Delta DVP24ES00T2
Delta DVP24ES00T2 – PLC with 16 inputs and 8 transistor outputs
The Delta DVP24ES00T2 is an original Delta DVP-ES PLC CPU with a 100–240 V AC supply, 16 digital inputs at 24 V DC (X0–X17) and eight NPN open-collector transistor outputs (Y0–Y7). The input addresses are octal, so X10 follows X7. Delta’s hardware sheet specifies 3,792 program steps. Typical duties include conveyor sequencing, product counting and pulse commands to a compatible drive.
Input signals and output loading
Check the AC supply to the CPU and the 24 V DC field input circuit separately. Match the S/S common to the PNP or NPN sensor circuit for the required sink/source arrangement. Follow the Delta wiring diagram. An inductive sensor can detect metal, a photoelectric sensor can detect passing products and a limit switch can report end-of-travel. Match the NO/NC contact action to the condition in the program.
The transistor outputs sink current in a suitable DC load circuit. Delta specifies 0.30 A per point at 40 °C and 0.10 A per point at 55 °C. Account for panel temperature, total current on the common terminal and coil inrush. Use an interposing relay where appropriate. Check load-circuit fusing and surge suppression as well as panel protective grounding.
Pulse outputs and encoder feedback
The ES transistor group supports pulse outputs of up to 10 kHz at Y0 and Y1. When connecting a stepper motor drive, check its pulse format, NPN input compatibility and pulse-circuit current requirements. For encoder feedback, select the counter mode and check the input frequency independently. Use the existing program and wiring diagram to identify the relevant I/O points.
Programming software and cable
Use Delta WPLSoft to read and back up the existing ladder diagram project and monitor it online. When programming the PLC, select the original DVP-ES family. If using ISPSoft, verify that the installed version offers an ES target, retain the original WPLSoft file and configure the serial connection in COMMGR.
For a USB-equipped computer, use the Delta UC-PRG020-12A converter cable. Plug its mini-DIN end into the PLC’s COM1 RS-232 port. Install the Windows driver and select the assigned COM number. The UC-MS020-01A cable can be used with a physical serial port. See Delta PLC programming cables.
RS-485 communication and related Delta models
COM2 is the RS-485 field port. For Modbus over RS-485, match the station address, baud rate, parity and device roles. Check CPU firmware and the project’s serial settings when using Modbus RTU. The RS-232, RS-422 and RS-485 comparison and industrial communication guide explain the physical interface and protocol.
The DVP14ES00T2 offers 8 inputs and 6 transistor outputs. The DVP24ES00R2 has the same 16 inputs and 8 outputs, with relay outputs. The DVP32ES00T2 has 16 inputs and 16 transistor outputs. When moving to the DVP-ES2 family, check program instructions, expansion modules, ports and field wiring.
Editor’s Note
Start with the nameplate when buying used. Ask for a photo that shows DVP24ES00T2 and the AC supply rating. Check L/N, S/S and the output commons for heat marks or loose terminals.
Back up the machine before removing the CPU. Save the program, required retained data, COM2 settings and terminal labels. Missing parameters can delay the restart.
Check the load as well as the output LED. Disconnect the machine loads and use a suitable DC test load to check the channel. Inspect the load supply, common and Y output together. See the electrical measurement and test guide.
Start at low speed when troubleshooting pulses. Check the drive input type, pulse/direction format and common. Then verify Y0/Y1 at the machine’s working frequency.
Check the cable first if you cannot connect. Inspect the COM1 socket, Windows COM assignment and software port settings. If available, try the same cable on a working ES unit.
Internal references and PDF files
Delta DVP PLC PDF files · Delta DVP-ES/EX installation and wiring sheet (English PDF).
Navigation · Delta DVP PLC series · Delta DVP-ES.
External references
Delta DVP product catalogue · Delta DVP application and programming manual · Delta PLC/HMI Cable Selection Guide (§1.2) · DVP-ES/EX technical information and pulse output table · Delta ISPSoft user manual.