Delta DVP60ES00T2
Delta DVP60ES00T2 – DVP-ES PLC with 36 Inputs and 24 Transistor Outputs
The Delta DVP60ES00T2 is a compact 60-point PLC from the Delta DVP-ES series. It operates from 100–240 V AC and provides 36 digital inputs rated at 24 V DC and 24 open-collector transistor outputs. The PLC CPU runs the machine program. Typical machine automation applications include feeding, conveying and sorting stations controlled from a single cabinet.
Inputs, outputs and addressing
The built-in inputs are addressed X0–X43 and the outputs Y0–Y27. The addresses use octal numbering, so X10 follows X7 and Y10 follows Y7. Keep this in mind when matching physical terminals to addresses in the machine program.
Use a photoelectric sensor to detect passing parts, an inductive sensor to detect metal targets or a limit switch to detect the end of mechanical travel. Check whether the device is normally open or normally closed and whether it has an NPN or PNP output. Wire the S/S common according to Delta’s sink/source diagram. Watching the input LED and the corresponding X address together helps trace the signal through the PLC input and output circuits.
The transistor outputs are rated for DC load circuits up to 30 V DC. Delta lists a per-point limit of 0.30 A at 40 °C, 0.20 A at 45 °C, 0.15 A at 50 °C and 0.10 A at 55 °C. Check the total load for each output common group as well. Use a suitable interposing relay to switch an AC coil. Check surge suppression for DC coils, fuse protection for the field supply and cabinet grounding against the wiring diagram.
For distance or motion measurement with an encoder, check which inputs are assigned to the high-speed counter and verify the signal type and frequency limit for the chosen counting mode. For high-speed pulse output, follow Delta’s instruction and terminal assignments. The installation sheet shows Y0 for PLSY.
Programming software and cable
Use Delta WPLSoft on Windows and select the legacy DVP-ES CPU type. Use COM1 RS-232 to read, save and monitor the ladder program.
Delta specifies the UC-PRG020-12A PLC programming cable, a 2 m cable with a female DB9 connector at the PC and a male 8-pin mini-DIN connector at the PLC. The earlier installation sheet also lists DVPACAB215 (1.5 m) and DVPACAB230 (3 m). If the PC has no serial communication port, use a USB-to-RS-232 adapter with its driver installed. Select the COM port assigned by Windows in WPLSoft.
COM2 RS-485 is available for field communication. Before connecting to an existing Modbus/RS-485 network, compare the PLC program with the connected device’s address, baud rate, parity and protocol settings. Read the existing program from the PLC and save a copy before starting online troubleshooting.
Editor’s Note
When buying a used unit, ask for a clear nameplate photo. Check the T2 suffix and the 100–240 V AC supply rating.
Start a bench check with the POWER, RUN and ERROR indicators. If ERROR flashes, read D1004 in WPLSoft to capture the fault code.
If an X input stops responding after a sensor replacement, check the sensor output, the 24 V DC supply and the S/S common.
If the Y indicator changes state and the load stays off, check the other outputs in the same group. Start with the output common and load supply, then test the channel with a known-good DC test load.
Before replacing the PLC in a running installation, keep the program backup, terminal photographs and serial port settings together.
When moving to ES2, perform the first check with the loads isolated. Check I/O mapping, expansion modules and HMI or drive communications individually.
Related Delta models
The DVP60ES00R2 provides 36 inputs and 24 relay outputs in the same ES series. For smaller I/O counts, the DVP40ES00T2 has 24 inputs and 16 transistor outputs, while the DVP32ES00T2 has 16 inputs and 16 transistor outputs.
Delta lists DVP-ES2 as the successor to DVP-ES. The DVP60ES200T is an ES2 model with 36 inputs and 24 transistor outputs. Compare terminal assignments, program requirements and module support in the two manuals before migrating. For a small I/O increase on an existing ES system, see the DVP08XP11T ES/EX expansion module.
OtomasyonAVM PDF files and internal references
Delta DVP PLC PDF Files · DVP-ES/EX installation and wiring sheet, 5011634301-YIE1 (English PDF)
Delta PLC overview · Delta DVP PLC series · Used Delta equipment
External references
Delta Electronics – DVP-ES series page · Delta PLC/HMI Cable Selection Guide, section 1.2 (English PDF) · Delta DVP-ES/EX electrical specifications (multilingual PDF)