Delta DVP16XN11T — 16 NPN Transistor Output Expansion Module
Delta DVP16XN11T is a 24 V DC-powered, 16-output expansion unit in the DVP ES/EX module family from Delta automation. It has no digital inputs. It adds switching points for suitably rated DC valve coils, indicators and intermediate control devices.
XN identifies output expansion, 11 DC-powered H-type construction and T transistor outputs. In the DVP PLC series, this is an expansion unit rather than a CPU with an independent program.
Supply, dimensions and mounting
Nominal supply: 24 V DC. The manufacturer electrical table gives 5 W maximum consumption for the DVP16XN11 group. This is not the total power required by the external output loads. Check supply polarity, terminal identification and the field-load power budget.
Dimensions: approximately 155 × 100 × 82 mm (width × height × depth). Mounting: 35 mm DIN rail or M4 screws. Operating temperature: 0–55 °C. The manufacturer layout shows at least 50 mm of surrounding ventilation clearance.
Output technology and wiring
The 16 outputs are NPN open-collector, sinking outputs. Connect the load between positive DC and its Y output; connect the corresponding C common to 0 V as shown in the device diagram. Do not wire these as PNP sourcing outputs or relay dry contacts.
The local outputs use Y0–Y17 octal numbering. Match the C0–C17 terminals and corresponding Y outputs in the 16XN drawing against the actual terminal labels. Do not assume an internal common connection; provide the required return for every output used.
Current limits and switching
The output voltage ceiling is 30 V DC; the manufacturer specifies 2 A per common. For resistive loads, the channel limit falls from 0.3 A at 40 °C to 0.2 A at 45 °C, 0.15 A at 50 °C and 0.1 A at 55 °C. Both channel and applicable common limits must be respected.
The 2013 DIDO sheet gives approximately 15 µs ON, 25 µs OFF and a switching frequency of up to 1 kHz, affected by the PLC scan. These figures do not automatically extend the CPU’s high-speed pulse/positioning functions to this module. Use an appropriate flyback diode or suppression device for inductive DC loads.
Host compatibility and addressing
DVP16XN11T appears in the legacy DVP-ES and DVP-EX digital extension tables. For DVP-ES2 and DVP-EX2 systems, consult the matching generation’s expansion table. Similar model codes do not establish identical wiring or compatibility.
The module adds 16 Y outputs and no X inputs. For example, as the first digital extension after an ES CPU with 16 outputs, its program allocation is Y20–Y37. Rebuild the address list when the host I/O configuration or preceding modules change.
Programming software and cable
No separate program is downloaded to DVP16XN11T. Outputs are controlled by the host PLC program. The legacy ES/EX manufacturer sheet names WPLSoft. If using ISPSoft, verify support for the exact CPU in the selected software version.
Connect the computer to the host CPU’s RS-232 COM1 port. The manufacturer cable guide shows UC-PRG020-12A USB-to-RS-232 and UC-MS020-01A serial options for ES/EX CPUs. The serial cable may require an appropriate USB-to-RS-232 converter. Check pinout, driver and COM port when selecting a Delta PLC cable; the expansion connection is not a programming port.
Editor’s Note
Check the complete DVP16XN11T label. XN11R has relay outputs, while XM11N is an input module. Terminal count alone is not enough to select a replacement.
An unloaded multimeter reading can mislead on an NPN output. With a compatible CPU and machine movement prevented, test each channel using a fused, low-current 24 V load.
If the LED lights but the load stays off, check field power, the corresponding C terminal and wiring first. An output indicator alone does not prove the power transistor is healthy.
If an output remains conducting, isolate power and disconnect the load before checking for a shorted transistor. Resolve excessive load or coil transients before replacing components.
Do not treat 0.3 A as valid at every cabinet temperature. Correct discoloured terminals, loose connections and inadequate ventilation to prevent a repeat failure.
Back up the CPU program, module order and Y addresses before replacement. Remove test forces afterwards. These are general inspection suggestions, not a claim that a particular used unit has been tested.
Related models and functional differences
DVP16XN11R: 16 relay outputs. DVP08XN11T: 8 transistor outputs. DVP24XN11T: 24 transistor outputs. DVP32XP11T: 16 inputs + 16 transistor outputs. DVP24XP11T: 16 inputs + 8 transistor outputs.
For input expansion, review DVP16XM11N and DVP08XM11N; for smaller mixed I/O, see DVP08XP11T. Relay-output options include DVP08XN11R and DVP24XN11R. Compare the I/O allocation and field wiring separately for each option.
PDF files and related topics
Use our Delta DVP PLC files page for series documents. The DIDO sheet contains English/Chinese sections; the legacy CPU sheet and cable guide are in English.
What is a PLC? · Delta PLC · DVP expansion modules · Modbus RS-485 communication
Navigation: Delta main page · ES/EX modules · DVP PDF archive
External references
Delta DVP-ES/EX DIDO — 15 August 2013, 5011671702-ED02: exact model, transistor limits, terminal drawing and addressing; English/Chinese, 2 large PDF pages.
Delta ES/EX manufacturer sheet — 4 July 2006: CPU, extension model table and WPLSoft; English, 2 pages. Delta PLC/HMI Cable Selection Guide — 15 August 2019: English, 175 pages; ES/EX host connection on PDF page 14, printed page 1-5.