Delta DVP20EX00R2
Delta DVP20EX00R2 – PLC with Analog I/O and Relay Outputs
Delta DVP20EX00R2 is a 100–240 V AC powered main PLC unit from the original DVP-EX family. It incorporates 8 digital inputs, 6 relay outputs, 4 analog inputs and 2 analog outputs. This combines switching control and analog I/O within one controller for small automation systems. The total of 20 includes the analog channels.
This is not a DVP-EX2 CPU. The R2 ending does not justify applying EX2 specifications. The original EX instruction sheet specifies 3792 program steps, placing it in the 4K class. A replacement project must consider the program, analog scaling and wiring together.
Analog channels and register addresses
The four analog inputs accept −10…+10 V or −20…+20 mA. Resolution is 10 bits, with a digital range of −512…+511. Present input values for CH0, CH1, CH2 and CH3 are read from D1056, D1057, D1058 and D1059, respectively.
The two analog outputs provide 0–10 V or 0–20 mA. Resolution is 8 bits, using commands 0–255: D1116 for CH0 and D1117 for CH1. A command of 128 represents approximately 5 V or 10 mA. This is a scaling example rather than a statement of measurement accuracy.
A 0–10 V sensor and a 4–20 mA sensor require different connections and calculations. Select the appropriate terminals for analog voltage or analog current; a 4–20 mA application also requires offset and engineering-unit scaling. A Pt100 or thermocouple requires a suitable transmitter or temperature module rather than direct connection to these inputs.
Power supply, digital inputs and relay outputs
The main AC supply connects to L/N. The auxiliary 24 V output does not mean that this CPU is powered through a 24 V input. Where an external 24 V power supply is used, do not parallel supply outputs without an appropriate design.
Digital inputs X0–X7 support DC sink/source wiring. Configure the S/S common to match the NPN/PNP arrangement, then check the sensor and limit switch connections. Relay outputs use Y0–Y5. The instruction sheet gives limits of 2 A per point and 5 A per common; load type and switching conditions must also be considered.
A relay output is unsuitable for high-speed servo pulse commands. Contactor and valve coils need suitable fuse protection and suppression matched to the AC/DC load. Check the polarity of a diode used across a DC coil.
Programming software and cable
WPLSoft is the established software for original EX projects. Select the correct CPU family when working with PLC programming and Ladder logic. For ISPSoft, the manufacturer's 2011 compatibility table specifies firmware V6.2 or later for the original SS/ES/EX family. Verify both the installed software's target list and the actual CPU firmware rather than assuming support for every old EX unit.
The programming interface is COM1 RS-232 with an 8-pin mini-DIN connector. The manufacturer's ES/EX cable table lists the UC-PRG020-12A USB programming cable and the UC-MS020-01A RS-232 cable. The latter requires a suitable computer serial port or converter. For ISPSoft, configure the COMMGR serial driver, COM number and communication settings. Back up the original WPLSoft project before conversion.
COM2 provides RS-485 field communication; match station and serial settings for a Modbus RTU application. RS-232 and RS-485 are electrically different interfaces. This CPU has no native Ethernet or USB port; a USB programming cable performs conversion on the computer side.
Analog wiring considerations
The manufacturer's diagram identifies V+/V− for voltage and I+/I− for current. Do not copy bridging arrangements from a different analog module. Analog output load limits are 1 kΩ–2 MΩ for voltage and 0–500 Ω for current. Evaluate receiver resistance and cable conditions against the selected output type.
The analog and digital sections are isolated, but the analog channels are not isolated from one another. Review grounding and signal commons where equipment operates at different potentials. Investigate a suspected short circuit or wiring error with power isolated. The normal PLC program does not replace the emergency stop and safety relay circuit.
Editor's Note
Read the complete label first. EX00R2 and EX200R may look similar, but they belong to different generations. Transferring the old analog calculations without checking them can produce incorrect measurements.
For a used unit, check more than the RUN indicator. Test the X inputs, all six relays and their commons separately; an audible relay click does not prove that its contact works under load.
Check analog inputs at several points using a known source. Then test both outputs with a suitable load and instrument. Keep voltage and current measurement arrangements distinct.
Before changing a machine program, save the project, communication settings and necessary retained data. Confirm that the backup opens correctly; a filename alone is not sufficient evidence of a usable backup.
Request photographs and test details for burn marks, corrosion, loose terminals or previous repairs. Check output behaviour after power restoration under controlled conditions. This page is not a test report for a particular unit.
Related models and replacement assessment
DVP20EX00T2 is the AC-powered transistor-output option in the original EX family. DVP20EX11R2 is the original EX relay-output model with a 24 V DC supply; this supply difference needs particular attention.
DVP20EX200R and DVP20EX200T belong to the later EX2 family. They are candidates for a replacement project, not assumed plug-in equivalents. Reassess the CPU target, analog ranges/scaling, terminal arrangement and output type.
PDF documents and related topics
See our Delta DVP PLC files page for further documentation. The existing Delta DVP-ES/EX wiring and specifications PDF covers this original EX model; its analog specification table continues onto the second page.
Related topics: combining analog signals with digital control, matching sensor outputs to input commons and serial communication connections.
To offer used equipment, send the brand, complete model, quantity, working/fault condition, label photographs and asking price to otomasyonavm@gmail.com. Used sales require an invoice, with no returns; workshop testing may be arranged. Confirm the item's condition and test scope before purchase.
Delta used models | Delta PLC | Delta DVP series | Delta DVP-EX | DVP20EX00R2 main page | DVP PDF files
External references
Delta DVP-PLC Application Manual – Programming, 5 June 2020: original EX analog functions, printed page 2-97. Delta PLC/HMI Cable Selection Guide, 15 August 2019: DVP-ES/EX section 1.2. Manufacturer's historical ISPSoft help manual: original SS/ES/EX firmware compatibility table.