Delta DVP-EX2

Delta DVP-EX2 PLC series

Delta DVP-EX2 is the second-generation compact controller family with built-in analog I/O in the DVP PLC range. As a PLC, it executes the machine program, reads measurement signals and controls outputs. The series provides 16K program steps and a fastest basic instruction time of 0.35 µs. This is not the scan time of the complete application.

20EX2 and 30EX2 models

DVP20EX200R: 8 digital inputs, 6 relay outputs, 4 analog inputs and 2 analog outputs. DVP20EX200T has the same channel counts with transistor outputs.

DVP30EX200R: 16 digital inputs, 10 relay outputs, 3 analog/temperature inputs and 1 analog output. DVP30EX200T has the same channel counts with transistor outputs. These four ordering codes use a 100–240 V AC supply; do not confuse mains power terminals with digital input or sensor circuits.

Analog inputs and temperature measurement

20EX2 has 12-bit analog inputs and outputs. For 0–10 V and 4–20 mA applications, match the channel voltage/current mode, wiring and numerical scaling. When connecting pressure sensors, the engineering units and transmitter range used for pressure measurement must be represented correctly in the program.

30EX2 provides 16-bit voltage/current inputs and a 12-bit analog output. Suitable input modes also accept PT100, PT1000, NI100 and NI1000 sensors. For temperature measurement, select the correct Pt100 type and two/three-wire arrangement. Understand the difference between Pt100 and thermocouples: a thermocouple must not be connected directly to an RTD input mode.

D1115 selects analog channel modes, but its bit arrangement differs between 20EX2 and 30EX2. D1110–D1112 carry the first three input values. D1113 is the fourth input on 20EX2 but channel status information on 30EX2. D1116 controls the first analog output; D1117 is the second output on 20EX2 only. Resolution, accuracy and displayed decimal places are different quantities.

For PID control, consider sensor scaling, sampling time and output limits together. When implementing PID control with a PLC, define feedback direction and sensor-disconnection behaviour too.

Programming software and cable

DVP-EX2 is programmed with WPLSoft or ISPSoft. Select the correct EX2 CPU. For ISPSoft connections, COMMGR manages the appropriate serial channel; the program editor and USB converter driver are separate components. Keep the source project, software version and CPU firmware information together.

The standard programming connection uses COM1 RS-232 and a DVPACAB2A30 cable. This approximately 3 m cable has a 9-pin female D-sub PC connector and an 8-pin mini-DIN PLC connector. See Delta programming cables for details.

Without a PC serial port, use USB → USB-to-RS-232 converter with its driver installed → DVPACAB2A30 → COM1. These models have no built-in USB programming port. Observe the differences between RS-232, RS-422 and RS-485 and do not substitute a USB-to-TTL adapter.

Communication, digital I/O and motion

Standard EX2 hardware has one RS-232 and two RS-485 ports. Match station addresses and serial settings on a Modbus RS-485 network; Modbus ASCII and Modbus RTU use different frame formats. An HMI panel also requires the correct PLC address, communication driver and register mapping.

When wiring inductive sensors or photoelectric sensors, match the input common to the sensor's PNP/NPN output. Designated fast outputs on transistor T models support pulse control in the 100 kHz class; relay R outputs cannot serve this purpose.

For encoder counting and stepper motor positioning, check electrical levels, fast channels and instruction limits. A servo versus stepper comparison must also consider compatibility between the PLC pulse command and the drive input circuit.

Choose DVP ES2/EX2 expansion modules by function and power budget. Do not substitute the earlier DVP-EX generation without comparing model codes, the program and terminal arrangements.

Editor's Note

First establish whether the unit is a 20EX2 or 30EX2. Analog channel counts, temperature support and register meanings differ. Loading the old program alone does not establish a correct replacement.

Back up the operating program, retained data, channel modes and port settings. Check the PLC's raw analog value before adjusting the number displayed on the HMI.

For a measurement fault, verify the sensor signal with suitable equipment and confirm whether the channel expects voltage or current. Inspect analog commons and shielding before changing calibration values.

Calculate the sensors' 24 V power demand. If an external DIN rail power supply is used, measure it under load and inspect interference from contactors and cable routing.

Test relay contacts separately from transistor output power and commons. An output LED is not a complete pulse test; use an oscilloscope with machine motion safely prevented.

For a used PLC, test every analog channel at several reference points as well as the digital I/O. If 30EX2 temperature inputs will be used, verify them separately with a suitable RTD simulator.

PDF manuals

Documentation is collected on our Delta DVP PLC files page. The existing Turkish ES2/20EX2 hardware guide and English ES2/20EX2 hardware guide include 20EX2 wiring. Use the dedicated 30EX2 document for its different analog/temperature hardware.

Related topics

Delta PLC main page · DVP series · Second-hand Delta equipment · DVP PDF files

External references

Delta DVP30EX2 instruction sheet, 2014 — English/Chinese · Delta ES2/EX2 family programming manual, 2022 — English