Delta UB-10-ID32B / DVPAETB-ID32B

Delta UB-10-ID32B / DVPAETB-ID32B 32-Point Input Terminal Module

Delta UB-10-ID32B, also identified as DVPAETB-ID32B, is a 32-point input terminal module with a DB37 connection for the AH32AM10N-5B digital input module. In a Delta AH PLC system, it brings sensor, pushbutton and limit-switch wiring to screw terminals and carries the signals to the input module through the appropriate I/O cable.

This Delta PLC accessory exposes the connected module's existing inputs for field wiring. It does not increase the PLC input count independently; program addresses and input characteristics depend on the AH module.

Construction and cable selection

Connections: A DB37 connector, 32 input signal terminals and four S/S common-terminal positions. The manufacturer's drawing gives body dimensions of 113 × 87 × 50.8 mm and shows DIN rail clips and base securing screws.

Compatible cable: UC-ET010-33B, also listed as DVPACAB7C10 in the hardware manual, is a 1 m I/O cable with male DB37 connectors at both ends. The documented combination is AH32AM10N-5B + this cable + UB-10-ID32B. See AH I/O cables and DVP / AH I/O cables for other connection arrangements.

24 V DC inputs and the S/S common

The manual describes the connected AH32AM10N-5B input circuit as 24 V DC, 5 mA, sinking or sourcing. The 5 mA value concerns the input circuit, rather than the total consumption of the terminal board. Select sensor outputs and supply connections within the input module's electrical limits.

With a PNP sensor output supplying positive voltage to an input, connect the S/S common to 0 V. With an NPN sensor output pulling the input to 0 V, connect S/S to +24 V. Apply the same current-path principle to dry contacts. Do not connect repeated S/S terminals to different potentials on the assumption that they represent independent input groups; follow the manufacturer's diagram.

Terminal labels and AH address mapping

The upper row starts X0, X2, X4, while the lower row starts X1, X3, X5. The label sequence continues from X7 to X10 and ends at X37. The manual's AH equivalent uses X0.0–X0.15 for the first 16 inputs and X1.0–X1.15 for the next 16.

For example, board label X10 corresponds to AH notation X0.8, while X20 corresponds to X1.0. These are the manual's mapping examples; confirm the actual starting address in the project's module configuration. Treating a terminal label as a literal program address can shift the channel assignment.

Related terminals and model differences

UB-10-ID32A / DVPAETB-ID32A is an input terminal with a 40-pin MIL connection. Its AH combinations include AH32AM10N-5C and AH64AM10N-5C, using MIL cables such as UC-ET010-24A. Keep this arrangement distinct from ID32B's DB37 connection.

UB-10-OT32B / DVPAETB-OT32B is a transistor output terminal; UB-10-OR32A / DVPAETB-OR32A and UB-10-OR32B / DVPAETB-OR32B are relay output terminals. A similar DB37 connector does not make these products interchangeable with an ID32B input terminal.

Editor's Note

If inputs are missing, start with the sensor's NPN or PNP output type and the S/S connection. An incorrect common connection can make both a healthy sensor and a healthy PLC input appear faulty.

When every input disappears together, prioritize the shared supply, S/S connection and DB37 cable. Distinguish a single-channel fault from a board-wide problem before replacing components.

Test channels individually in a safe test arrangement. Record the terminal label, PLC input LED and monitored software address together; the X7–X10 transition is an easy place to introduce an indexing error.

On a used terminal, inspect DB37 pins, connector screws, terminal threads, corrosion and cracked solder joints. Investigate the connection separately if gentle cable movement makes a signal intermittent.

Before continuity testing, isolate power, disconnect both cable ends and separate the circuit from connected electronics. Do not use an insulation tester with the PLC or sensors connected, or apply voltage to unidentified pins.

Route long sensor cables separately from motor and drive power wiring. For intermittent input states, check the 24 V supply, sensor return, loose connections and electrical interference before replacing the terminal.

PDF documents, software and related topics

Visit Delta PLC accessories PDF and software files for wiring documentation. Read the terminal drawing together with the connected AH input module's S/S wiring diagram.

Related topics: AH external terminals + AH digital modules + AH expansion modules.

Navigation: Delta products + Delta PLC models.

External references

Delta AH catalogue (accessory selection); Delta PLC/HMI Cable Selection Guide (2-3, 2-17 and 2-35 / Figure 7); Delta AH Motion Hardware Manual (3-61, 3-62, 3-76 and 4-74).