Delta DVP14ES00T2
Delta DVP14ES00T2 · DVP-ES PLC with 8 Inputs and 6 Transistor Outputs
The Delta DVP14ES00T2 is a compact PLC main unit from the original DVP-ES family. It has a 100–240 V AC supply, eight 24 V DC digital inputs and six open-collector transistor outputs. It reads sensors, runs machine sequences and switches DC control signals in small machines. Delta’s ES/EX specification sheet lists a program capacity of 3,792 steps.
Inputs, outputs and load selection
The inputs are addressed X0–X7. Wire the S/S input common to match the PNP or NPN circuit. When connecting an inductive sensor, photoelectric sensor or limit switch, use the machine schematic to identify the signal input and the common connection.
The Y0–Y5 outputs are for DC control circuits. Delta’s wiring sheet specifies a 30 V DC transistor output limit. The per-point current limit falls from 0.30 A at 40 °C to 0.10 A at 55 °C. Check the output-group limit as well. For a contactor or interposing relay coil, check the coil voltage, current and required transient suppression.
When using pulses to control a stepper motor drive or a servo drive, check the instruction used for Y0/Y1 against the drive’s pulse input circuit. For encoder feedback, check the input signal level and the frequency limit for single-phase or A/B counting.
Programming software and cable
Use WPLSoft for PLC programming, ladder editing, program backup and online monitoring. If using ISPSoft, verify the DVP-ES target and instruction support in the installed version. Select the serial channel in COMMGR. Keep the original WPLSoft project file before converting it.
COM1 is the 8-pin mini-DIN RS-232 programming port. For a PC with USB, use the UC-PRG020-12A cable. Install the driver and select the COM number assigned by Windows. A PC with a physical RS-232 port can use the UC-MS020-01A serial cable.
COM2 is the RS-485 field port. For an HMI panel or another serial device, match the communication protocol, station address and serial settings. If the panel uses Modbus RTU, back up the existing project settings.
Related Delta models
The DVP14ES00R2 has the same eight inputs and six outputs with relay switching. The DVP14ES01T2 has the same I/O count and uses a 24 V DC supply. The DVP24ES00T2 provides 16 inputs and eight transistor outputs. If the machine also uses analog signals, see the built-in analog channels on the DVP20EX00T2.
Editor’s Note
When buying a used unit, look for 00T2 on the nameplate. Check the supply marking and panel schematic before applying power, especially when the old unit was marked 01.
On the bench, try reading the program through COM1 first. If it fails to connect, check the cable driver, COM number and serial settings before inspecting the PLC port.
Monitor each input individually. If an output LED turns on, use a suitable DC test load to verify switching. Checking the output common and load supply first saves time.
If the serial link drops while the machine runs, see whether the signal cable shares a duct with motor wiring. Check panel grounding and the drive’s EMC filter, if fitted.
Keep a backup of the PLC program, required retained register values and serial port settings. When moving to DVP-ES2, compare the terminals and instructions with the original machine project.
Related topics and internal references