Delta DVP16XM11N

Delta DVP16XM11N – 16-Digital-Input ES/EX Expansion Module

Delta DVP16XM11N adds 16 digital 24 V DC inputs to legacy DVP-ES/EX systems and has no outputs. It does not execute its own PLC program; as an input expansion module, it transfers field signals to the host CPU. XM identifies input expansion and the final N identifies the absence of outputs.

Applications include pushbuttons, limit switches, inductive sensors, photoelectric sensors and suitable capacitive sensors. DVP16XM211N, DVP16XM01N and DVP16HM11N are different codes. Compare generation, enclosure, expansion interface and CPU compatibility before considering a replacement.

Power and system connection

The unit operates in a 24 V DC system. The legacy manufacturer manual classifies it as an extension without a power supply, rather than an AC-powered extension generating its own 24 V service supply. Arrange electronic power, input circuits and sensor power according to the exact terminal diagram and host expansion budget. Never apply mains voltage to X or S/S terminals.

At a nominal 5 mA per input, all 16 inputs ON represent approximately 80 mA of input-circuit load. This is not the module’s total consumption; electronic and sensor loads must also be considered. Plan the 24 V supply, fuses and protective grounding together. Do not assign another unit’s service-output capacity to this model.

Input specifications and PNP/NPN wiring

16 inputs, 0 outputs. Local terminals are labelled X0–X7 and X10–X17. The ES/EX DIDO extension sheet specifies 24 V DC, approximately 5 mA, ON above 16.5 V, OFF below 8 V, and approximately 20 ms response. Inputs have optocoupler isolation and status LEDs; this does not establish independent isolation between channels.

For PNP sensors connect S/S to 0 V; for NPN sensors connect S/S to +24 V, with the sensor output connected to its X terminal. Check NPN versus PNP and sink/source wiring together. Confirm which inputs share each S/S connection in the terminal plan; do not mix different sensor logic indiscriminately within a common group.

A digital input detects ON/OFF state. Use a suitable analog I/O module for 0–10 V or 4–20 mA measurements. With two-wire sensors, check OFF-state leakage and ON-state voltage drop. The approximately 20 ms response makes these inputs unsuitable as dedicated high-speed encoder counters. CPU-specific 10 ms and D1020/D1021 filter descriptions must not be assigned directly to this extension.

Addressing and a program example

DVP X addresses use octal numbering: X10 follows X7, and X0–X17 contains 16 points. Local labels need not match the CPU addresses. For example, as the first digital extension after a 32ES CPU with 16 inputs, a suitable ES/EX arrangement assigns X20–X37. A different CPU or preceding modules changes the starting address.

In a separate test project with this allocation confirmed, choose an unused internal relay and use LD X20 / OUT M100 to monitor the first input through the CPU’s M100 bit. The module has no physical Y outputs. The ladder program runs in the host CPU; no analog-module CR setup or FROM/TO template is required for these digital inputs.

Programming software and cable

DVP16XM11N has no separate user-program download. The primary tool for legacy ES/EX host projects is WPLSoft. If using ISPSoft, confirm support for the exact CPU and software release, setting up COMMGR when required. Target the host CPU in the project. Back up the existing program and necessary data before making changes.

The ES/EX CPU’s 8-pin mini-DIN RS-232 COM1 port can use a UC-PRG020-12A USB-to-RS-232 programming cable. Alternatively, use a UC-MS020-01A serial cable with a suitable PC serial port or USB-to-RS-232 converter. Older documents also list DVPACAB215 / DVPACAB230. Check the driver, pinout and COM number. Connect programming equipment to the CPU, never to this module’s X or S/S terminals.

Mounting and compatibility

Mount the module on a 35 mm DIN rail or with suitable screws inside a cabinet. Operating temperature is 0–55°C. Connect the side expansion interface with power removed and keep ventilation openings clear. For DVP-ES and DVP-EX, check the exact CPU, module order, total I/O capacity and power budget. A similar connector does not establish compatibility with another family.

Editor’s Note

Read the complete 16XM11N code first. An extra 2 or an HM/XM difference can lead you to another family. Photograph the label and existing connections before proceeding.

If an input LED stays off, check sensor power and S/S first. Establish whether the sensor is PNP or NPN before changing the common connection. An incorrect reference can make a healthy input appear faulty.

If the LED changes but the CPU does not see it, check expansion order and the X address being monitored. Local X0 may be X20 in the program. Test every input rather than judging the unit from its first channel.

Take multimeter readings at the module terminals using the correct circuit reference. A brief sensor pulse may be missed because of input delay and CPU scanning; do not use a short pulse as the only functional test.

If a whole group disappears, inspect the common wire, terminal connections and expansion connector. Check for short circuits, corrosion and damaged field cables. Never disconnect or reconnect the expansion interface with power applied.

Test all 16 inputs on a used module with a compatible CPU. Isolate machine motion during testing, since an input transition can trigger an action in the existing program. Remember that the module itself has no outputs.

PDF manuals

Start with our Delta DVP PLC files page. The DVP-ES/EX English series sheet – 5011634301-YIE1, 2006-07-04 includes the exact DVP16XM11N 16-input / 0-output selection row. CPU program memory, communication ports and output features elsewhere in the sheet do not belong to this input module.

Related models and navigation

DVP08XM11N provides 8 inputs in the same legacy ES/EX family. DVP16XN11R provides 16 relay outputs and DVP16XN11T provides 16 transistor outputs; neither is a direct substitute for an input module. DVP16XM211N is another generation, while DVP16HM11N is a 16-input EH-family module. Compare the exact CPU and wiring plan before replacement.

Delta main page | Delta PLC | DVP PLC series | DVP expansion modules | ES/EX expansion modules | DVP16XM11N model page | DVP PDF files

External references

Delta ES/EX DIDO extension sheet – 2013-08-15 distribution record; Legacy manufacturer DVP manual – DVP16XM11N model and wiring sections, archive copy; Delta PLC/HMI Cable Selection Guide – 2019-08-15. Manufacturer download-centre access conditions apply; compare older editions against the actual equipment label.