Delta DVP08XP11R
Delta DVP08XP11R – Digital Expansion Module with 4 Inputs and 4 Relay Outputs
Delta DVP08XP11R is a mixed I/O expansion module in the DVP ES / EX module family, providing 4 digital inputs and 4 relay outputs. It uses a 24 V DC supply to add a small number of field connections to a compatible Delta PLC. The connected host CPU executes the user program.
Applications include pushbuttons, limit switches, inductive sensors and photoelectric sensors, with suitable indicator, interposing relay or contactor control circuits. The 08 code represents 8 physical points: 4 inputs plus 4 outputs. The distinction between analog and digital inputs matters; this module does not measure analog values.
Supply, dimensions and input characteristics
Supply: nominal 24 V DC at the +24 V and 0 V terminals. The ES/EX DIDO manufacturer sheet lists 5 W maximum consumption for this DC expansion group. Dimensions are approximately 42 mm wide × 100 mm high × 82 mm deep, with 35 mm DIN rail mounting. Include the module and field loads when selecting a suitable DIN rail power supply.
Inputs: X0, X1, X2 and X3; 24 V DC Sink/Source, nominally 5 mA per channel. Input response is approximately 20 ms. Fast encoder pulses require suitable high-speed input or counter hardware. The CPU scan also affects overall response.
PNP / NPN wiring and common terminals
For a PNP sensor, connect S/S to 0 V; the sensor output applies +24 V to the selected X input. For an NPN sensor, connect S/S to +24 V; the sensor output pulls X toward 0 V. Verify sensor type, power and reference together when selecting the Sink/Source arrangement.
0 V, S/S and C0 have different functions. The 0 V terminal is the module supply return, S/S is the input common, and C0 is the relay output common. Select the C0 load supply for the controlled circuit; do not automatically treat C0 as 0 V. Follow the manufacturer diagram when arranging external power supplies and reference connections.
Relay outputs and the C0 current limit
Outputs are Y0, Y1, Y2 and Y3, sharing common C0. The R suffix identifies relay outputs. The sheet specifies 2 A per output and 5 A per common, voltage limits of 250 V AC / 30 V DC, and additional load limits of 90 W resistive / 75 VA inductive. Apply these limits together when selecting loads.
Example: four outputs drawing 1.5 A each total 6 A and exceed C0’s 5 A limit. Keeping each output below 2 A is insufficient by itself. Protect the load circuit with suitable fuses and consider an appropriate interposing relay and socket for high inrush or frequent switching.
Relay response is approximately 10 ms, with a specified maximum switching frequency of 1 Hz. These contacts are unsuitable for servo pulse commands or fast PWM. Suitable flyback diodes on DC coils and manufacturer-recommended RC/MOV suppression on AC coils can reduce contact stress.
CPU compatibility and similar modules
DVP08XP11R appears in the original DVP-ES and DVP-EX expansion documents. Check the exact CPU, expansion connection, total I/O and module order. A similar enclosure or an XP designation alone does not establish compatibility with a different generation.
DVP08XP11T provides 4 inputs and 4 transistor outputs. DVP08XM11N provides 8 inputs only, while DVP08XN11R provides 8 relay outputs only. For more mixed I/O, compare DVP24XP11R with 16 inputs and 8 relay outputs. These units perform different electrical and physical roles; output technology and addressing must be considered during replacement.
Programming software and cable
No separate user program is downloaded to DVP08XP11R. Use X contacts and Y coils in the host CPU’s supported WPLSoft or ISPSoft project. For ISPSoft, configure the COMMGR driver and correct COM port. Preserve the CPU selection and format of an existing ES/EX project.
The ES/EX cable guide shows the UC-PRG020-12A USB programming cable connected to the host CPU’s COM1 RS-232 port. UC-MS020-01A is an alternative for a PC RS-232 port or suitable USB-to-RS-232 converter. Install the USB cable driver and select its assigned COM port. Connect to the host CPU; the module’s expansion connector is not a PC interface.
Addressing: 4 physical channels in an 8-address block
The manufacturer sheet allocates DVP08XP11R an 8-input and 8-output address block. The upper four addresses in each direction have no physical channels. This allocation does not mean the module has 8 real inputs and 8 real outputs.
Example: as the first digital expansion after a DVP32ES00R2 CPU, real inputs occupy X20–X23 and real outputs occupy Y20–Y23. X24–X27 and Y24–Y27 have no physical channels. The following digital expansion starts in the X30/Y30 area in this example. Recheck the actual starting addresses whenever module order changes.
The sheet recommends placing this type of expansion with unused addresses at the end of the chain where possible. Match all four input LEDs to actual X bits and all four relay contacts to actual Y bits. The module does not require its own Modbus station address.
Editor’s Note
Read the full label: DVP08XP11R. The eight-point description means four inputs and four relay outputs, not eight channels in either direction.
Before applying power, trace the +24 V and 0 V supply, S/S input common and C0 load common separately. Automatically wiring C0 to 0 V can make a working output appear faulty.
Test all four inputs and all four relays with a compatible host CPU. A clicking relay does not establish a healthy contact under load; use an appropriate low-power test load first.
Do not wait for X24 or Y24 to respond in the first-expansion example above: those addresses have no physical channels. Record the module order and actual starting addresses before troubleshooting.
For a welded contact or excessive voltage drop under load, inspect the relay, solder joints and C0 terminal. A replacement relay must match coil voltage, contact arrangement, pinout and load capability. Correct excessive load or coil transients as well.
For a used unit, request label, connector and terminal photographs together with a test record. Check cabinet grounding and electromagnetic interference conditions. Safely disable machine movement before testing outputs.
PDF documents and related topics
Use the Delta DVP PLC PDF files page for the instruction sheet, legacy catalogue and CPU cable guide. Our ES/EX manufacturer instruction sheet (English) also includes DVP08XP11R. Document language is independent of page language.
For the basic system structure, see What is a PLC?, PLC accessories and HMI panels. Timers and counters perform different device functions; this module’s control logic runs in the host CPU.
Consider panel components, cable routing and load protection together. Related hardware is listed under DVP expansion modules and DVP PLC series.
Navigation: Delta home · Delta PLC · ES / EX modules · DVP files
External references
Delta ES/EX DIDO manufacturer sheet – 5011671702-ED02, English/Chinese · Delta WPLSoft / ISPSoft explanation