Delta DVP24XP00R

Delta DVP24XP00R – AC-Powered Expansion Unit with 16 Inputs and 8 Relay Outputs

Delta DVP24XP00R is an expansion unit in the DVP ES/EX module family, providing 16 digital 24 V DC inputs and 8 relay outputs. Its main supply is 100–240 V AC, and its 24 points are the combined input/output count. It extends a suitable host PLC rather than running an independent user program.

Typical tasks include reading pushbuttons, limit switches and sensors and operating suitable valves, interposing relays and indicators. When selecting DVP expansion modules, read the 00/11 supply code and R/T output suffix together. DVP24XP00R does not provide analog measurement channels.

Supply and digital inputs

Main supply: 100–240 V AC, 50/60 Hz, through L/N. The ES/EX DIDO sheet specifies 25 VA maximum consumption and a 400 mA auxiliary 24 V DC output for the 24XP00 group. Include input circuits and sensors in the auxiliary supply budget; do not directly parallel it with another power supply.

Inputs: 16 channels, 24 V DC, nominally 5 mA, with sink/source wiring through S/S. The expansion sheet specifies an input response of approximately 20 ms; these inputs must not automatically be treated as high-speed encoder-counter inputs.

PNP/NPN wiring and relay outputs

For PNP sensors, connect S/S to 0 V; for NPN sensors, connect S/S to +24 V. Connect the sensor signal to the relevant X input. Use a consistent arrangement within each common group. Never apply the AC main supply to X, S/S or auxiliary 24 V terminals.

Relay outputs: 8 channels; the sheet specifies 2 A/channel, 5 A/COM and 250 V AC/30 V DC limits. It also lists 90 W resistive and 75 VA inductive load limits. Apply current, voltage and load-type limits together rather than calculating an allowable load simply by multiplying 2 A by mains voltage.

The contacts switch an externally supplied load circuit; a Y output does not generate 24 V by itself. Wire the commons according to the actual 00R terminal diagram, rather than copying the 11R arrangement. Relay response is approximately 10 ms, and the sheet specifies a maximum switching rate of 1 Hz. Consider suitable diode suppression for DC coils and RC/MOV suppression for AC coils.

Host PLC family

The model appears in the original DVP-ES and DVP-EX expansion documentation. Verify the exact host CPU, module order, expansion connection and total I/O limit. Different Delta DVP series must not be assumed to share the same expansion arrangement.

DVP24XP200R is a different code belonging to the DVP-ES2/DVP-EX2 generation. Keep the additional 2 in the identification; it is not automatically the same unit or a direct replacement for DVP24XP00R.

X/Y addressing example

When fitted as the first digital expansion after a suitable DVP32ES00R2 host, an example allocation is X20–X37 and Y20–Y27. Local X0 maps to X20 and X17 to X37; local Y0 maps to Y20 and Y7 to Y27. Preceding modules or a different CPU can change these starting addresses.

DVP X/Y numbers use octal notation: X27 is followed by X30. Distinguish the terminal labels from the system addresses in the project. After adding a module, verify every input and output address using online monitoring.

Programming software and cable

The program is downloaded to the host CPU, not DVP24XP00R. The original ES/EX manufacturer document identifies WPLSoft. If using ISPSoft, check support for the host CPU and project version. Select the appropriate Delta PLC software according to the main unit rather than the expansion code.

The legacy ES/EX guide lists DVPACAB215 (1.5 m) and DVPACAB230 (3 m) for PC connections. Connect to the host CPU’s RS-232 programming port. A PC without a serial port requires a suitable USB-to-RS-232 adapter and driver. Verify the pinout and communication settings against the CPU documentation; see DVP programming cables for related options.

DVPACAB403 is listed as a 30 cm expansion connection cable and is not a PC programming cable. Disconnect power before adding, removing or rewiring the module.

Differences from related models

DVP24XP11R provides the same 16-input/8-relay-output arrangement with a 24 V DC supply. DVP24XP11T is a DC-powered transistor-output variant. DVP24XP00T is the AC-powered transistor-output model and must not be substituted using unchanged relay-output wiring.

DVP32XP00R provides 16 inputs/16 relay outputs with AC power, while DVP32XP11R provides that I/O arrangement with DC power. The smaller DVP08XP11R provides 4 inputs/4 relay outputs. Account for point count, supply and terminal differences when comparing them.

Editor’s Note – Field testing and used equipment

Confirm the complete DVP24XP00R label first. Do not connect a similar-looking 11R or 200R unit on appearance alone.

Before removing the old module, photograph L/N, S/S, output commons and the expansion order. Avoid reconstructing relay-common wiring from memory.

Use a suitable host CPU to test all 16 inputs and 8 relay outputs individually. Compare input LEDs with X bits, then compare Y bits with actual contact behaviour.

A clicking relay does not prove a sound contact. Check switching and voltage drop with a suitable low-power load; investigate the common supply and fuse if an entire group fails.

For welded or blackened contacts, check load inrush and coil suppression. Replacing a relay without correcting the cause can bring the fault back.

For used equipment, obtain a record of the CPU and channels used in testing. On a machine, arrange output testing so that it cannot create unintended movement.

PDF documents and related topics

Follow the shared documents on our Delta DVP PLC PDF files page. The original ES/EX manufacturer guide hosted on our site includes this model. Its archive record links the 2013 ES/EX DIDO expansion sheet and 2006 ES/EX guide, with each document’s language and edition recorded separately.

For input-only expansion, see DVP08XM11N and DVP16XM11N. For relay-output-only expansion, compare DVP08XN11R, DVP16XN11R and DVP24XN11R.

Navigation: Delta main page · Delta PLC · ES/EX modules · DVP PDF archive