Delta DVPPCC01
Delta DVPPCC01 Program and Parameter Copy Module
Delta DVPPCC01 is a memory accessory for Delta DVP PLC systems, used to read programs and parameters through the PLC COM port and transfer them to a compatible PLC. Also identified as DVP-PCC01 in manufacturer documentation, it is used for service backups and loading programs into compatible controllers on matching machines.
The Delta catalogue identifies it as a 64K-word data backup memory card. This does not increase the connected PLC's program capacity to 64K steps. When choosing DVP memory accessories, distinguish backup storage capacity from the program capacity supported by the CPU.
What do RD and WR mean?
RD: PLC → DVPPCC01. Data is read from the PLC into the copy module. WR: DVPPCC01 → PLC. The stored copy is written to the target PLC. Select the direction before connection. Do not change the switch, remove the module or interrupt PLC power while a transfer is in progress.
The POWER, COM, OK and ERR indicators show power, communication, completion and error conditions. The outline drawing shows a 33 × 66.3 mm body and a 300 mm connection cable. ERASE is the data clearing button; consult the applicable instructions before using it.
Which DVP PLCs are supported?
The manufacturer's earlier application table covers families including DVP-SS, DVP-SA, DVP-SX, DVP-SC, DVP-EH, DVP-EH2 and DVP-SV. The accessible program, D/M devices and file registers depend on the CPU group.
The 2016 DVPPCC01 instruction sheet also covers DVP-SS2, DVP-SA2, DVP-SX2, DVP-EH3 and DVP-SV2 groups. However, its compatibility matrix lists DVPPCC01 firmware versions v1.4, v1.6, v2.2 and v2.22 separately. The product name alone does not establish support for every DVP CPU.
Check the source CPU, target CPU and copy module version together. Direct transfer between different generations within the DVP family must not be assumed. A model mismatch or unsupported program capacity can cause writing to be rejected.
Programs, parameters and password conditions
Delta's application manual describes M1085 OFF as copying the program and parameters, and M1085 ON as copying the program only. Check the applicable CPU table for the data areas included. Decide separately whether machine-specific recipes and calibration values should be transferred.
PLC passwords, PLC IDs and subroutine passwords form part of the transfer conditions on systems supporting these features. Correct authentication is required. An enabled copy-count limit may also prevent further writing. An ERR indication therefore does not automatically mean a defective cable.
Plan the maintenance operation with the machine stopped; confirm that the target PLC is in STOP before writing. Use WPLSoft or a CPU-supported version of ISPSoft for project and communication checks. Keep the editable engineering project, comments and revision record separately.
Differences from DVP-512FM and programming cables
Delta DVP-512FM and DVPPCC01 are different model codes and should not be purchased as direct equivalents without verification. DVPPCC01 carries a program/data copy obtained through the PLC. DVP programming cables are selected separately for computer access; a cable such as UC-PRG020-12A must also match the CPU connection requirements.
The manufacturer specifies 10-year data retention and at least 10,000 write operations. The stated operating temperature is 0…55 °C, with storage at −25…70 °C. These ratings do not establish the present condition of an old or used module.
Editor's Note
Start by checking the direction. Reading a backup from a working machine requires RD. Before connecting an unfamiliar module in WR mode, establish which machine its stored copy belongs to and whether that copy is suitable.
Label the backup with its date, machine and CPU code. After a program change, do not leave an older copy on the shelf labelled as current. Include the recipes and calibration values used during commissioning in the maintenance record.
A POWER light alone is not an acceptance test for a used unit. Inspect the plug, cable entry and selector switch for damage or looseness. Ask the seller to demonstrate successful reading and writing with a compatible test PLC.
Validate the backup on a separate test CPU where possible. Use the same model and a suitable version, then compare the program and required data areas through the programming software. Disconnect field loads in the test setup and control any restart.
Do not treat ERASE as a fault reset button. It can clear stored data and also has a RUN/STOP role in certain older CPU applications. Record the ERR and OK light pattern before consulting the matching error table. Keep the only known backup intact while investigating.
Handle the connector by its body. Do not pull the cable or trap it in a cabinet door. With intermittent communication, inspect the connector and cable first; work on a module containing a valuable backup should be a last resort.
PDF manuals and software
Use our Delta PLC accessories PDF and software files page for related documents. Read the firmware compatibility matrix in the DVPPCC01 Instruction Sheet and the copy-card sections of the DVP-PLC Application Manual – Special Modules against the version of your equipment.
Related subjects
For other maintenance equipment, see DVP communication cables, Delta PLC accessories and used Delta PLC models. Select the memory module, computer programming cable and communication accessories according to their separate tasks.
Navigation: Used Delta products | Delta PLC models | PLC accessories | DVP memory accessories | PDF and software files
External references
Delta DVPPCC01 Instruction Sheet, 2016-05-03 | Delta DVP/TP catalogue, 2023 | Delta DVP Special Modules Application Manual, Chapter 11 | Delta DVP-PCC01 legacy instruction sheet, 2006