Delta DVP-EX
Delta DVP-EX Series PLC
Delta DVP-EX is an earlier-generation main PLC in the Delta DVP family, combining digital control with built-in analog measurement and outputs. Its basic configuration is 8 digital inputs, 6 digital outputs, 4 analog inputs and 2 analog outputs. The 20-point designation includes both digital and analog channels; it does not mean 20 digital I/O points. Built-in analog signal processing can reduce the need for a separate analog module in smaller machines.
EX and EX2 are different generations. DVP20EX00R2/T2 belongs to the original EX group, whereas DVP20EX200R/T identifies EX2. The earlier EX is in the 4K-step class; Delta's 2006 ES/EX sheet specifies 3792 program steps. Do not apply EX2 memory, speed or analog-resolution ratings to an original EX.
Models, supply and output types
DVP20EX00R2: 100–240 V AC supply and 6 relay outputs. DVP20EX00T2: 100–240 V AC supply and 6 transistor outputs. DVP20EX11R2: 24 V DC supply and 6 relay outputs. These models retain the 8 digital inputs and 4 AI/2 AO configuration.
Verify the supply code on the nameplate. Size the power supply for a DC model using the combined PLC, sensor and auxiliary load requirements; suitable DIN-rail power supplies can be assessed for cabinet installations. An AC-powered CPU does not mean its input and output signals operate at mains voltage.
Built-in analog inputs and outputs
The analog inputs on these EX models support −10 to +10 V or −20 to +20 mA; the analog outputs support 0–10 V or 0–20 mA. The 2006 ES/EX sheet specifies 10-bit input resolution and 8-bit output resolution, with input digital values of −512 to +511 and output values of 0 to 255. These raw values are not directly pressure, temperature or rotational speed.
For example, scale a pressure sensor's 4–20 mA or 0–10 V signal using its lower and upper measurement limits. Understand the difference between voltage and current signals before wiring; their terminals are not interchangeable. When working with external analog signal controllers, also compare common-terminal arrangements, input impedance and isolation.
Temperature sensors such as thermocouples and Pt100 elements require an appropriate converter rather than a direct connection to a standard V/mA input. For a channel fault, check the signal type, wiring and raw value first. Small, stepped changes from an 8-bit analog output do not by themselves indicate a fault.
Digital signals and field devices
When connecting inductive sensors, photoelectric sensors, limit switches and pushbuttons, assess the 24 V DC input circuit, S/S common and sensor PNP/NPN wiring together. Match the actual diagrams rather than relying on wire colours.
On relay models, direct switching or the use of an interposing relay depends on load current and load type. Provide suitable suppression for contactor coils and correctly selected fuses. Transistor models require their own common-terminal, load-polarity and leakage-current checks; do not transfer relay wiring unchanged.
For encoders or pulse applications, match the high-speed counter and pulse instructions to the exact CPU limits. External counters and tachometers may serve a different purpose from a PLC counter. Similarly, distinguish a program delay from the circuit duty of independent timer relays.
Which software programs the EX?
WPLSoft is a primary tool for editing ladder programs, transferring programs and monitoring earlier DVP-EX machines online. ISPSoft can also be used with supported original EX targets. Select the CPU according to the EX/ES family and actual model rather than creating an EX2 project for an original EX.
ISPSoft 2.0 and later use a COMMGR communication channel. Preserve the original WPLSoft .dvp file before conversion, then check instructions, addressing and compilation results. Select tools by their roles in the Delta PLC software section. An HMI panel project or SCADA application does not replace the PLC program; preserve their communication and scaling settings separately.
Programming cable and ports
The basic PC connection uses COM1 RS-232. UC-PRG020-12A is a converter-equipped cable with USB at the PC end and an 8-pin male mini-DIN connector at the PLC end. Delta's cable guide includes DVP20EX00R2/T2 in this connection group. Install the USB driver and select the assigned Windows COM port in the software.
A computer with a serial port can use UC-MS020-01A or a correctly wired DVPACAB2A30. These serial cables need an additional USB-to-RS-232 converter when used through a USB port. Distinguish a Delta PLC programming cable from an ordinary USB cable; the original EX must not be treated as having a direct USB programming port.
COM2 RS-485 is used for field communication. Match Modbus ASCII or Modbus RTU, baud rate, data bits, parity, stop bits and station address to the existing CPU and port settings. Consult the Modbus communication explanations when troubleshooting. A connector fitting physically does not establish a working connection.
Applications and expansion
The analog output can provide a reference to a compatible variable frequency drive when signal ranges and input requirements agree. Treat the motor start command, speed reference, fault feedback and protection circuit separately. Route analog wiring away from power and coil wiring, using suitable panel components for sound terminal and shielding arrangements.
For additional I/O, match DVP expansion modules to the original ES/EX expansion system. A similar housing does not establish compatibility with Slim or EX2 modules. Record the existing module order and addresses before replacing equipment.
Editor's Note
Start with the exact code: 00 or 11, R or T? A supply mismatch and an output-type mismatch create different problems. Get a clear nameplate before choosing a used unit.
Do not test an analog input at only one value. Use a calibrated source at lower, middle and upper points, comparing both raw data and the displayed engineering value.
Test analog outputs with suitable loads as well as at no load. Use the correct voltage measurement or properly arranged current loop; avoid connecting a meter in the wrong mode.
Back up the program, retained data, HMI recipes and communication settings. Clearing memory first can leave an otherwise serviceable machine unavailable for much longer than expected.
If analog readings fluctuate, check sensor power, common terminals, shielding and proximity to power wiring before blaming the PLC. A known working signal source helps separate field faults from channel faults.
On a used unit, test digital outputs, analog channels and both serial ports separately. A lit POWER indicator or a successful program upload does not establish that every field circuit works.
Manuals and related topics
Use Delta DVP PLC files for model-matched installation and programming documents. Related models: DVP20EX00R2 · DVP20EX00T2 · DVP20EX11R2. See DVP-EX2 for a generation comparison.
Navigation: Delta DVP PLC series · Delta PLC main category · Used Delta equipment · Delta PLC software · DVP files
External references
Delta DVP-ES/EX installation and specification sheet, 2006 (English, manufacturer's document hosted by a distributor) · Delta PLC/HMI cable selection guide, 2019 (English).