Delta DVP04PT-H
Delta DVP04PT-H – 4-Channel Pt100 Temperature Module
Delta DVP04PT-H is a temperature input module for the DVP-EH family, accepting four 3-wire Pt100 probes. It converts resistance changes from temperature sensors into digital data for the PLC program. A Pt100 element measures 100 Ω at 0°C; select the correct probe type and three-wire connection together.
Range, resolution and power
The specified range is -200 to +600°C, represented by -2000 to +6000 with 0.1°C resolution. The 14-bit conversion is read as signed temperature data. For example, 250 = 25.0°C and -105 = -10.5°C. Displaying one decimal place does not establish ±0.1°C measurement accuracy.
Supply the module with 24 V DC; the permitted range is 20.4–28.8 V DC. Analog and digital sections are isolated, but channels are not isolated from each other. The stated response is 200 ms × channel count, approximately 800 ms for four channels. Averaging and PLC polling add to the displayed response. Observe the probe’s own temperature and environmental limits.
Three-wire Pt100 connection
Each channel uses L+, L- and I-. Connect the two wires from the same end of the Pt100 element to L- and I-, and the wire from the opposite end to L+. Verify the probe diagram and disconnected resistance measurements instead of relying on wire colors alone. Match lead size, length and connection quality for lead-resistance compensation.
Separate shielded sensor wiring from motor and power cables. Connect FG and protective earth according to the manufacturer diagram. Grounding, electromagnetic interference and noise immunity affect measurement stability. Do not apply external voltage to sensor inputs or use terminals marked as unconnected.
PLC connection, software and programming cable
Connect the DVP04PT-H to the right-side extension bus of a compatible CPU system. Special modules are numbered 0–7 by their distance from the main unit. The module occupies no digital X/Y points. When moving legacy -H hardware to an EH2/EH3 system, verify the CPU module support, supply budget and existing program.
Prepare the host program in WPLSoft or ISPSoft and access CR control registers with FROM/TO instructions. Connect the PC to the main PLC. For a DVP-EH COM1 RS-232, 8-pin mini-DIN port, use a suitable DVP cable such as DVPACAB230. A PC without a serial port needs a USB-to-RS-232 adapter and its driver. In ISPSoft, select the COMMGR serial driver with the correct COM port and communication settings.
CR registers and reading example
CR#0 identifies the module as H0402. CR#2–#5 set channel averaging; CR#6–#9 contain averaged Celsius readings; CR#18–#21 contain present Celsius readings. CR#30 holds errors and CR#34 the firmware version. CR#1 is reserved on this model; do not write another generation’s sensor-type setting there.
For the first special module, FROM K0 K6 D100 K4 reads the four averaged temperatures into D100–D103. Change K0 to match the actual module position. Divide readings by 10 for display and use signed data for negative temperatures. More averaging can reduce fluctuations while delaying the display of real changes.
Standalone RS-485 communication
The D+ / D- terminals support Modbus ASCII/RTU. In standalone use, CR#31 sets the station address and CR#32 the communication format and speed. Match the address, serial format and register mapping before reading from SCADA or another master.
The module’s RS-485 port cannot be used while it is connected to the main PLC through the extension bus. Do not design the bus and standalone serial interface as simultaneous access paths. Publishing readings through the main PLC’s communication port is a separate approach.
Other temperature and analog modules
Pt100 and thermocouples use different measurement methods. A thermocouple requires a suitable module such as DVP04TC-H. A transmitter’s analog current or analog voltage output requires an analog input matching its range. Establish the analog signal type and analog I/O function before ordering.
DVP04PT-H2 is a separate generation, identified as H6402. Do not transfer H2 or S-series sensor options, ranges or special functions to the legacy H model. A PID controller implemented in the PLC program can use the readings as feedback. For heating PID control, provide the control calculation and output hardware separately. Do not apply S-series built-in PID registers to this module.
Safety and technical files
Handle temperature errors and broken probes explicitly in the control program. Design the emergency stop and required safety relay arrangement according to the machine risk assessment. Assess independent overtemperature protection where heaters are used.
Use Delta DVP PLC files for wiring and CR documentation. Some averaging and power-consumption details differ between the early sheet and later application manual. Match setting limits to the module label, firmware and applicable document edition.
Editor's Note
Start with the probe when the displayed temperature is wrong. Pt100, thermocouple and NTC sensors differ. Confirm the label and three-wire connection before concluding that the card is faulty.
Disconnect probe leads from the module before checking resistance with power removed. Ohm’s law and resistance measurements help with basic checks; use a calibrated Pt100 simulator for precise channel testing and reproduce the three-wire circuit correctly.
Test all four channels of a used module separately with the same reference. One successful channel test does not validate the others. Establish whether the displayed value is averaged or present temperature.
For unstable readings, inspect cable joints, loose terminals, shielding and proximity to power cables. Do not conceal a broken or weak connection by increasing averaging.
Back up the program and CR settings before initialization. Verify heater shutdown on a sensor fault under controlled conditions. Remove all supplies before disconnecting the module or its extension connection.
Related topics and navigation
Delta DVP-H modules · DVP04TC-H · DVP04PT-H2 · DVP expansion modules · DVP PLC series · DVP PLC files
External manufacturer documents
Delta DVP04PT-H Instruction Sheet, 2004, EN · Delta DVP Special Modules Application Manual, 2013, Chapter 4, EN · Delta WPLSoft / ISPSoft FAQ