Delta DVP20EX00T2

Delta DVP20EX00T2 | PLC with 4 Analog Inputs, 2 Analog Outputs and NPN Outputs

The Delta DVP20EX00T2 is a first-generation DVP-EX PLC CPU with a 100–240 V AC supply. It has 8 digital inputs, 6 NPN transistor outputs, 4 analog inputs and 2 analog outputs. A typical application reads a pressure transmitter and sends the result of a PLC PID loop to a drive as an analog speed reference.

Analog ranges, resolution and D registers

The built-in analog inputs cover ±10 V or ±20 mA, with 10-bit resolution and a raw range of −512 to +511. The analog outputs provide 0–10 V or 0–20 mA, with 8-bit resolution and a command range of 0 to 255. Match the voltage or current signal to the field device. A 4–20 mA sensor starts at 4 mA. For a drive with a 0–10 V reference, check the drive’s scaling as well.

D1056–D1059 hold the present values of CH0–CH3. D1110–D1113 hold the corresponding averages. D1116 and D1117 command analog outputs CH0 and CH1. For example, 128 in D1116 commands approximately 5 V when CH0 is wired as a voltage output. Use the sensor’s endpoints to convert the analog signal into engineering units. When changing hardware, check the register map and scaling of EX2 models such as the DVP20EX200T separately.

Digital I/O and serial communication

Wire the S/S common of the 24 V DC digital inputs according to the sink/source diagram. Check the output polarity of an inductive sensor before connecting it. The NPN open-collector outputs sink current in an external DC load circuit. For high-speed pulse output, check the instruction, output terminal and drive input together. Digital and analog inputs serve different purposes.

Use WPLSoft for PLC programming. If you plan to use ISPSoft, first verify DVP-EX CPU support in the installed version. Use the COM1 RS-232 port to transfer or monitor a ladder program. Delta’s cable diagram shows the UC-PRG020-12A for a USB connection and the UC-MS020-01A for DB9 RS-232. Install the USB cable driver and select the resulting COM port.

COM2 RS-485 can provide serial Modbus communication with an HMI. Match the station address, baud rate and frame settings. Select ASCII or RTU according to the existing project and the connected device.

Editor’s Note

Read the complete model code. When buying used, ask for photos of the 00T2 code, supply rating and analog terminals.

Check scaling at two points. For a 4–20 mA input, apply 4 mA and 20 mA separately and record the raw readings. Compare the raw values before checking the displayed units.

Test the output under load. Before connecting the drive, measure the analog output at low and midrange commands with a suitable test load. Verify the voltage or current wiring against the diagram.

Keep the project and parameters. Back up the analog scaling and COM2 settings with the program. Compare the register assignments channel by channel when changing the CPU.

If the reading jumps when a drive starts, check signal cable routing, shield termination, grounding and possible electromagnetic interference.