Delta DVP20EX11R2

Delta DVP20EX11R2 24 V DC Relay Output PLC

The Delta DVP20EX11R2 is a 24 V DC Delta DVP-EX CPU with built-in analog I/O. It provides 8 digital inputs, 6 relay outputs, 4 analog inputs and 2 analog outputs. A single PLC CPU can read pressure or level signals and sequence pumps, valves or machine operations.

Power supply and digital I/O

The nominal supply is 24 V DC and the documented supply range is 20.4–26.4 V DC. X0–X7 accept 24 V DC signals and can be wired for sink or source operation using the S/S common. The six relay outputs have two common groups. C0 feeds Y0–Y2 and C1 feeds Y3–Y5. The manual specifies 2 A per point and 5 A per common. Check the applicable load rating and contact protection when selecting a contactor coil or solenoid. Program capacity is 3,792 steps.

Analog channels and register addresses

The 4 analog inputs accept ±10 V or ±20 mA with 10-bit resolution. The raw range is −512 to +511. Read the instantaneous values of CH0–CH3 at D1056–D1059 and the averaged values at D1110–D1113. The default analog input sampling interval is 5 ms and can be set at D1118.

The 2 analog outputs provide 0–10 V or 0–20 mA with 8-bit resolution. Write the command for CH0 to D1116 and CH1 to D1117. The command range is 0–255. Match the analog input of the drive or valve positioner to the PLC output wiring diagram.

Check both channel wiring and scaling when working with analog inputs and outputs. For a pressure transmitter that delivers 4–20 mA, map the low end of the process range to the reading at 4 mA and the high end to the reading at 20 mA. The analog current, analog voltage and 0–10 V and 4–20 mA guides explain the signal formats.

Programming software and cable

Use Delta WPLSoft to read, edit and download a PLC program. For ISPSoft, check the installed release for classic DVP-EX CPU support and verify project compatibility. ISPSoft 2.0 and later set up the serial driver through COMMGR.

Connect the PC through COM1 RS-232. Delta’s ES/EX cable diagram shows UC-PRG020-12A for a PC with USB and UC-MS020-01A for a native RS-232 port. The diagram uses the DVP20EX00R2/T2 as its example. Check the COM1 socket and pinout on the EX11R2 before connecting. Once the USB driver is installed, select the Windows-assigned COM port in WPLSoft. COM2 RS-485 is the field communication port. See industrial communication and Modbus over RS-485 for more on serial networks.

Editor’s Note

Start with the CPU nameplate on the bench. Confirm the EX11R2 model code and check the supply at the 24VDC and 0V terminals shown in the drawing.

If an output LED is on and its coil stays off, check power at the relevant C0 or C1 common and check the contact with the load connected.

Read the live ADC value before replacing a transmitter on an older machine. Checking at 4 and 20 mA helps distinguish a measurement error from a scaling error.

For an analog output bench test, identify the voltage or current terminals in the drawing and measure each channel individually.

Back up the original program before servicing the unit. Save the analog channel assignments, drive reference settings and serial port parameters with the backup. See the PLC troubleshooting guide for LED and I/O checks.

Related topics

See the DIN rail and grounding guides for panel installation. For extra digital points, check the Delta DVP expansion modules and confirm classic EX compatibility before selecting a module.

Classic DVP-EX · DVP20EX00R2 and DVP20EX00T2. EX2 family · DVP20EX200R and DVP20EX200T.

Delta DVP PDF files

Delta DVP PLC files · Delta DVP-ES/EX installation and wiring sheet (PDF)

Categories · Second-hand models · Delta Automation · Delta PLC · DVP PLC series · DVP-EX2

External references · Delta DVP PLC programming manual (PDF) · Delta PLC/HMI cable selection guide (PDF)