Delta DVP40ES00R2
Delta DVP40ES00R2 – 40-Point PLC with Relay Outputs
The Delta DVP40ES00R2 is a first-generation Delta DVP-ES compact PLC powered by 100–240 V AC. It has 24 digital inputs rated at 24 V DC and 16 relay outputs. In conveyors, packaging equipment and other machine automation applications, it reads sensors and switches control circuits for devices such as contactors and valves.
Inputs, outputs and panel wiring
The input range is X0–X27 and the output range is Y0–Y17. Addresses use octal numbering, so X10 follows X7. Before wiring an inductive sensor, capacitive sensor, photoelectric sensor or limit switch, check its output signal and the S/S input common against the wiring diagram. PNP and NPN sensors require different common wiring. For a continuous measurement signal, see the difference between analog and digital inputs.
Delta specifies relay contact limits of 2 A per point and 5 A per common. Contact voltage must stay below 250 V AC or 30 V DC. When switching a coil, account for inrush current and use suppression appropriate to the coil. The outputs are grouped under commons C0–C3. Check the 35 mm DIN rail, protective grounding and fuse protection in the panel. Review the emergency-stop function as part of the machine’s safety circuit.
Programming software and cable
Delta WPLSoft is the documented programming tool for this CPU. Select the first-generation DVP-ES family in the PLC programming software. WPLSoft can read the ladder program from the PLC and monitor its I/O online. If you inherit an ISPSoft project, check that your version lists the legacy DVP-ES target and can connect to this CPU online.
For COM1 (RS-232), use UC-PRG020-12A with a USB-equipped PC or UC-MS030-01A with a PC that has a physical RS-232 port. Install the USB cable driver and select the COM number shown in Windows Device Manager in WPLSoft. See Delta PLC cables for more details.
COM2 (RS-485) supports serial communication within a panel or between machines. On an existing RS-485 Modbus link, check the station numbers, baud rate, parity and protocol mode. For Modbus RTU, check the CPU firmware version and COM2 mode. If the link runs Modbus ASCII, record the existing settings. If a SCADA system uses this link, confirm that it reads the expected addresses after the PLC swap.
Editor’s Note
Ask for a label photo first. When buying used, check the exact model code and both terminal strips. If you see discoloration or looseness around C0–C3, pay particular attention to that group during the bench test.
Identify the power terminals before energizing. L/N are the AC supply terminals. +24V and 24G are the auxiliary DC output terminals.
Read and save the program first. With the machine in a safe state, back up the old CPU if possible. Keep the port settings and any existing project file alongside it.
Check the inputs one by one. On the bench, apply a suitable test signal and compare the X LED with the address in WPLSoft. If a group stays inactive, revisit the common wiring.
Check the relay under load. With the Y LED on, verify that the contact switches a suitable, safe test load. A worn contact can click and still drop out under load.
Related Delta models
The DVP40ES00T2 has the same 24-input, 16-output count with transistor outputs. The DVP32ES00R2 has 16 inputs and 16 relay outputs, while the DVP60ES00R2 has 36 inputs and 24 relay outputs. The DVP40ES200R belongs to the later ES2 generation. Compare the terminal layout, expansion modules and program before replacing a CPU.
Internal references and PDF files
Delta DVP PLC PDF files · Delta DVP-ES/EX wiring guide (PDF) · Delta DVP PLC series · Used Delta products
External references
Delta PLC/HMI Cable Selection Guide – DVP-ES/EX, section 1.2 (PDF) · Delta DVP PLC Programming Manual – model terminals and addressing (PDF) · Delta WPLSoft software information