Delta DVP30ES00R2

Delta DVP30ES00R2 — 18-input, 12-relay-output PLC

The Delta DVP30ES00R2 is a compact PLC CPU from the original Delta DVP-ES series. It operates from a 100–240 V AC supply and provides 18 digital 24 V DC inputs and 12 relay outputs. Typical applications include conveyor sequencing, packaging and sorting, where the PLC reads sensors and controls field devices.

Digital inputs, relay outputs and terminals

The inputs are labelled X0–X21 and the outputs Y0–Y13. The addresses are octal, so X10 follows X7. The PLC inputs can read signals from an inductive proximity sensor, a photoelectric sensor or a limit switch. Check the wiring diagram for the S/S input common arrangement that matches the sensor’s PNP or NPN output.

The Y outputs share five C0–C4 common groups. Each relay contact switches a suitably powered load circuit. For a contactor or valve coil, check the coil voltage and inrush current against the contact rating. For frequent switching or high-speed pulse output, check the required transistor-output model and its supported pulse channels.

Programming software and cable

Delta WPLSoft is the starting point for reading, backing up and monitoring an existing Ladder program. Select the DVP-ES family and the computer’s COM port. Before making any PLC programming changes, read the program from the controller and save a dated copy.

COM1 is the programming port. It uses an 8-pin mini-DIN connector and the RS-232C interface. Use a Delta DVPACAB2A30 or DVPACAB230 cable. On a PC without a serial port, use a compatible USB-to-RS-232 adapter and select the COM port assigned by its driver. If you use ISPSoft, check that your installed version offers the DVP-ES target and configure the serial link with COMMGR.

COM2 and field communications

COM2 is the RS-485 field port. When setting up industrial communications, check the differences between RS-232, RS-422 and RS-485 to match the devices’ interfaces. For an HMI or variable frequency drive, match the station address, baud rate and parity for Modbus over RS-485. Check the existing project and CPU version to confirm whether it uses Modbus RTU or Modbus ASCII. If the machine has a SCADA connection, record the register addresses as well.

Related Delta models

The DVP24ES00R2 has 16 inputs and 8 relay outputs. The DVP32ES00R2 has 16 inputs and 16 relay outputs, and the DVP40ES00R2 has 24 inputs and 16 relay outputs. When considering the 32-point unit, check whether the existing program uses X20 and X21. The DVP30ES00T2 has the same 18/12 split with transistor outputs. Check its output terminal layout and load circuit before substitution.

For a move to Delta DVP-ES2, compare the program, I/O addresses, terminals and serial settings. If the machine uses a Delta DOP-100 HMI, check the panel driver and addresses in the screen project too.

Editor’s Note

Start with the label. When buying used, ask for a clear photo of the full DVP30ES00R2 code. There is also a 30-point transistor-output version.

Save the program first. Read it from the PLC at the bench and keep the backup. Photograph the field wires and commons before lifting them.

Test X20 and X21 as well. Use a known 24 V DC test signal and compare the physical input LED with the X status in WPLSoft.

Test each Y output with a suitable low-voltage load. Check that the load actually turns on and off. An output LED or relay click tells you only part of the story.

Inspect the terminals before powering up. Look for loose or discoloured terminals, verify protective grounding and disconnect machine loads for the initial bench test.

Internal references and PDF files

See Delta DVP PLC PDF files for the series documentation. Appendix B, printed page 11-2 of the application manual shows this model’s terminal layout.

DVP-ES series · Delta PLC models · Used Delta equipment

External references

Delta DVP catalogue · Ordering code, supply and I/O table.

Delta DVP-PLC application manual · Terminal layouts for DVP30ES00R2 and DVP30ES00T2.

Delta DVP-ES/EX/SS application manual · COM ports and programming cables in Appendix A.