Delta DVP32XP00T

Delta DVP32XP00T – ES/EX Expansion Unit with 16 Inputs and 16 Transistor Outputs

Delta DVP32XP00T is a 100–240 V AC powered mixed digital expansion unit for legacy DVP-ES/EX systems, providing 16 digital inputs and 16 NPN/sinking transistor outputs. It is not a PLC CPU executing its own program; its inputs and outputs are managed by the host processor. The 00 suffix identifies the AC-powered version, while T identifies transistor outputs.

Typical duties include pushbutton, limit switch, inductive sensor and photoelectric sensor signals, together with suitable DC interface relays, indicators and small control loads. DVP32XP11T uses a 24 V DC main supply; DVP32XP00R has relay outputs. Similar codes do not establish identical wiring. DVP32XP200T is a different-generation model requiring a separate compatibility review.

Main supply and 24 V service output

Connect the 100–240 V AC, 50/60 Hz main supply to L and N. Input signals and transistor-load circuits use DC; never transfer AC mains to those terminals. Coordinate power switching of the host and powered extension. Provide appropriate protective grounding, fuses and supply wiring according to the cabinet schematic.

The ES/EX extension document specifies a 400 mA, 24 V DC service supply for the AC-powered 00 group. This is not the current rating of each transistor output. Subtract input and sensor consumption from the service-supply budget. Use an appropriate external 24 V supply for larger loads, and do not parallel its positive output with the module’s service +24 V terminal.

16 digital inputs and S/S wiring

Local input terminals are X0–X7 and X10–X17. They use 24 V DC sink/source circuits with nominal 5 mA input current. The ES/EX DIDO extension sheet specifies ON above 16.5 V, OFF below 8 V, and approximately 20 ms response. The CPU’s 10 ms response and D1020/D1021 filter descriptions in general series documents must not be assigned automatically to this extension.

For PNP sensors connect S/S to 0 V; for NPN sensors connect S/S to +24 V, with the sensor output connected to the required X terminal. Check NPN/PNP selection and sink/source wiring together. Inputs sharing S/S use the same reference. An optocoupler input circuit does not establish individual channel-to-channel isolation.

These are digital inputs, not direct 0–10 V or 4–20 mA measurement channels. Their approximately 20 ms response also makes them unsuitable as a substitute for dedicated high-speed encoder inputs.

16 transistor outputs and common groups

The outputs are NPN/sinking, open collector. Connect each DC load between +DC and the appropriate Y output; the corresponding C common provides the 0 V return. These are not relay dry contacts and must not switch AC loads directly.

C0: Y0–Y3; C1: Y4–Y7; C2: Y10–Y13; C3: Y14–Y17. Check each group separately. If an entire group fails to operate, inspect its common return and field supply first.

Maximum output voltage is 30 V DC. Per-output resistive-load limits derate to 0.3 A at 40°C, 0.2 A at 45°C, 0.15 A at 50°C and 0.1 A at 55°C; also observe the 2 A/COM limit. Check coil current and inrush separately. Use a suitable interface driver for larger contactors and loads.

Fit a reverse-parallel diode or other appropriate suppression to DC coils. Diagnose a field-wiring short circuit through measurements rather than an LED alone. Electrical switching times do not establish support for high-speed PLSY/PWM instructions on this expansion unit.

X/Y addressing examples

DVP X/Y numbering is octal; X0–X17 represents 16 inputs. Local terminal labels need not match the final CPU addresses. In the ES/EX extension-sheet example, a DVP32XP00T fitted directly after a 14ES/20EX/32ES host occupies X20–X37 and Y20–Y37. Preceding extensions change the allocation.

In the 60ES example, the same first extension occupies X50–X67 and Y30–Y47, demonstrating that input and output starting addresses can differ. After confirming the actual CPU and module order, LD X20 / OUT Y20 can form a simple ladder test for the first allocation only. No analog-module CR setup or FROM/TO template is required.

Programming software and cable

DVP32XP00T has no separate user-program download. The primary tool for legacy ES/EX host projects is WPLSoft. If using ISPSoft, verify support for the exact CPU and software release, configuring COMMGR when required. Select the host CPU as the project target. Back up the program, settings and necessary retained data first.

The ES/EX CPU’s 8-pin mini-DIN RS-232 COM1 port can use a UC-PRG020-12A USB-to-RS-232 programming cable. Alternatively, use a UC-MS020-01A serial cable with an appropriate PC serial port or USB-to-RS-232 converter. Older documents also list DVPACAB215 / DVPACAB230. Check the pinout, USB driver and COM number. The programming cable connects to the CPU and does not replace the expansion connection.

Installation and commissioning

Mount the unit on a 35 mm DIN rail or with suitable screws inside a cabinet. Operating temperature is 0–55°C; keep ventilation openings clear. Connect the side expansion interface with power removed. For DVP-ES and DVP-EX, verify the exact CPU, total I/O capacity and expansion power budget. A similar connector does not establish compatibility with another CPU family.

Editor’s Note

Check the complete 00T suffix. Although 11T provides the same number of points, its main supply differs. Identify L/N and +24 V/24G before transferring any wiring.

If the input LED changes but the program does not see it, check the CPU’s I/O count and preceding modules before removing the extension. A 60ES host does not assign identical input and output starting numbers.

If an output LED is on but its load stays off, inspect the corresponding C0–C3 return, field supply and cable. Interpret multimeter readings together with a small, suitable test load.

Test all 16 inputs and 16 outputs on a used unit, sequentially with a compatible CPU. Inspect terminal discolouration, oxidised expansion contacts, broken DIN clips and loose connections. An LED alone does not prove operation under load.

Check the service 24 V both unloaded and under its intended load. If voltage collapses, investigate the power budget and field wiring. Do not attempt to fix this by paralleling an external supply onto the service output.

After a transistor failure, inspect the coil and suppression device as well as the module. Start output tests with machine motion isolated, and preserve the program and address backup.

PDF manuals

Start with our Delta DVP PLC files page. The locally hosted DVP-ES/EX English series sheet – 5011634301-YIE1, 2006-07-04 includes the exact DVP32XP00T selection row. CPU program capacity, communication ports and processor functions elsewhere in that document are not features of this expansion unit.

Related models and navigation

DVP32XP00R is the AC-powered relay-output version with the same I/O count. DVP32XP11T provides 16 inputs and 16 transistor outputs with a 24 V DC main supply. DVP16XM11N provides 16 inputs, while DVP16XN11T provides 16 transistor outputs. DVP32XP200T is a different generation. These descriptions do not establish direct replacement compatibility.

Delta main page | Delta PLC | DVP PLC series | DVP expansion modules | ES/EX expansion modules | DVP32XP00T model page | DVP PDF files

External references

Delta DVP-ES/EX DIDO extension sheet – 2013-08-15 distribution record; Delta PLC/HMI Cable Selection Guide – 2019-08-15, ES/EX connection section. Manufacturer download-centre access conditions apply. Check the document edition and exact equipment code together.