Delta DVP16SM11N

Delta DVP16SM11N – 16-Channel 24 V DC Digital Input Module

Delta DVP16SM11N is a DVP Slim module that adds 16 digital inputs on the right side of a compatible PLC CPU. Its 16 DI / 0 DO layout brings position, limit and status signals into the PLC. Understanding how PLC input and output modules work helps distinguish similar order codes.

Power supply and input ratings

The CPU expansion bus powers the module. The field inputs use 24 V DC and Delta specifies approximately 5 mA per channel. Input impedance is 4.7 kΩ and response time is approximately 10 ms. The ON threshold is above 16.5 V and the OFF threshold is below 8 V. Isolate power before fitting the module on a 35 mm DIN rail and mating the expansion connector.

S/S commons and sensor wiring

The first S/S common serves X0–X7. The second serves X10–X17. For a PNP sensor, connect that group’s S/S to 0 V and the sensor’s switching output to X. For an NPN sensor, connect S/S to +24 V and the switching output to X. Select the sensors in each group to match its common connection. See sinking and sourcing connections for current flow diagrams.

An inductive sensor can detect a metal part, a photoelectric sensor can detect a passing box, and a limit switch can detect the end of mechanical travel. The module reads their ON/OFF state. For a device that sends a measured value, check the distinction between analog and digital inputs. On machines that need frequent disconnection, cable and connector selection also affects maintenance time.

If the sensor state and PLC input disagree, measure the voltage between X and its group’s S/S terminal. If the input stays on, check for off-state leakage from a two-wire sensor. For intermittent faults, check grounding and keep signal cables clear of power wiring. For short encoder pulses, consider the CPU’s high-speed counter inputs and compare the actual pulse width with the module’s response time.

CPU compatibility, addressing and software

Match the module to the exact CPU and its right-side expansion limits in series such as DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 and DVP-SE. The X markings on the case are local. For example, as the first digital input expansion on an SS2 CPU, it uses X20–X27 and X30–X37 in the program. Addressing is octal and preceding input modules shift the allocation.

The PLC program reads the inputs as X bits. Use WPLSoft or a compatible ISPSoft release according to the CPU and project version. On a DVP14SS211R/T, connect the UC-PRG020-12A cable to the CPU’s COM1 RS-232 port. Install the USB serial driver and select the virtual COM port. For other CPUs, choose the programming cable for the port provided.

Related models

DVP08SM11N has eight DC inputs, while DVP08SM10N has eight AC inputs. DVP32SM11N provides 32 DC inputs with a MIL connector. DVP16SN11T adds 16 transistor outputs. Check the SM/SN code, field voltage and connector when selecting a spare.

Editor’s Note

When buying a spare, check both S/S terminals, the side expansion connector and the rail clip.

If eight inputs fail together, measure the S/S connection and field supply for that group first.

If the input LED lights and the X bit stays unchanged, start troubleshooting by comparing module order with the program address.

With motion outputs disabled, verify one channel in each group using a known good sensor or dry contact.

Check emergency stop and guard circuits against the machine’s safety design.

PDF manuals and related pages