Delta DVP24ES00R2
Delta DVP24ES00R2 PLC | 16 Inputs, 8 Relay Outputs
The Delta DVP24ES00R2 is a compact PLC CPU from the original Delta DVP-ES series. It takes a 100–240 V AC supply and provides 16 digital inputs at 24 V DC and 8 relay outputs. On a conveyor, filling station or packaging machine, it can read an inductive sensor or a photoelectric sensor and operate valves or contactors in sequence.
I/O and cabinet wiring
The built-in PLC inputs and outputs use addresses X0–X7 and X10–X17 for the inputs and Y0–Y7 for the relay outputs. Check the S/S common against Delta’s sink/source diagram for the PNP or NPN sensors in use. The ES/EX specification sheet lists 3,792 program steps and EEPROM program memory.
Delta rates the relay contacts at up to 2 A per point and 5 A per common. The 24ES00 relay wiring diagram labels the commons C0–C7. Check voltage, inrush current and inductive load limits separately. For pressure or level transmitters, check the analog and digital input requirements and select a suitable module. Follow the wiring sheet when checking cabinet protective grounding and the load circuit fuse.
Programming software and cable
WPLSoft is the software listed in Delta’s ES/EX sheet for reading, editing and monitoring the Ladder program. To set up the programming connection, select the legacy DVP-ES CPU type and the COM port assigned by Windows. Read from the PLC to the PC and save a backup first. If you use ISPSoft, check that your installed version offers the DVP-ES target and can connect online to the CPU.
COM1 is the RS-232 port for the PC connection. Delta’s cable guide lists UC-PRG020-12A for a USB-equipped PC and UC-MS030-01A for RS-232. The earlier ES/EX sheet also lists DVPACAB215 and DVPACAB230. On a PC without a serial port, install the UC-PRG020-12A driver or use the serial cable with a compatible USB-to-RS-232 adapter.
COM2 provides RS-485 field communication. Match the Modbus format, RTU or ASCII, as well as the station address, baud rate and parity at both ends. Check the firmware version before applying communication settings to an older CPU. See Delta PLC cables for connection options.
Related Delta models
DVP24ES00T2 has the same I/O count and uses transistor outputs. If the application requires high-speed pulse output, check the output type, supported channels and frequency limits. DVP24ES11R2 is the 24 V DC-powered relay variant. DVP32ES00R2 provides 16 relay outputs. In the successor series, DVP24ES200R also provides 16 inputs and 8 relay outputs. Before moving to ES2, compare terminal layouts, expansion modules and program instructions.
Editor’s Note
Start with a clear photo of the side label when buying used. It is easy to miss the supply difference between the 00R2 and 11R2.
Record the POWER, RUN and ERROR indicators, then confirm that you can read the CPU through COM1.
If an input LED stays dark, check the S/S common and field supply before tracing the sensor.
When a Y LED lights, verify that the contact actually switches a small test load. Disable machine motion for the output test.
If serial communication drops only while the variable-frequency drive is running, check the cable route and sources of electromagnetic interference.