay-switched wiring from communication and low-level signals to reduce electromagnetic interference.

Editor’s Note

This is a 16-output device, not an input module. Check the 16XM/16XN distinction and the relay R/transistor T suffix before working on supply or load wiring.

Inspect the C terminals before adding common bridges. Every Y output on this model has its own C terminal. Test the correct C–Y pair instead of applying the four-output common grouping found on other modules.

For second-hand equipment, test all 16 outputs with a suitable fused load. A clicking relay or illuminated Y LED does not establish contact integrity. Check contact voltage drop and heating under load.

If a load remains energised with the program output OFF, first separate external bridges and backfeeds from a possible welded contact. Do not confuse a contact fault with the CPU driving the wrong address.

A replacement relay must match coil voltage, contact arrangement, ratings, dimensions and isolation clearances. Repeated failure on one channel calls for an inrush-current and suppression check. Retest all outputs after repair.

Review the machine’s emergency stop and safety relay arrangement. A welded contact may leave the load energised despite a program OFF command. Disconnect power before changing expansion connections and prevent unexpected motion during testing.

PDF documentation

Use our Delta DVP PLC files page for documentation. The 2013 ES/EX DIDO sheet covers the model and output characteristics. Appendix 11.3 of the 2012 programming manual shows the DVP16XN11R/T terminal arrangement. The cable guide describes the ES/EX CPU’s computer connection. Compare legacy documents with the exact equipment code and terminal label.