Delta DVP24XN11T
Delta DVP24XN11T – 24-Point Transistor Output Expansion Module
Delta DVP24XN11T adds 24 digital transistor outputs to legacy DVP-ES/EX systems and uses a 24 V DC supply. It has no digital inputs. It operates through the host PLC program's Y addresses rather than running as an independent PLC CPU. In this family, XN identifies digital output expansion, T identifies transistor outputs, and 11 denotes the DC-powered H-type construction.
Typical automation duties include controlling suitable DC valves, indication lamps, interposing relays and electronic command inputs. DVP24XP11T is a different mixed module with 16 inputs and eight outputs. DVP24XN11R uses relay outputs; changing between relay and transistor circuits requires a wiring and load review.
Supply and NPN output wiring
The nominal module supply is 24 V DC. Check the marked supply terminals, 0 V reference and polarity. Do not copy AC-powered DVP24XN00T wiring onto the 11T version. When selecting a power supply or DIN rail power supply, calculate the electronics requirement separately from the total field-load current. Include load current in conductor and fuse selection.
The outputs use an NPN sinking, open-collector arrangement. Typically, a load connects between DC positive and its Y output, with the corresponding output commons referenced to 0 V as shown in the manufacturer's circuit. These are semiconductor outputs rather than voltage-free relay contacts, and they do not directly switch AC loads. Check PNP/NPN and sink/source compatibility when controlling another device's input.
Output current and temperature limits
The ED02 transistor table gives a 30 V DC voltage limit and 2 A per COM. Current per output depends on temperature: 0.3 A at 40 °C; 0.2 A at 45 °C; 0.15 A at 50 °C; 0.1 A at 55 °C. The 0.3 A figure is therefore not valid across the full operating-temperature range or as an unrestricted total-load allowance. Check the physical common arrangement against the terminal diagram.
For a contactor or valve coil, verify DC coil voltage and inrush. Use suitable fuses and inductive-load suppression. A flyback diode must have correct polarity and suit the coil manufacturer's recommendations. If the load exceeds the permitted limits, use a suitable interposing relay and socket or interface. The 2 A-per-point ratings of relay versions do not apply to this transistor model.
The 2013 ED02 edition specifies approximately 15 µs ON and 25 µs OFF response, with a maximum switching frequency of 1 kHz; actual frequency is affected by CPU scan time. Do not confuse this table with the host CPU's high-speed pulse-output specification. For a variable frequency drive or servo command, verify input voltage, circuit type, supported function and the required Y address separately.
Host compatibility, software and cables
DVP24XN11T belongs to the DVP-ES/EX expansion module family. With a DVP-ES or DVP-EX host, check the exact CPU, expansion port, module sequence and I/O capacity. Do not transfer specifications from similarly named ES2/EX2, E2 or EH modules; cross-generation compatibility requires its own documentation.
WPLSoft is the established programming tool. Use the host CPU's Y outputs in its Ladder program; no separate user program is downloaded into DVP24XN11T. Consider ISPSoft only after confirming that the actual CPU and firmware are supported by the selected software release. Ordinary digital outputs do not require analogue-module FROM/TO register access.
Connect the programming cable to the host CPU's RS-232 port. The legacy ES/EX manufacturer sheet lists DVPACAB230 (3 m) and DVPACAB215 (1.5 m) PC-to-PLC cables. A computer without a serial port requires a suitable USB-to-RS-232 converter, driver and COM setting; a TTL converter is not equivalent. DVPACAB403 (30 cm) is an expansion interconnection cable, rather than a PLC programming cable.
Y addressing, mounting and testing
Delta X/Y addresses use octal numbering. Example: if the host outputs occupy Y0–Y17 and there is no preceding output expansion, a first 24-output module may occupy Y20–Y47. Verify the starting address against the actual CPU and expansion sequence. This unit has no X input addresses. Adding or moving a module can affect subsequent Y assignments.
Start bench testing with a known, low-power DC load and check each output separately. Compare the HMI or SCADA command, CPU Y bit, module LED and physical load response. An illuminated LED does not prove a healthy output transistor, and an unloaded multimeter reading can be misleading.
Inductive sensors, photoelectric sensors and capacitive sensors connect to suitable CPU or input-module terminals; these sensors do not add inputs to DVP24XN11T. High-speed encoder signals require suitable counter inputs as well. Approximate dimensions are 155 × 100 × 82 mm (width × height × depth), with 35 mm DIN rail or M4 screw mounting and a 0–55 °C operating range. Respect ventilation clearances and signal/power cable separation when arranging panel components.
Editor's Note
Read the complete code first: 24XN11T is a DC-powered 24-output unit. Overlooking XP/XN or 00/11 distinctions can result in selecting the wrong device.
Do not assess a transistor output as though it were a relay contact using continuity mode alone. Apply the correct supply polarity and test every channel with a known load.
If an output stays active, isolate the load wiring and distinguish a failed transistor from a cable short or program command. A working load with its output LED off deserves further investigation.
If several channels fail together, inspect output commons, field fuses and the 0 V reference. A larger fuse does not repair a short circuit or overload.
A board that passes a cool bench test may fail inside a hot enclosure. Measure coil current, calculate common-terminal totals and remember the 0.1 A-per-point limit at 55 °C.
Record the wiring and Y assignments and back up the CPU program before removal. Do not replace a powered module. Test all repaired outputs under load before declaring the unit serviceable.
PDF documents and related models
Use our Delta DVP PLC PDF files page for technical documents. The main wiring reference is DVP-ES/EX DIDO 5011671702-ED02, 15 August 2013. The older 5011634301-YIE1, 4 July 2006 ES/EX sheet is retained for model, WPLSoft and cable references. Do not mix its earlier response-time figures with the later expansion-unit table.
Related topics: DVP24XN11R · DVP16XN11T · DVP08XN11T · DVP16XN11R · DVP08XN11R · DVP08XP11R · DVP08XP11T · DVP24XP11R · DVP32XP11T · DVP08XM11N · DVP16XM11N. These links compare functions; they are not a list of interchangeable replacements.
Navigation: DVP24XN11T main page · DVP expansion modules · Delta PLC · Delta DVP PLC series · Delta PLC and HMI manuals · Second-hand Delta products · What is a PLC?.
External references
Delta DVP-ES/EX DIDO ED02 – manufacturer document hosted by a distributor.