Delta DVP04TC-H Thermocouple Temperature Measurement Module

Delta DVP04TC-H is a four-channel thermocouple temperature measurement module for DVP-EH PLC systems. Among PLC input and output modules, it provides temperature acquisition. It accepts J, K, R, S or T thermocouples; a suitable temperature sensor can monitor furnaces, extruders and process heating zones.

Sensor types and measurement ranges

Type J: −100 to +700 °C. Type K: −100 to +1000 °C. Types R and S: −10 to +1700 °C. Type T: −100 to +350 °C. The thermocouple type is selected separately for each channel. Match the sensor and compensating cable to the applicable thermocouple standards.

The sensor’s analog signal is processed by the analog input circuit and a 14-bit ADC. Celsius registers use 0.1 °C per count: 1000 means 100.0 °C; −200 means −20.0 °C. Resolution and overall measurement accuracy are different specifications. The stated response time is 200 ms × number of channels, approximately 800 ms for four channels.

Power: External 24 V DC, allowable range 20.4–28.8 V DC, maximum consumption 2.5 W. Include sensor-related equipment when sizing the DC supply and current budget. The analog and digital sections are isolated; individual input channels are not isolated from one another.

CPU compatibility and module number

This page covers the original −H generation DVP04TC-H. In the manufacturer’s coding, H identifies the DVP-EH host family. Check the PLC CPU model, expansion connection and hardware generation together. DVP04TC-H2 is a separate model; consult the actual CPU’s expansion compatibility table for an H2/EH3 replacement project.

The module occupies no digital X/Y points. FROM/TO uses a special-module number from 0 to 7, starting with 0 for the nearest special module to the CPU. Other special modules affect this numbering. The identification value in CR#0 is H0403.

Programming software and cable

Configure the module through FROM/TO instructions in the host program. Use WPLSoft for DVP-EH projects. For ISPSoft, verify that the installed version supports the actual CPU model. The module does not receive a separate ladder program.

Use a DVPACAB2A30 cable between the PC and the EH CPU programming port. This is an RS-232 connection. A USB-only PC requires a suitable USB-to-RS-232 converter, its driver and the correct COM-port selection. Preserve the CPU port pinout; matching connectors alone do not establish electrical compatibility.

Control registers and reading example

CR#1: sensor-type selection. CH1 uses b2–b0, CH2 b5–b3, CH3 b8–b6 and CH4 b11–b9. Codes are 0 = J, 1 = K, 2 = R, 3 = S, 4 = T. Selecting type K on all four channels gives H0249. For module number 0, write it under a first-scan condition using TO K0 K1 H0249 K1.

CR#2–#5: averaging counts per channel, range 1–20, factory setting 10. CR#6–#9: averaged Celsius readings. CR#14–#17: present Celsius readings. For example, FROM K0 K6 D100 K4 reads four averaged temperatures from module 0 into D100–D103. Read CR#30 error status with FROM K0 K30 D110 K1. These D addresses are application-selected storage locations.

Sensor wiring and RS-485

Connect each thermocouple with correct polarity to its channel’s L+ and L− terminals. SLD is the shield/noise-suppression connection. Use compensating cable suitable for the sensor and follow the manufacturer’s wiring diagram for shielding and grounding. Separate sensor wiring from motor and power cables, and keep the terminal block away from strong heat sources.

For independent operation, the module supports ASCII/RTU Modbus RS-485 communication. The module’s RS-485 communication is disabled when it is connected to the CPU through the expansion bus. Expansion-bus access and independent serial access are not simultaneous communication paths.

The difference between Pt100 and thermocouples matters when selecting inputs. A Pt100 sensor requires suitable RTD hardware such as DVP04PT-H. For PID control with a PLC, temperature can provide feedback; an appropriate PLC output and power device operate the heater.

Editor’s Note

When buying a used module, confirm DVP04TC-H on the label and check the suffix carefully. Inspect the terminal block, expansion connector, locking parts and signs of corrosion.

Test every channel separately with a suitable thermocouple simulator. In type K mode, 0/100/300 °C should produce approximately 0/1000/3000. Set the simulator’s cold-junction compensation and test cable correctly.

For drifting readings, check sensor selection, polarity, junctions and 24 V power first. Do not hide wiring problems with OFFSET adjustments or change calibration values without a verified reference.

During PLC debugging, read the module identification from CR#0 and errors from CR#30. Separate power, input-range, mode-selection and averaging errors. Test the heater command’s response to a disconnected sensor under controlled conditions.

Write averaging settings at startup or when settings change rather than on every scan. More averaging slows the response. Back up the program, CR settings and any independent RS-485 communication settings before making changes.

PDF manuals

Start with our Delta DVP PLC files page. The model-specific reference is the English DVP04TC-H Thermocouple Sensors Instruction Sheet, 5011639500-4TE0, dated 20 October 2005. Do not substitute an H2 manual for this model without checking its scope.

Related topics

Browse Delta DVP-H modules and DVP expansion modules for the hardware group. DVP04TC-S and DVP04TC-E2 belong to different expansion families; similar functions do not establish physical interchangeability.

Delta DVP PLC series | DVP04TC-H model page | DVP file archive

External references

Delta DVP04TC-H manufacturer instruction sheet — English archive copy | Delta programming-cable guidance — DVPACAB2A30