Delta DVP24ES11R2 – 24 V DC PLC with 8 relay outputs
The Delta DVP24ES11R2 is a first-generation Delta DVP-ES compact PLC main unit. It runs on 24 V DC and has 16 digital inputs and 8 relay outputs. Typical applications include conveyor sequencing, part detection, valve control and simple machine sequences.
Power supply, inputs and relay outputs
Supply range is 20.4–26.4 V DC (24 V DC, −15%/+10%). Use the 24 V DC and 0 V terminals identified on the unit. Check the S/S input common when wiring inductive sensors, photoelectric sensors and limit switches. Use Delta’s wiring diagram to match the S/S connection to the PNP or NPN sensor output.
Program capacity is 3,792 steps. Delta specifies 2 A per point and 5 A per common group for the relay outputs. Check load type and inrush current separately. Use suitable fusing and the coil maker’s specified suppression for inductive loads. A suitable interposing relay can help protect PLC contacts in frequent switching applications. The Y outputs are relay contacts. Select an appropriate transistor-output CPU for high-speed pulse commands to a servo or stepper drive.
The built-in inputs and outputs are digital. A pressure transmitter with a 4–20 mA or 0–10 V analog signal requires a suitable analog interface. A relay run command to a variable frequency drive and an analog speed reference are separate signals.
Programming software and cable
WPLSoft is the first choice for editing Ladder, reading the program and monitoring the CPU online. Select ES in the PLC project. If your ISPSoft release supports the first-generation ES target, set up the connection in COMMGR. Keep a backup of the original project before converting it.
Programming port is COM1, RS-232, 8-pin mini-DIN. Delta’s DVP-ES/EX instruction sheet lists DVPACAB215 (1.5 m) and DVPACAB230 (3 m) for a PC with a physical serial port. For a USB connection, pair one of these with a compatible USB-to-RS-232 adapter. Delta’s ES/EX family cable guide also lists the UC-PRG020-12A integrated USB-to-RS-232 option. Confirm the connector and pinout of the Delta PLC cable, then select the COM port assigned by Windows in the software.
COM2 RS-485 serves field communications. For an existing HMI or drive network, match the station address, serial settings and Modbus ASCII or Modbus RTU mode at both ends. When troubleshooting, identify whether each device uses RS-232 or RS-485 first.
Related Delta models
The DVP24ES00R2 has the same 16 inputs and 8 relay outputs with a 100–240 V AC supply. The DVP24ES00T2 offers the same I/O count with AC power and transistor outputs. The AC-powered DVP32ES00R2 has 16 inputs and 16 relay outputs. The DVP24ES200R belongs to the DVP-ES2 generation. Before replacing the CPU, check supply, terminal layout, expansion modules and project target together. The DVP24ES01R2 shares the 24 V DC and 16+8 ratings and uses the low-profile housing. Delta lists the 11R2 as the high-profile version.
Editor’s Note
Check the nameplate first. Ask for a photo of the full model number and supply terminals. The 00R2 and 11R2 share the same I/O count, so appearance alone is a poor guide.
Test past the POWER light. Check each input at the bench. A problem at S/S can make several sensors disappear at once.
Check the contact while the Y LED is on. Test all eight outputs in turn with a suitable load. If the indicator lights and the load stays off, check the common, relay contact and terminal separately.
Read before you write. Save the existing program, required retained data and serial port settings. Verify COM1 with a PC and COM2 with a known-good field device.
If faults appear when a coil energizes, measure the 24 V supply under load. Then inspect grounding, cable routing, electromagnetic interference and the installation’s noise immunity.
Internal references and PDFs
Delta DVP PLC files · DVP-ES/EX instruction sheet, English PDF. See §2.3 for model identification, §3.2 for electrical ratings and the wiring section for terminal drawings.
Related topics · Delta DVP PLC series · Delta PLC · Used Delta equipment
External references
Delta DVP-PLC programming manual · Delta PLC/HMI cable selection guide, §1.2 · Delta ISPSoft user manual