Delta DVP04AD-H

Delta DVP04AD-H 4-Channel Analog Input Module

The Delta DVP04AD-H is a four-channel analog input module for compatible DVP-EH PLC main units. It converts external voltage or current signals into digital data. Its basic input ranges are −10 to +10 V and −20 to +20 mA; the channel mode must match the field wiring. This model does not generate analog outputs.

Use our Delta DVP PLC files page for wiring diagrams and control-register information. Preserve the -H suffix when identifying the module: DVP04AD-H2 and DVP04AD-H3 belong to different generations. Similar connectors alone do not establish CPU compatibility or identical parameter behaviour.

Input range, resolution and measurement characteristics

Voltage conversion uses 14 bits, 1.25 mV/LSB and −8000 to +8000; current conversion uses 13 bits, 5 µA/LSB and −4000 to +4000 as its basic specifications. Describing every input type simply as “14-bit” misses this distinction. For analog signals and 0–10 V / 4–20 mA applications, also check the selected mode's conversion curve.

Input impedance is above 200 kΩ for voltage and 250 Ω for current. Conversion time is 3 ms × the number of channels, giving approximately 12 ms for four channels before averaging and PLC scan effects. The analog and digital sections are isolated, but the analog channels are not isolated from each other.

Pressure sensors, temperature transmitters and analog controllers can connect through suitable electrical outputs. Direct thermocouple or Pt100 measurement requires the appropriate module, such as DVP04TC-H or DVP04PT-H. A conventional switching-output inductive sensor or photoelectric sensor is not a substitute for an analog voltage/current source.

Power supply and terminal wiring

The module requires an external 24 V DC supply, with a specified operating range of 20.4–28.8 V DC. Include module and field-device consumption when selecting a power supply. When using DIN rail power supplies, distinguish the module's supply terminals from its analog signal inputs.

For voltage measurement, connect the signal between V+ and COM. For current measurement, bridge V+ and I+ and connect the loop through the appropriate input and COM terminals according to the manufacturer's diagram. A two-wire transmitter also needs its external loop supply completed. Do not treat COM, FG and supply 0 V as interchangeable terminals.

Route shielded signal wiring appropriately away from variable frequency drive, contactor and relay load wiring. Consider control panel components, shield connections and suitable supply fuse protection together. Because channels lack individual isolation, review common connections carefully when devices operate at different ground potentials.

CPU compatibility and module numbering

The original instruction sheet identifies DVP04AD-H as a DVP -H special module used through a DVP-EH main-unit program. For another CPU generation, check that CPU's supported expansion modules table. Do not assume compatibility across every DVP family.

Special modules are assigned K0–K7 according to their distance from the CPU; the stated limit for this arrangement is eight special modules. Analog modules do not occupy digital X/Y points. CR#0 contains model code H0400, which can be read to check module presence and generation.

Programming software and programming cable

No separate PLC program is downloaded to DVP04AD-H. Use a CPU-compatible version of WPLSoft or ISPSoft. The CPU program writes settings with TO and reads measurements or status with FROM. In ISPSoft, select the correct CPU and COMMGR connection; the analog module is not the project's CPU type.

Delta identifies DVPACAB2A30 as the PC communication cable for suitable DVP PLC RS232 programming ports. If the computer lacks RS232, use a suitable USB-to-RS232 converter and driver to provide a COM port. Select the Delta PLC programming cable for the CPU's actual port. Sensor wiring and the module's D+/D− RS485 terminals serve different purposes from CPU programming.

Channel modes and FROM/TO example

CR#1 selects channel modes: Mode 0: −10 to +10 V; Mode 1: −6 to +10 V; Mode 2: −12 to +20 mA; Mode 3: −20 to +20 mA. Each channel uses three setting bits. On the standard Mode 2 curve, 4 mA corresponds to zero and 20 mA to 4000; in Mode 3, 4 mA is approximately 800. Choose scaling from the actual curve rather than the “4–20 mA” label alone.

For a module at K0, TO K0 K1 H0000 K1 selects Mode 0 for all four channels and can be executed once during initialization. FROM K0 K6 D100 K4 reads the four averaged inputs into D100–D103. FROM K0 K30 D110 K1 reads error status into D110. Change K0 to match the actual module position and review the example before applying it to an existing machine.

CR#2–CR#5 configure averaging; CR#6–CR#9 hold averaged measurements; CR#12–CR#15 hold present values; CR#30 reports errors. Results can be converted into engineering units for an HMI panel or SCADA. Recheck the raw-value calculation if OFFSET/GAIN settings have changed.

RS485 operation and related models

Independent serial access supports Modbus ASCII or Modbus RTU. However, the manufacturer states that RS485 cannot be used while the module is connected through the CPU expansion bus. Do not assume simultaneous CPU FROM/TO access and independent serial access. Our Modbus communication guide explains the addressing concepts.

The DVP04DA-H provides analog outputs, while DVP06XA-H provides mixed analog I/O. Their duties differ from the DVP04AD-H's four-input function. Compare signal direction, CPU support, terminal layout and conversion curves when considering a replacement.

Editor's Note

Confirm the complete -H suffix when buying a used module. Do not treat H2 or H3 as the same device. Record the CPU model, module order and existing FROM/TO instructions together.

Begin a bench test with one channel and a known working calibrator. Check 0, 5 and 10 V for voltage, or 4, 12 and 20 mA for current. Match the calibrator's source/simulate setting to the actual current-loop arrangement.

If current is not being read, check the V+–I+ bridge, loop supply and COM return before condemning the module. A bridge left in place during voltage measurement can also disturb readings. Wiring and CR#1 must describe the same operating mode.

If a reading is doubled or shifted, inspect the input mode and OFFSET/GAIN registers first. Do not use calibration to conceal incorrect scaling. Establish how the program converts raw values into engineering units.

If one channel affects another, investigate shared returns and ground potential differences. These channels are not individually isolated. Eliminate shielding and supply problems before replacing board components.

Read CR#30 when the ERROR indicator is active and record the corresponding error bits. Back up both the program and module parameters before changing persistent settings, and consider how measurement changes affect the process.

Related topics and files

Delta DVP PLC series · DVP -H modules · DVP expansion modules · Delta DVP PLC manuals and PDF files.

External references

Delta analog conversion and resolution explanation · Delta PC communication cable explanation · Delta DVP04AD-H 2004 instruction sheet, archived manufacturer document.

Delta DVP04AD-H | Delta PLC | DVP PLC files