Delta UC-ET010-33B

Delta UC-ET010-33B — 1 m DB37 I/O Connection Cable

Delta UC-ET010-33B is a 1-metre I/O connection cable with male DB37 connectors at both ends. Within the Delta AH I/O cables range, it connects suitable digital modules to AH external terminals, carrying module signals to the terminal assembly inside the control panel.

Connectors and application

Item UC-ET010-33B
Cable length1 m
Module endMale DB37
External terminal endMale DB37
FunctionConnection between a digital I/O module and an external terminal

The cable routes AH500 module inputs or outputs to an external terminal. The connected module determines signal direction and electrical characteristics. The 37 contacts in a DB37 connector do not represent 37 independent I/O channels. Common and supply connections must also follow the equipment diagram.

Module and terminal combinations in manufacturer documents

AH module Function External terminal
AH32AM10N-5B 32 digital inputs UB-10-ID32B
AH32AN02T-5B 32 NPN (sink) outputs UB-10-OR32A / UB-10-OT32B
AH32AN02P-5B 32 PNP (source) outputs UB-10-OR32B / UB-10-OT32B

The table shows UB-10-OR32A and UB-10-OR32B for relay interfaces, and UB-10-OT32B for transistor-output connections. The relay terminal code differs between NPN and PNP modules. Check the PLC module, terminal assembly and output type together when selecting the cable.

DB37 and MIL connector distinction

AH32AM10N-5B uses a DB37 connection, while the similarly named AH32AM10N-5C uses a MIL connection. The 5B / 5C suffix affects cable and terminal selection.

UC-ET010-24A and UC-ET010-24B use IDC40–IDC40 connections; UC-ET010-24C and UC-ET010-24D use IDC40–two IDC20 connections. These differ from the DB37 arrangement of UC-ET010-33B. A shared one-metre length does not make the cables interchangeable.

Additional code in the manual and wiring checks

The AH Motion hardware manual identifies the cable as UC-ET010-33B (DVPACAB7C10). This documented reference can help when encountering the DVPACAB7C10 code. Check the actual part’s label and both connectors as well.

Read pin numbering using the correct connector viewing direction. Follow the relevant module diagram when repairing or testing the cable. A mechanically matching connector does not establish that another DB37 cable carries the same signal arrangement.

Editor’s Note

Check the module suffix first. Do not confuse AH32AM10N-5B with 5C, and read the terminal code: ID32B, OR32A, OR32B or OT32B. Match the devices at both ends rather than choosing the cable in isolation.

DB37 pins are closely spaced and delicate. Do not force a connector with bent, recessed or corroded pins. Tighten both retaining screws evenly; engaged screws alone do not prove that the connector is fully seated.

Measure the intended route instead of estimating one metre by eye. Include duct routing, bends and removal clearance. A tight installation that loads the cable entry can eventually cause intermittent contact.

Switch off power and disconnect both ends before measurement. Check continuity and unintended shorts using the correct pin view. Remember that front and rear connector views place the numbered contacts differently.

For an input fault, compare the field signal, common connection, module LED and value read by the PLC. For an output fault, check NPN/PNP operation and terminal power. Diagnose the complete path before blaming or ruling out the cable.

For a used cable, one working channel is insufficient. Test the required channels sequentially with suitable equipment. Test outputs under conditions that cannot cause machine movement, and inspect crushed insulation or any spliced sections separately.

PDF and related topics

Use the Delta PLC accessories PDF and software files page for wiring diagrams. Further documentation is available under Delta PLC and HMI manuals and Delta user manuals.

For module selection, review Delta AH digital modules and the Delta AH PLC series.

Navigation: UC-ET010-33B main page · Delta PLC accessories · Delta PLC models · Used Delta products

External references

Delta PLC/HMI Cable Selection Guide — 2-17 / 2-20 / 2-35 · Delta AH Series Catalogue — Accessory Selection, 30–31 · Delta AH Motion Hardware Manual — 3-61