Delta DVP32SM11N

Delta DVP32SM11N 32-Channel Digital Input Module

The Delta DVP32SM11N is an expansion module that adds 32 digital inputs at 24 V DC to a compatible DVP Slim PLC. It has 32 inputs and 0 outputs. A 40-pin MIL connector carries field signals from sensors, position switches and dry contacts.

See Delta DVP PLC files for the pinout, S/S wiring and addressing example.

24 V DC inputs and field wiring

Delta specifies a nominal input of 24 V DC and 5 mA per channel, an input impedance of 4.7 kΩ, and a response time of approximately 10 ms. The CPU powers the module electronics. Plan the 24 V DC field signal circuit together with its S/S commons.

Use the DVPAETB-ID32A breakout terminal and DVPACAB7A10 cable to terminate field wiring in the cabinet. The cable is 1 m long with 40 pins at each end. Delta’s cable selection guide also shows UB-10-ID32A with UC-ET010-24A or UC-ET010-24B cables.

Selecting sensors and contacts

On a conveyor, an inductive sensor can detect a metal pallet, a photoelectric sensor can detect a passing carton, and a limit switch can report end of travel. When replacing a sensor, check its PNP or NPN output and its NO or NC operation separately. Typical three-wire DC wiring uses S/S at 0 V for PNP and S/S at +24 V for NPN. Check the relevant common group in Delta’s diagram when choosing the sink or source connection.

Off-state leakage from a two-wire electronic sensor can cause a false ON state. Monitor both sensor states at the PLC with the load connected. For fast parts, consider counting frequency, pulse width and PLC scan time. If the pulse approaches the module’s roughly 10 ms response time, use a compatible CPU’s high-speed counter input.

Compatible CPUs, X addressing and programming

Fit the module to the right-side expansion bus of a compatible DVP Slim CPU. Check the host’s expansion capacity and module order in DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 and DVP-SE projects. In Delta’s first digital expansion example, local terminals X0–X37 map to X20–X57 in the PLC. For example, terminal X0 → PLC X20. Addresses are octal, so X30 follows X27.

Monitor the X bits through the CPU in WPLSoft or ISPSoft. For the DVP14SS211R, use the UC-PRG020-12A cable on COM1 RS-232. For the DVP12SE11R, use an RJ45 Ethernet cable at the CPU. See DVP programming cables for other CPU models.

Editor’s Note

Inspect the used set. Confirm 32SM11N on the label. Inspect the 40-pin socket, cable latches and field terminal block together.

Switch off power before fitting the module. Check that the side-bus connector is seated and the ribbon cable is aligned to pin 1.

Start with one input. Apply a suitable 24 V DC test signal to one channel. Check that its indicator and the matching PLC X bit change together.

Check the common if an entire group fails. Inspect the S/S connection, field supply and relevant ribbon-cable conductors.

Verify the first and last channels after replacement. If module order changed, compare the original program addresses with the new terminal assignments.

Related topics

DVP08SM11N 8 inputs · DVP16SM11N 16 inputs · DVP32SN11TN 32 outputs

Delta pages

DVP expansion modules · Delta DVP PLC series · Delta PLC · Delta and used models

External references

DVP32SM11N / DVP32SN11TN Instruction Sheet · Delta DVPAETB External Terminal Instruction Sheet · Delta DVP Series Module Manual · Delta PLC/HMI Cable Selection Guide