Delta DVP-ES

Delta DVP-ES Series PLC

Delta DVP-ES is an earlier-generation main PLC series in the Delta DVP family, intended for basic sequential control. Different models provide different digital I/O counts, relay or transistor outputs, and AC or DC supplies. Delta describes it as a 4K-step program-memory series; the 2006 ES/EX specification sheet lists 3792 program steps.

DVP-ES, DVP-ES2 and DVP-ES3 are separate generations. For example, DVP24ES00R2 is an original ES model, while DVP24ES200R belongs to ES2. The R2/T2 suffix alone does not identify an ES2 CPU. Match the software target, expansion system and wiring to the complete ordering code.

ES models and digital I/O counts

14 points: DVP14ES00R2 and DVP14ES00T2 provide 8 digital inputs + 6 digital outputs.

24 points: DVP24ES00R2 and DVP24ES00T2 provide 16 digital inputs + 8 digital outputs.

30 points: DVP30ES00R2 provides 18 digital inputs + 12 relay outputs.

32 points: DVP32ES00R2 and DVP32ES00T2 provide 16 digital inputs + 16 digital outputs.

40 points: DVP40ES00R2 and DVP40ES00T2 provide 24 digital inputs + 16 digital outputs.

60 points: DVP60ES00R2 and DVP60ES00T2 provide 36 digital inputs + 24 digital outputs.

The main units above with the 00 supply code use 100–240 V AC. DVP24ES11R2 is a separate 24 V DC variant with 16 inputs + 8 relay outputs. Check the nameplate on other 01/11 variants as well. R identifies relay outputs and T transistor outputs; their output wiring is not interchangeable.

Supply and field wiring

Size the power supply for a DC model and its field devices using total load, starting current and voltage drop. Suitable DIN-rail power supplies and well-chosen panel components help establish sound supply and terminal arrangements. An AC-powered PLC does not permit mains voltage to be applied to its digital inputs.

For inductive sensors, photoelectric sensors, limit switches and pushbuttons, check the 24 V DC input circuit, S/S common and PNP/NPN wiring together. Match the sensor's electrical output to the PLC input circuit rather than relying on wire colours or connector shape.

Relay-output ES models suit contact-control duties within their load ratings. Select interposing relays, contactor coils and fuses for the actual load, with suitable coil suppression. Transistor models require different common-terminal, polarity and current-limit checks.

Pulse outputs and counters

Appropriate transistor-output ES models support independent high-speed pulses up to 10 kHz at Y0 and Y1. This feature does not apply to R relay models. For encoders, check the counting mode and frequency limit separately; single-phase and two-phase counting have different capabilities.

Compare the duties of external counters and tachometers with the PLC's internal counters. When replacing the function of independent timer relays with program logic, also consider power-up, power-loss and restart behaviour. Sending a digital run command to a variable frequency drive is different from generating an analog speed reference.

Which software programs the ES?

WPLSoft is a primary tool for creating ladder programs, transferring programs and monitoring original DVP-ES machines online. ISPSoft can also be used with supported original ES targets. Select the ES family and correct CPU rather than assuming that ES2 or ES3 instructions and memory resources apply.

ISPSoft 2.0 and later use a COMMGR communication channel. Keep the original WPLSoft .dvp file before conversion, then check compilation, addressing and instruction support. The Delta PLC software page explains the different tools. Back up the HMI panel project and any SCADA application separately from the PLC program.

Programming cable and PC connection

The basic programming connection uses COM1 RS-232. UC-PRG020-12A is a converter-equipped cable with USB at the computer end and an 8-pin male mini-DIN connector at the PLC end. Delta's cable guide includes original ES models in this connection group. Install its Windows driver and select the assigned COM port number in the software.

A computer with a physical serial port can use UC-MS020-01A or a correctly wired DVPACAB2A30. These serial cables need an additional USB-to-RS-232 converter when used through USB. Distinguish a Delta PLC cable from an ordinary USB cable; the original ES has no built-in USB programming port.

For ISPSoft, create and start an appropriate serial driver in COMMGR, then select the same channel in ISPSoft. Match the baud rate, data bits, parity, stop bits and station address to the CPU's existing settings. Read the device information to confirm the target and make a backup before transferring a program.

RS-485, analog requirements and expansion

COM2 RS-485 is used for field communication. Distinguish Modbus ASCII from Modbus RTU, matching port settings and station addresses across the PLC, HMI and connected devices. Consult the Modbus communication explanations when checking protocol and wiring issues. A standard original ES has no built-in Ethernet port.

Do not confuse ES with DVP-EX, which has built-in analog channels. An analog signal application using a pressure sensor or temperature sensor requires a suitable interface. Do not connect a 0–10 V or 4–20 mA signal to a standard digital input. External analog signal controllers or another PLC solution must be selected using verified signal and communication compatibility.

With suitable original ES/EX digital expansion modules, the series supports up to 256 I/O points in total. Not every DVP expansion module uses the same connection system. Do not assume compatibility with Slim or later-generation modules; check module order, power requirements and I/O addressing against the existing project.

Editor's Note

Seeing R2 on the label does not make the unit an ES2. Read the full code first; original ES and ES2 units have different software targets and hardware capabilities.

Do not rely only on the POWER indicator or a successful program upload when buying used equipment. Test inputs, outputs and both serial ports separately, including faults that appear after the unit warms up.

Test relay contacts with a suitable load. An output indicator can light even when a contact fails to conduct. On transistor models, check the common terminal, load supply and leakage current separately.

Back up the program, required retained data, HMI recipes and communication settings. Avoid starting work by clearing memory; one missing initial value can considerably extend commissioning.

If communication fails, check the cable, USB driver, COM number and port settings first. Comparing the same connection with a known working unit can prevent a mistaken diagnosis of a failed PLC port.

For intermittent resets or unexpected input changes, measure the supply under load. Check loose terminals, common connections and coil interference before internal repair; first separate field faults from board faults.

Manuals and related topics

Use Delta DVP PLC files for installation, connection and programming documents. Generation comparison: DVP-ES · DVP-ES2 · DVP-ES3. See DVP-EX for an earlier-generation option with analog channels.

Navigation: DVP PLC series · Delta PLC main category · Used Delta equipment · PLC software · DVP files