Delta DVP40ES00T2
Delta DVP40ES00T2 | 40-Point Transistor Output PLC
The Delta DVP40ES00T2 is a compact PLC main unit from the original Delta DVP-ES series. It runs on 100–240 V AC and has 24 digital inputs rated at 24 V DC and 16 open-collector transistor outputs. It reads sensors, runs the machine sequence and switches DC control loads in applications such as conveyors, packaging machines and assembly stations.
Inputs, outputs and power supply
24 V DC inputs: The S/S common connection determines whether the input circuit is configured for sinking or sourcing. Check PNP and NPN wiring against the panel diagram. When connecting an inductive sensor, photoelectric sensor or limit switch, check both the signal voltage and the input common. The onboard inputs are digital. Use a suitable interface for 0–10 V or 4–20 mA measurements. See the guide to analog and digital inputs for details.
Transistor outputs: The outputs switch DC loads. Delta gives a 30 V DC voltage limit and a per-channel current rating of 0.30 A at 40 °C, 0.20 A at 45 °C, 0.15 A at 50 °C and 0.10 A at 55 °C. The common-group limit is 2 A per COM. Check both channel and group limits. Use a suitable flyback diode or suppressor for a DC coil. Select a suitable interposing relay or driver for an AC coil or a higher-current load.
Program memory and counting: The hardware sheet lists 3,792 program steps in built-in EEPROM. For an incremental encoder application, use the manual to check the assigned high-speed counter inputs and the frequency limits for single-phase or two-phase operation.
Programming software and cable
WPLSoft: Start here when reading, backing up or monitoring the program on an existing DVP-ES machine. Select the original DVP-ES CPU family in the project. See the guides to Delta WPLSoft, ladder diagrams and PLC programming.
ISPSoft: You can use ISPSoft when the installed version offers the original DVP-ES target. Set up the serial connection in COMMGR and select the same channel in ISPSoft. If converting a WPLSoft project, retain the original file and compile the converted project with the correct CPU target.
Programming cable: The PLC’s COM1 port is an 8-pin mini-DIN RS-232 connection. Use Delta UC-PRG020-12A for a USB-equipped PC or UC-MS020-01A for a PC with a physical RS-232 port. Install the Windows driver for the USB cable and select the COM number assigned by Windows in the programming software. See Delta PLC cables to compare cable types.
COM2 / RS-485: This second serial port is used for field communication. When connecting an HMI or drive, check the existing project’s protocol, baud rate, parity and station address. The guides to RS-232, RS-422 and RS-485, Modbus and RS-485, Modbus ASCII and Modbus RTU explain the interface and protocol choices.
Editor’s Note
1. When buying used, ask for a clear photo of the label and output terminals. Confirm the model code ends in 00T2.
2. Look for discoloration, loose terminal screws and a cracked housing. If an output common shows signs of heat, test that group under load.
3. An output LED can light even when the channel can no longer sink current. Disconnect the machine loads and use a suitable DC test load to check that each output group switches on and off.
4. If the old CPU still communicates, back up the program and the settings needed to run the machine before removing it. A successful COM1 backup only confirms the programming connection. Test the COM2 field link separately.
5. If several inputs stop responding together, measure the 24 V field supply and check the S/S common first. Then monitor the individual X inputs online.
Internal References | Related Delta Models
The DVP40ES00R2 has the same I/O count and uses relay outputs. The DVP32ES00T2 has 16 inputs and 16 transistor outputs. The DVP60ES00T2 has 36 inputs and 24 transistor outputs.
The DVP40ES200T has the same 24/16 point split and belongs to the ES2 generation. When considering a migration, compare the terminal layout, program instructions, expansion modules and serial settings. See the Delta DVP-EX family for models with onboard analog channels.
Related Topics
See grounding and fuses for the power side of a panel, and NO and NC contacts for field input logic. See safety relays for emergency stop and guard-door circuits.
OtomasyonAVM PDF and Series Links
Delta DVP PLC files · Delta DVP-ES/EX hardware and wiring sheet (PDF)
All Delta DVP PLC series · Used Delta models
External References
Delta DVP-PLC programming manual (EN, PDF) · Delta PLC/HMI cable selection guide, section 1.2 (EN, PDF) · Delta WPLSoft and ISPSoft FAQ (EN)