Delta DVP32XP11T — 16 Input and 16 Transistor Output Expansion Module

Delta DVP32XP11T is a 24 V DC-powered, 32-point digital expansion unit in the legacy DVP ES/EX module family from Delta automation. Its total consists of 16 digital inputs and 16 NPN transistor outputs, allowing a host PLC to receive sensor/button signals and switch DC control loads.

XP identifies mixed I/O expansion, 11 the DC-powered H-type construction, and T transistor outputs. Within the DVP PLC series, this is an expansion unit with no independent CPU program. When considering a newer generation, compare the complete ordering code and host family.

Supply, dimensions and mounting

Nominal supply is 24 V DC. Check polarity, terminal identification and the host power budget, allowing separately for field-load power. DVP32XP00T also provides 16 inputs/16 outputs but uses 100–240 V AC power; its supply wiring must not be treated as interchangeable.

Dimensions: approximately 155 × 100 × 82 mm (width × height × depth). Mounting: 35 mm DIN rail or direct mounting with M4 screws. Operating temperature: 0–55 °C. The manufacturer layout calls for at least 50 mm of surrounding ventilation clearance.

Digital inputs: NPN/PNP wiring

The 16 inputs accept 24 V DC sink/source wiring. Nominal current is approximately 5 mA per input, with an input response of approximately 20 ms. The stated ON threshold is above 16.5 V and the OFF threshold below 8 V. These are not equivalent to dedicated high-speed encoder/counter inputs.

For PNP sensors, connect input common S/S to 0 V; for NPN sensors, connect S/S to +24 V. Devices sharing an input common must use a compatible wiring arrangement. Input sink/source selection does not change the outputs into PNP outputs.

Transistor outputs and current limits

The 16 outputs are NPN open-collector, sinking outputs. Connect the appropriate common to 0 V and the opposite side of the load to the positive DC supply, following the actual terminal grouping. The output voltage ceiling is 30 V DC, with a total limit of 2 A per common.

For resistive loads, the permitted current per channel falls from 0.3 A at 40 °C to 0.2 A at 45 °C, 0.15 A at 50 °C and 0.1 A at 55 °C. Both channel and common limits apply. Use an appropriate flyback diode/suppression device for inductive DC loads.

The DIDO sheet states electrical transitions of approximately 15 µs ON and 25 µs OFF and a switching frequency of up to 1 kHz, affected by the PLC scan. These figures do not automatically extend the host CPU’s high-speed pulse/positioning functions to this module.

Compatibility and I/O addressing

DVP32XP11T appears in the digital expansion documentation for DVP-ES and DVP-EX. Check the separate expansion tables when working with DVP-ES2 or DVP-EX2. Connector, power and addressing compatibility cannot be inferred from similar model names.

Local inputs use X0–X17 and outputs Y0–Y17, with octal numbering. Program addresses depend on the CPU and module order. For example, as the first digital extension after a 16-input/16-output ES CPU, its inputs occupy X20–X37 and outputs Y20–Y37. Recalculate the allocation when preceding modules are present.

Software and programming cable

No separate program is downloaded to this module. Its I/O is used by the host PLC program. The legacy ES/EX manufacturer sheet names WPLSoft as its programming tool. If using ISPSoft, confirm that the selected version lists the exact host CPU as a supported target.

Connect the computer to the host CPU’s RS-232 COM1 port. The manufacturer cable guide shows UC-PRG020-12A USB-to-RS-232 and UC-MS020-01A serial-cable options for ES/EX CPUs. The serial option may require an appropriate USB-to-RS-232 converter. Check the pinout, USB driver and COM port when selecting a Delta PLC cable. The inter-module expansion cable serves a different purpose.

Editor’s Note

Read the complete XP11T label before wiring. XP11R has relay outputs, while XP00T uses AC power. Similar housings do not prove identical connections.

If an input LED stays off, check the sensor’s NPN/PNP type, S/S connection and voltage while the sensor operates. An incorrect common can make a healthy module appear faulty.

An unloaded multimeter reading can be misleading on NPN outputs. With a compatible CPU and field wiring isolated to prevent movement, use a fused, low-current 24 V test load and observe both its response and the output LED.

If an output remains conducting, disconnect the load and check for a shorted transistor. Investigate coil transients, load current and the 0 V connection before replacing components.

For a failed group, check its common and field supply first. Do not continue using the 0.3 A rating as cabinet temperature rises; apply the temperature derating.

Before replacement, retain the program backup, module order and X/Y allocation. Remove test forces afterwards. These are general inspection suggestions, not certification that a particular used unit has been tested.

Related models and selection differences

DVP32XP11R: 16 inputs + 16 relay outputs. DVP24XP11T: 16 inputs + 8 transistor outputs. DVP08XP11T: 4 inputs + 4 transistor outputs. DVP16XN11T: 16 transistor outputs only. These options differ in I/O distribution or output technology.

For input-only expansion, consider DVP16XM11N or DVP08XM11N. For mixed relay I/O, review DVP24XP11R and DVP08XP11R. Check the host family, terminal arrangement and power budget for each selection.

PDF files and related topics

Use our Delta DVP PLC files page to follow the series documentation. The DIDO sheet contains English and Chinese sections; the CPU sheet and cable guide are in English.

What is a PLC? · Delta PLC · DVP expansion modules · Modbus RS-485 communication

Navigation: Delta main page · ES/EX modules · DVP PDF archive

External references

Delta DVP-ES/EX DIDO — 15 August 2013, 5011671702-ED02, English/Chinese: exact model, I/O wiring, current limits and addressing; 2 large PDF pages.

Delta ES/EX manufacturer sheet — 4 July 2006, English: host CPU, expansion model table and WPLSoft reference; 2 pages. Delta PLC/HMI Cable Selection Guide — 15 August 2019, English: 175 pages; ES/EX connection on PDF page 14, printed page 1-5.