Delta DVP32ES00R2

Delta DVP32ES00R2 Relay Output PLC

The Delta DVP32ES00R2 is a compact PLC CPU from the original DVP-ES family. It takes a 100–240 V AC supply and has 16 digital inputs rated at 24 V DC and 16 relay outputs. Its built-in EEPROM holds a program of up to 3,792 steps. Typical automation applications include conveyor sequencing, filling and packaging.

Digital inputs and relay outputs

Inputs X0–X17 can read an inductive proximity sensor for metal part detection, a photoelectric sensor for box detection, or a limit switch for end-of-travel feedback. Wire the S/S input common according to the sensor’s PNP or NPN output type and Delta’s wiring diagram. Addresses are octal, so X7 is followed by X10 and Y7 by Y10. Continuous pressure or level measurement requires an analog input. The DVP20EX00R2 is an example of a Delta CPU with built-in analog I/O.

Relay outputs Y0–Y17 can switch an interposing relay, a suitable contactor control circuit, or a panel indicator. Delta specifies 2 A per output and 5 A per common, with a relay response time of about 10 ms. For coil loads, check inrush current, contact ratings for the load type and total current through each common. Select the fuse and coil suppression for the load circuit.

Programming software, cable and serial communication

Start with WPLSoft for PLC programming, program backup and live Ladder monitoring. Select the ES CPU family in the project. If using ISPSoft, check the installed version’s CPU list for the original ES target and set up the serial connection in COMMGR.

Use the PLC’s 8-pin Mini-DIN COM1 (RS-232) port. For a USB connection on the PC, use Delta’s UC-PRG020-12A programming cable. Install its driver and select the COM number assigned by Windows. A PC with a DB9 RS-232 port can use UC-MS020-01A.

COM2 is the RS-485 field communication port. Before reconnecting an existing operator panel or drive, record the working protocol, station address, baud rate and parity. Check Modbus command and frame support against the CPU revision. Route serial wiring away from motor and power cables to reduce electrical interference.

Editor’s Note

When buying used, start with the label. Write down the full DVP32ES00R2 code and the unit’s revision. Look for discoloration at the relay commons, loose terminals and bent pins in the serial port.

If the old CPU still runs, back up its program first. Save the HMI and drive communication settings while the machine can still be checked. Having both records makes the bench work much easier.

Apply a suitable 24 V DC test signal to inputs X0–X17 one at a time. Watch the physical input LED and the input status in WPLSoft together.

An output LED tells you the command is on. To check whether the contact actually switches, isolate the PLC from the machine loads on the bench, then test Y0–Y17 by common group with a suitable low-voltage load.

Before reinstalling the PLC, check the L/N supply, S/S input common and protective grounding against the wiring diagram. If moving the project to a different CPU, compare terminal order and serial settings first.

Related models and topics

The DVP24ES00R2 has 16 inputs and 8 relay outputs, while the DVP40ES00R2 has 24 inputs and 16 relay outputs. For the same 16+16 I/O count with transistor outputs, see the DVP32ES00T2. Before moving to the later DVP32ES200R, verify the project, terminal layout, serial ports and expansion modules together.

RS-232, RS-422 and RS-485 compared · Delta DVP PLC series · Used Delta models

Internal references and PDF files

OtomasyonAVM Delta DVP PLC Files · Delta DVP-ES/EX installation and wiring sheet (PDF, EN)

External references

Delta DVP-ES series record · Delta DVP-PLC Application Manual (Programming, PDF, EN) · Delta PLC/HMI Cable Selection Guide (PDF, EN)