Delta UB-10-OR32B / DVPAETB-OR32B
Delta UB-10-OR32B / DVPAETB-OR32B 32-Relay External Terminal
Delta UB-10-OR32B / DVPAETB-OR32B is a DB37 external terminal board with 32 relay outputs, transferring control signals from a compatible AH output module to field connections. The manufacturer's hardware manual lists both codes as alternative names. It belongs to Delta AH external terminals and Delta PLC accessories.
AH32AN02P-5B and cable matching
The specified module is AH32AN02P-5B. Its PNP / Source transistor outputs control the relays through the appropriate terminal. The catalogue shows UC-ET010-33B for this connection; legacy AH documents also list the DB37 cable as DVPACAB7C10. Compare complete codes, pin assignments and connector orientation when replacing a cable.
Preserve the 5B suffix when selecting Delta AH PLC series and Delta AH digital modules. AH32AN02P-5C uses a different MIL connector and is paired with an OR16B terminal in the manufacturer's table.
Relay outputs, power and common terminals
The AH catalogue lists 32 relay outputs, 240 V AC / 24 V DC and 2 A for UB-10-OR32B. Assess the PLC module's transistor-output rating separately from the external relay-contact rating. Check load type, starting current and total common-terminal loading against the applicable wiring and relay limits.
The terminal drawing identifies +24V and GND supply connections and C0–C7 common groups. Each common serves four outputs. For example, AH addressing associates C0 with Y0.0–Y0.3 and C7 with Y1.12–Y1.15. Compare the board markings with the actual I/O addresses in the CPU project.
Relay power, control signals and load contacts have separate functions. Supply loads through the relay Y/C terminals rather than the DB37 control connections. Plan common-terminal bridges, fuses and inductive-load suppression for the actual voltage and load arrangement. Do not infer a 64 A simultaneous load capacity by multiplying 32 channels by 2 A.
OR32A, OR16B, OT32B and ID32B distinctions
UB-10-OR32A / DVPAETB-OR32A is paired with the AH32AN02T-5B NPN / Sink module. Do not select OR32A or OR32B solely by relay count or DB37 appearance; the control-side output direction determines the correct pairing.
UB-10-OR16B / DVPAETB-OR16B belongs to the 16-relay MIL connection group. UB-10-OT32B / DVPAETB-OT32B is used for transistor-output connections, while UB-10-ID32B / DVPAETB-ID32B is a digital-input terminal. Assess these functions separately under Delta external terminals.
Installation, wiring and software
The manufacturer's drawing gives dimensions of 215 × 87 × 39.4 mm. Check the DIN-rail clip and fixing components. Allow for DB37 cable bends, access to relay terminals and cable-duct clearance in the cabinet layout.
Review connections under Delta AH I/O cables and Delta DVP / AH I/O cables. No independent program or firmware is loaded into the terminal. CPU/module configuration and output addressing in Delta ISPSoft depend on the AH system being used.
Editor's Note
Check the B suffix on the label. Thirty-two relays and a matching socket appearance are insufficient; verify the AH32AN02P-5B pairing. Record the hardware revision and board label when comparing UB-10 and DVPAETB designations.
Label output wiring and common groups before removal. Field loads may use a separate supply, so isolate the relevant circuits and verify absence of voltage at the terminals being serviced.
If four outputs fail together, check the relevant common terminal, fuse and field supply. For a board-wide fault, inspect +24V/GND power, the DB37 cable and PLC output status together.
A clicking relay does not prove that its contact is sound. Observe actual load operation in a safe test arrangement and assess welded contacts, high contact resistance and intermittent operation separately.
Inspect a used board for overheated terminals, corrosion, loose connectors and relay solder joints. Replacement relays must match coil voltage, contact arrangement, pin layout and load category; housing size alone is insufficient.
PDF and wiring documentation
Consult Delta PLC accessories files and Delta PLC and HMI manuals for relevant documents. The AH Motion Controller Hardware Manual lists alternative codes and module matching; the AH500 Hardware Manual covers terminal arrangement and load wiring. The PLC/HMI cable guide shows the connection on printed page 2-20 and terminal layout on 2-36 / Figure 10.
Related topics
Delta AH32AN02P-5B · Delta UC-ET010-33B · Delta DVPACAB7C10 · Delta UB-10-OR32A / DVPAETB-OR32A · Delta UB-10-OR16B / DVPAETB-OR16B · Delta UB-10-OT32B / DVPAETB-OT32B
Return to Delta PLC accessories. Browse controllers in the Delta PLC category and available equipment under second-hand Delta products.
External references: Delta AH Series Catalogue · Delta AH Motion Controller Hardware Manual (archived manufacturer document) · Delta PLC/HMI Cable Selection Guide