Delta DVP ‑H modules are right-side special-function expansion units documented for the original Delta DVP-EH series. They add analogue input, analogue output, temperature measurement, high-speed counting or single-axis positioning to a compatible PLC. Start with the field signal. Reading a sensor, sending a reference to a drive, counting encoder pulses and commanding an axis are distinct PLC I/O functions.
Module selection table · Compatibility and programming · PDF files
Eight ‑H modules at a glance
| Model | Function and selection details | Module ID |
|---|---|---|
| DVP04AD-H | Four analogue inputs, 14-bit measurement. Catalogue ranges of ±10 V or ±20 mA. | 0x0400 |
| DVP04DA-H | Four analogue outputs, 12-bit. Catalogue ranges of 0–10 V or 0–20 mA. | 0x0401 |
| DVP06XA-H | Four analogue inputs and two analogue outputs. Measurement and reference signals in one unit. | 0x0604 |
| DVP04PT-H | Four temperature inputs for three-wire Pt100 sensors. | 0x0402 |
| DVP04TC-H | Four thermocouple inputs. Select J, K, R, S or T for the sensor on each channel. | 0x0403 |
| DVP01PU-H | Single-axis positioning. Differential pulse output rated up to 200 kHz in the catalogue. | 0x0110 |
| DVP01HC-H | Single-channel high-speed counter. Select the terminal appropriate for a 5 V, 12 V or 24 V signal. | 0x0120 |
| DVP02HC-H | Two-channel high-speed counter. The catalogue lists a 24 V input level. The count limit depends on the selected mode. | 0x0220 |
Analogue measurement, drive references and temperature
AD reads measurements, DA sends references, and XA combines both in one unit. Consider AD to read the analogue signal from a pressure transmitter, or DA to send a speed reference to a variable frequency drive. For 0–10 V and 4–20 mA applications, check the channel mode, field terminal and PLC scaling together. Record which pressure or level value corresponds to 4 mA.
Choose PT or TC according to the sensor. DVP04PT-H uses three-wire Pt100 sensors. With DVP04TC-H, check the thermocouple’s type, polarity and extension cable. The differences between Pt100 and thermocouples determine the wiring and measurement method. Match the TC channel setting to the sensor type and compare the indicated temperature with a known reference during commissioning.
PU sends commands and HC counts incoming pulses
DVP01PU-H supplies a pulse command to one axis. When selecting the drive for a stepper motor or servo motor, check its pulse input type, wiring arrangement and frequency limit. Record the direction, speed and position settings from the existing PLC project.
DVP01HC-H and DVP02HC-H count signals from an encoder or another suitable pulse source. In addition to the channel count, check the A/B phases, input voltage and differential encoder wiring. When evaluating the 200 kHz catalogue ceiling, check the counting frequency allowed by the selected mode.
CPU compatibility, software and FROM/TO access
Delta lists separate module IDs for ‑H, ‑H2 and ‑H3. For example, DVP04AD-H has ID 0x0400 and DVP04AD-H2 has ID 0x6400. When planning a replacement, check the full CPU ordering code, hardware revision, module order and the module’s CR register map. For DVP-EH2 and DVP-EH3 systems, consult the manufacturer tables linked from the ‑H2 and ‑H3 pages.
Start with WPLSoft for an original EH project. If using ISPSoft, verify CPU support in the installed version. In the PLC program, FROM reads module data and TO writes settings or commands. Back up the Ladder project and match the module number and CR address to the manual for the exact model.
Editor’s Note
Ask for both label photos when buying used. Get a clear view of the CPU code and the module code, including the final ‑H, ‑H2 or ‑H3 suffix.
Record the module order before removal. Photograph the module’s position relative to the CPU and its terminal numbers. Find the module number used in the program’s FROM/TO calls.
Test an analogue channel at two points. Apply known low and high signals and check both the raw value and the displayed engineering units.
Check the counter direction. Use a known pulse count or one controlled revolution to compare A/B direction and program scaling.
Start with a bench test. Disconnect machine loads and inspect the 24 V DC cabinet supply, connectors and protective grounding. Confirm that the PLC identifies the correct module before enabling the motion system.
Internal references and PDF files
Delta DVP PLC PDF files · Hardware catalogues, special module guides and programming documentation.
All DVP expansion modules · DVP EH digital expansion modules · Delta PLC models · Used Delta equipment
External references
Delta DVP technical catalogue · Channel and signal tables for all eight ‑H models on PDF pages 20–21.
Delta DVP special modules application manual · Wiring and CR tables for analogue, temperature, positioning and high-speed counter modules.
Delta DVP programming manual · ‑H, ‑H2 and ‑H3 module IDs on PDF page 142.